Fire Engineering Glossary

Technical terms spanning standards, manufacturers, commissioning, networking, testing and fault finding.

Technical guidance only. Confirm current project requirements against the applicable standards, legislation, system documentation and site-specific fire strategy.

Showing 22 of 22 matching glossary entries.

Fire detection

Addressable system

A fire alarm system in which each device has a unique address, letting the panel identify exactly which detector, call point or interface generated an event.

Makes fault-finding far faster than conventional zones — always keep the device schedule current.

Fire detection

Class A wiring

Ring wiring returned to the panel so devices stay in communication from the other direction after a single break.

Fire detection

Class B wiring

Radial (spur) wiring; devices beyond a break are lost, so a break shows as multiple missing devices downstream of one point.

Fire detection

Commissioning

The systematic proving of a completed installation against the design: device tests, cause-and-effect verification, sound levels, battery calculations and documentation.

Fire detection

Conventional system

A fire alarm system arranged in radial zones where the panel knows the affected zone but not the individual device.

Diagnosis relies on the zone chart and physically checking each device in the zone.

Fire detection

Detection zone

The area covered by a group of detection devices reported together, sized and bounded so responders can locate the origin of an alarm quickly.

Fire detection

Disablement

A deliberate, indicated inhibition of a device, zone or output at the panel; a controlled impairment that must be recorded and reinstated.

Isolations left over from previous visits are a classic 'why didn't it work' finding.

Fire detection

Double knock

Cause-and-effect logic requiring a second confirming trigger (same or second device) before a critical output such as plant shutdown or release operates.

Emergency lighting

Duration test

A full rated-duration discharge of emergency lighting with every luminaire inspected at the end of the period, when failing batteries drop out.

Schedule so the building can tolerate discharged batteries during the recharge that follows.

Standards & law

EN 54 series

The European product standards for fire detection and alarm system components — panels, power supplies, detectors, call points, sounders, isolators and radio devices each have their own part.

Standards & law

EN 54-23

The EN 54 part covering visual alarm devices (VADs), including the coverage classification system used to select and site them.

Fire detection

End-of-line device

The resistor, capacitor or active unit at the end of a monitored circuit that lets the panel supervise the wiring for open and short circuit faults.

Fire detection

Fire alarm category (L/P/M)

The UK convention describing system objectives: L categories protect life, P categories protect property, M is manual-only; the category drives detection coverage.

Confirm the category from the design documentation before judging coverage — never assume.

Interfaces

Interface unit

A monitored input/output device connecting the fire system to other building systems — plant, dampers, lifts, security — under cause-and-effect control.

Fire detection

Isolator module

A loop device that disconnects a faulted section (typically a short circuit) so the remainder of the loop keeps operating.

When the panel shows 'isolator operated', the isolated section is your search area.

Fire detection

Loop

The two-wire circuit connecting addressable devices to the panel, normally wired as a ring so devices remain in communication from either direction if the ring is broken at one point.

Fire detection

Manual call point

The break-glass device that lets an occupant raise the alarm manually; tested with the manufacturer's key so the frangible element is not broken.

Power & batteries

Quiescent current

The current a system draws in normal standby, from panel and all devices together; the first input to any battery calculation.

Loop devices often dwarf the panel's own figure — never use the panel datasheet alone.

Fire detection

Soft addressing

Assigning device addresses from the panel or programmer rather than physical switches; convenient, but replacements must be re-addressed deliberately.

After a soft-addressed replacement, run the device list and check for duplicates.

Fire detection

Visual alarm device (VAD)

A flashing warning device providing visual alarm indication, selected and sited using its rated coverage classification.

Fire detection

Walk test

A one-engineer test mode where activated devices register at the panel (often without outputs) so devices can be proven while walking the site.

Always confirm test mode is cancelled before leaving — a panel left in test cannot raise a real alarm normally.

Fire detection

Zone chart

The diagram at the panel showing zone boundaries and device locations so a stranger — fire officer or relief engineer — can locate any event quickly.