Power & batteriesBattery charger fault
A panel indication that the charging circuit or the batteries are outside limits — aged batteries, poor connections or a failed charger stage.
Check battery date codes and terminal voltage under load before condemning the charger.
Standards & lawCompetent person
A person with the training, experience and knowledge to carry out the task safely and correctly — the basis on which standards allocate design, installation and maintenance duties.
Fire detectionDouble knock
Cause-and-effect logic requiring a second confirming trigger (same or second device) before a critical output such as plant shutdown or release operates.
SignallingDual-path signalling
Alarm transmission over two independent paths (e.g. IP plus radio) so a single path failure does not silence the site; both paths need testing.
Emergency lightingDuration test
A full rated-duration discharge of emergency lighting with every luminaire inspected at the end of the period, when failing batteries drop out.
Schedule so the building can tolerate discharged batteries during the recharge that follows.
Emergency lightingEscape route lighting
Emergency lighting arranged to illuminate escape routes and exits so occupants can leave safely on supply failure.
SecurityFail-safe / fail-secure locking
Whether an electrically controlled lock releases (fail-safe) or stays locked (fail-secure) on power loss — chosen per door from escape and security requirements.
Escape routes generally demand fail-safe behaviour; confirm against the fire strategy.
Smoke controlFail-safe state
The position equipment adopts on power or signal loss — open or closed varies by design strategy, so confirm the intended state before judging behaviour a fault.
Emergency lightingFunctional test
A brief regular test proving each emergency luminaire operates on supply failure — proves function, not duration.
Emergency lightingMaintained luminaire
An emergency luminaire that is lit in normal use and remains lit on mains failure.
Emergency lightingNon-maintained luminaire
An emergency luminaire that lights only when the normal supply fails.
Fire detectionPhased evacuation
An evacuation strategy where areas evacuate in stages rather than simultaneously, driven by the cause-and-effect programme and voice alarm or staged signals.
Standards & lawRegulatory Reform (Fire Safety) Order 2005
The primary fire safety legislation for most non-domestic premises in England and Wales, placing duties on the responsible person including maintenance of fire safety systems.
Legislation — a legal duty, distinct from the recommendations of a code of practice.
Standards & lawResponsible person
The duty holder for fire safety in a premises under UK fire safety legislation, responsible for ensuring the system is maintained and impairments are managed.
Smoke controlSmoke damper
A powered damper in ductwork controlled to restrict smoke movement; the test is trigger → movement → position feedback, not just a status LED.
Power & batteriesStandby battery calculation
Sizing batteries from standby current × standby duration plus alarm current × alarm duration, with the required safety margin, rounded up to a standard battery size.
SecurityVideo management system (VMS)
The software managing CCTV recording, display and analytics; the place to verify retention, analytics behaviour and failure alerts.