Showing 9 of 9 matching glossary entries.
Power & batteriesBattery charger fault
A panel indication that the charging circuit or the batteries are outside limits — aged batteries, poor connections or a failed charger stage.
Check battery date codes and terminal voltage under load before condemning the charger.
Fire detectionCause and effect matrix
The site-specific document mapping every alarm input to its required outputs (sounders, dampers, doors, plant, signalling); the reference for commissioning and testing.
An unversioned or missing matrix is a defect worth reporting in its own right.
Fire detectionEnd-of-line device
The resistor, capacitor or active unit at the end of a monitored circuit that lets the panel supervise the wiring for open and short circuit faults.
SecurityGraded intruder system
An intruder alarm specified to a grade matching the assessed intruder skill and risk, driving supervision, tamper and signalling requirements.
Check insurer requirements before modifying anything on a graded system.
InterfacesInterface unit
A monitored input/output device connecting the fire system to other building systems — plant, dampers, lifts, security — under cause-and-effect control.
Fire detectionIsolator module
A loop device that disconnects a faulted section (typically a short circuit) so the remainder of the loop keeps operating.
When the panel shows 'isolator operated', the isolated section is your search area.
Fire detectionLoop
The two-wire circuit connecting addressable devices to the panel, normally wired as a ring so devices remain in communication from either direction if the ring is broken at one point.
Smoke controlSmoke damper
A powered damper in ductwork controlled to restrict smoke movement; the test is trigger → movement → position feedback, not just a status LED.
SecurityTamper circuit
Supervision detecting opening or removal of security equipment, active whether the system is set or unset.