25 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from. EMS Ltd's FireCell wireless fire detection system: a Radio Hub and Radio Cluster Communicators (RCCs) that pass wireless device data to a host fire alarm control panel over loop connections.

Fault records

25 records

Aerial Tamper

Not yet verified

Hub/RCC fault status: Aerial Tamper (also the front-plate Fault LED)

In the Hub/RCC Fault Status menu, this indicates a remote aerial on the RCC or Radio Hub is not attached or is damaged (monitoring resistance of 47 kΩ not present). The manual separately notes the Radio Hub's front-plate yellow Fault LED illuminates constantly for this same aerial tamper condition.

Sourced — not yet independently verifiedFireCell Programming Guide, p. pp.25-26, p.11

Battery Fail (PSU)

Not yet verified

Power supply unit: Battery Fail LED

The PSU's Battery Fail LED illuminates when the battery is disconnected.

Sourced — not yet independently verifiedFireCell Programming Guide, p. p.13

Battery Fault (device)

Not yet verified

Device fault status: Battery Fault

In the device Fault Status menu, this shows the device has either a low battery (minimum operational life 7-30 days remaining) or a battery missing.

Sourced — not yet independently verifiedFireCell Programming Guide, p. p.19

Battery Fault (Hub/RCC)

Not yet verified

Hub/RCC fault status: Battery Fault

In the Hub/RCC Fault Status menu, this indicates either no battery present, a low battery, or a battery charger failure on an RCC.

Sourced — not yet independently verifiedFireCell Programming Guide, p. pp.25-26

Battery Low (PSU)

Not yet verified

Power supply unit: Battery Low LED

The PSU's Battery Low LED illuminates when the battery voltage is below 5.7 V.

Sourced — not yet independently verifiedFireCell Programming Guide, p. p.13

Checksum Error

Not yet verified

Hub/RCC fault status: Checksum Error (also the System Fault LED)

In the Hub/RCC Fault Status menu, this message is displayed if an error is detected in either the software program or the configuration data. The manual separately notes the Radio Hub's front-plate yellow System Fault LED flashes for this same checksum-error condition.

Sourced — not yet independently verifiedFireCell Programming Guide, p. pp.25-26, p.11

DEV Ch1 RFI Det

Not yet verified

Hub/RCC fault status: DEV Ch1 RFI Det

In the Hub/RCC Fault Status menu, this indicates radio-frequency interference has been detected on radio channel 1 of the radio device-to-RCC communication path.

Sourced — not yet independently verifiedFireCell Programming Guide, p. pp.25-26

DEV Ch2 RFI Det

Not yet verified

Hub/RCC fault status: DEV Ch2 RFI Det

In the Hub/RCC Fault Status menu, this indicates radio-frequency interference has been detected on radio channel 2 of the radio device-to-RCC communication path.

Sourced — not yet independently verifiedFireCell Programming Guide, p. pp.25-26

Head Dirty

Not yet verified

Device fault status: Head Dirty

In the device Fault Status menu, this shows the detector's head is deemed dirty or contaminated.

Sourced — not yet independently verifiedFireCell Programming Guide, p. p.19

Head Fault

Not yet verified

Device fault status: Head Fault

In the device Fault Status menu, this indicates a detector's head has a fault, i.e. no communication between the head and the wireless base.

Sourced — not yet independently verifiedFireCell Programming Guide, p. p.19

Head Missing

Not yet verified

Device fault status: Head Missing

In the device Fault Status menu, this indicates the detector's head, sounder, strobe-only or sounder/strobe head is not currently fitted on the wireless base.

Sourced — not yet independently verifiedFireCell Programming Guide, p. p.19

In Tamper

Not yet verified

Device fault status: In Tamper

In the device Fault Status menu on the Radio Hub, this indicates the device's tamper switch is not currently making contact against the ceiling- or wall-mounted base plate.

Sourced — not yet independently verifiedFireCell Programming Guide, p. p.19

Mains / Charger Fail

Not yet verified

Power supply unit: Mains / Charger Fail LED

The PSU's Mains / Charger Fail LED illuminates whilst the PSU cannot detect a valid mains supply, or when the battery is not charging.

Sourced — not yet independently verifiedFireCell Programming Guide, p. p.13

Mains Fault

Not yet verified

Hub/RCC fault status: Mains Fault

In the Hub/RCC Fault Status menu, this indicates there is no mains present on the Radio Cluster Communicator (RCC).

Sourced — not yet independently verifiedFireCell Programming Guide, p. pp.25-26

No Signal/PSU

Not yet verified

Hub/RCC fault status: No Signal/PSU

In the Hub/RCC Fault Status menu, this indicates there has been no communication between the Radio Hub and an RCC for 300 seconds, or communication is being achieved but not at an acceptable level; it may also indicate total loss of power to the RCC.

Sourced — not yet independently verifiedFireCell Programming Guide, p. pp.25-26

No Sndr Audio

Not yet verified

Device fault status: No Sndr Audio

In the device Fault Status menu: the primary and secondary stage sounder tones can be monitored; if enabled and no audio is detected within 10 seconds of sounder activation, this fault is indicated.

Sourced — not yet independently verifiedFireCell Programming Guide, p. p.19

Open Circuit

Not yet verified

Device fault status: Open Circuit (I/O unit input)

In the device Fault Status menu, this indicates an open-circuit wiring fault on the input of an Input/Output (I/O) unit.

Sourced — not yet independently verifiedFireCell Programming Guide, p. p.19

Processor Fail

Not yet verified

Hub/RCC fault status: Processor Fail

In the Hub/RCC Fault Status menu, this indicates the on-board processor on an RCC or the Radio Hub is in a failure condition.

Sourced — not yet independently verifiedFireCell Programming Guide, p. pp.25-26

PSU Fault LED

Not yet verified

Power supply unit: Fault LED

The PSU's Fault LED illuminates whilst any fault is present at the PSU.

Sourced — not yet independently verifiedFireCell Programming Guide, p. p.13

RCC Ch1 RFI Det

Not yet verified

Hub/RCC fault status: RCC Ch1 RFI Det

In the Hub/RCC Fault Status menu, this indicates radio-frequency interference has been detected on radio channel 1 of the RCC network communication path.

Sourced — not yet independently verifiedFireCell Programming Guide, p. pp.25-26

RCC Ch2 RFI Det

Not yet verified

Hub/RCC fault status: RCC Ch2 RFI Det

In the Hub/RCC Fault Status menu, this indicates radio-frequency interference has been detected on radio channel 2 of the RCC network communication path.

Sourced — not yet independently verifiedFireCell Programming Guide, p. pp.25-26

Receiver Fail

Not yet verified

Hub/RCC fault status: Receiver Fail

In the Hub/RCC Fault Status menu, this indicates one of the on-board wireless receivers on an RCC or the Radio Hub is in a failure condition.

Sourced — not yet independently verifiedFireCell Programming Guide, p. pp.25-26

Short Circuit

Not yet verified

Device fault status: Short Circuit (I/O unit input)

In the device Fault Status menu, this indicates a short-circuit wiring fault on the input of an Input/Output (I/O) unit.

Sourced — not yet independently verifiedFireCell Programming Guide, p. p.19

Signal Fault

Not yet verified

Device fault status: Signal Fault

In the device Fault Status menu, this is shown for two reasons: there has been no communication between the device and its Radio Cluster Communicator (RCC) for 300 seconds, or the signalling path is poor and communication is being achieved but at an unacceptable level for reliable communication.

Sourced — not yet independently verifiedFireCell Programming Guide, p. p.19

Unassigned

Not yet verified

Device fault status: Unassigned

In the device Fault Status menu, this indicates the device is not yet assigned to the system. Assign it via the rotary control or the Assign Devices menu option.

Sourced — not yet independently verifiedFireCell Programming Guide, p. p.19

Ask about the EMS Fire FireCell — free, no account

One question, answered from the fault records above. If they don't cover it, we'll say so. Sign up free for 5 questions a day across every panel.

Records marked “sourced — not yet independently verified” carry a real citation but have not yet completed formal review. Always confirm against the manufacturer's current documentation before acting on site.

Got the panel in front of you? Look the fault up.

Search fault records by panel, each showing its review status and the source document where one is cited, and ask the assistant when a message is not listed. A free account needs no card and includes 5 assistant questions and 20 fault searches a day.