Fike Twinflex fault records

10 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from.

Fault records

10 records

Display blank and no LEDs showing

Not yet verified

Twinflex Pro: blank display and no LEDs

The manual says that if the display is blank and no LEDs are showing, either the unit is not powered or the mains has failed and the batteries are lower than 21 V. To recover from the low-battery shut-off, power down completely, check the batteries are no lower than 21 V and power the system up. If the batteries are lower than 21 V they should be replaced or monitored during initial charging to ensure they recharge correctly, which could take several hours. If the batteries are below 18 V they should be replaced, as they will have lost much of their capacity and are unlikely to recover.

FAULT LED

Not yet verified

Twinflex Pro: FAULT LED

Yellow FAULT indicator, continuous: the manual says the control panel is in the fault state and other indicators will show the origin. The indication can also be confirmed from the message in the panel information screen or the relevant event log.

FIRE OUTPUT fault LED

Not yet verified

Twinflex Pro: FIRE OUTPUT fault LED

Yellow FIRE OUTPUT indicator, flashing: the manual says a fault condition is present on a monitored relay circuit. Continuous means a device or an action associated with the monitored relay circuit has been disabled.

SYSTEM FAULT LED (continuous)

Not yet verified

Twinflex Pro: SYSTEM FAULT LED (continuous)

Yellow SYSTEM FAULT indicator, continuous: the manual says it indicates the presence of a processor or a checksum error. To clear it, power the system down, reprogram all settings and test the system. During a system fault, depending on the cause, all relays will be off, all zones powered down, and the zone, power fault and disabled LEDs on continuously (page 14). The panel should be powered down for approximately 2 minutes and re-powered by a competent person and the event entered in the log; if the panel appears operational, a reset will clear the fault (page 14).

SYSTEM FAULT LED (flashing, write enable)

Not yet verified

Twinflex Pro: SYSTEM FAULT LED (flashing, write enable)

Yellow SYSTEM FAULT indicator, flashing: the manual says this LED is also illuminated if the write protect / write enable switch is left on while the system is not in the engineer menu. In access levels 1 and 2 a system fault is then shown on the LEDs and display and the fault relay is off, but it has no effect on the operation of the panel and serves as a reminder to switch write enable off before leaving the panel (page 14).

Ask about the Fike Twinflex — free, no account

One question, answered from the fault records above. If they don't cover it, we'll say so. Sign up free for 5 questions a day across every panel.

Recorded standards

standards
EN 54-2,EN 54-4