Morley-IAS DX Connexion fault codes

24 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from.

Fault codes and messages

24 records

CONFIG CHECKSUM FAIL

Source-checked

Configuration settings corruption detected

Some form of corruption has been detected within the configuration settings — this can occur following a software upgrade if the memory is not 'wiped'. Try wiping the memory or re-configuring from the configuration tool to clear the fault (followed by a reset); alternatively the base-card PCB must be returned to the factory.