8 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from. Single loop digital addressable fire alarm control panel, up to 192 Protec 6000PLUS-series loop devices.

Fault records

8 records

Aux. Supply Fault (24 V output)

Not yet verified

Protec 6100: Aux. Supply Fault (24 V output)

The manual says a fault has been detected with the auxiliary 24 V supply output of the 6100. There may no longer be an auxiliary supply to external devices, or the auxiliary devices are drawing too much current. The General Fault indicator is illuminated accompanied by the Aux Supply Fault indicator.

Fire link Fault (monitored fire link path)

Not yet verified

Protec 6100: Fire link Fault (monitored fire link path)

The manual says a fault has been detected on the monitored fire link path. This may be a wiring fault or a fire link interface fault. The connection to the fire station link is no longer reliable, and expert advice should be sought immediately. The General Fault indicator is illuminated accompanied by the Fire Link Fault indicator.

General fault handling

Not yet verified

Protec 6100: General fault handling

The manual says that when the 6100 detects a fault in any of the critical operating paths it shows it on the front panel display and the internal buzzer pulses slowly. The General Fault indicator is illuminated and is always accompanied by other indicator(s) detailing the exact fault. Fault indicators flash until the fault is accepted (by pressing Mute Buzzer at access level 2); the indicator then illuminates steadily and the buzzer is muted, and further faults activate the buzzer again. Its listed actions: investigate the fault, accept it at access level 2, note it in the logbook and take action to remedy it, seeking expert advice in all cases. When the fault has been rectified the fault indicator extinguishes automatically.

Zone Faults (indicators)

Not yet verified

Protec 6100: Zone Faults (indicators)

The manual says the 6100 displays any faults in the first 16 zones on the multifunction zone indicators, and all zone faults are also displayed on the LCD. The General Fault indicator is illuminated with the relevant zone indicator flashing yellow. Pressing Mute Buzzer mutes the buzzer but will not make the zone indicator go steady.