Siemens Fire Safety Cerberus PRO FC726 fault records

10 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from. Product family recorded from the cited official manufacturer source.

Fault records

10 records

'Zone', 'Serial no. ("ID-Nr.")', 'Dev.location fault'

Not yet verified

Displayed for each swapped C-NET device if the C-NET detector line was restarted after devices of the same type were swapped over in their bases. To clear, at least the device types in the corresponding bases must be correct; procedure given: rectify localization errors, connect PC to the Station, load configuration from Station to PC, disconnect PC.

Topology is invalid

Not yet verified

Displayed after a C-NET detector line has been read in, if the topology of that line is invalid (source gives four invalid-topology diagrams: stub on stub or loop interrupted; stub on stub on loop; several stubs starting from the same location on loop; loop on loop). Action: check the detector line with line tester FDUL221 (see document 008250); create a valid topology by rectifying the wiring or re-planning the detector line.