18 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from.

Fault records

18 records

EARTH

Not yet verified

Premier AL power supply indicator: EARTH

Power supply status indicator on the Zeta Premier AL power supply board. The manual lists it as: Earth fault, printed in the manual as “Earth fault (disabled)”; the diagram beside it shows the earth fault monitoring link/disable jumper.

System fault (complete system failure)

Not yet verified

Premier AL: system fault

Per the manual, in the event of a complete system failure a system fault is indicated: the SYSTEM FAULT and GENERAL FAULT LEDs illuminate and all other LEDs are extinguished; the internal buzzer sounds continuously; the LCD backlight switches off and the text, which shows the last condition, should be ignored; local alarm circuits are silenced if active; all loop devices remain in the condition they were in when the fault occurred, so some sounders may remain active. The manual warns that the system is completely inactive. User action: call your service engineer immediately. Service engineer actions listed: open the outer door, operate the SYSTEM FAULT RESET switch and then the PROCESSOR RESET switch on the motherboard, and observe that the panel restarts and shows the POWER UP DELAY message; if it does not restart properly the panel requires replacement.

The Fault Condition (general response)

Not yet verified

Premier AL: fault condition

Per the manual, a fault is indicated if any part of the system enters an abnormal condition. The COMMON FAULT LED pulses (and the ALARM FAULT/DISABLEMENT LED also pulses if the fault is with an alarm circuit), the internal buzzer sounds continuously, the LCD displays details of the event (for example a zone number with OPT FAULT and the device location), and the event is printed if a printer is fitted. During a fault condition events of lower priority are suppressed. User actions listed: switch the access controls keyswitch on, press SILENCE BUZZER (the FAULT and BUZZER SILENCED LEDs go steady), investigate and rectify the cause, and when it is cleared press RESET to return the system to the quiescent condition.

Ask about the Zeta Premier — free, no account

One question, answered from the fault records above. If they don't cover it, we'll say so. Sign up free for 5 questions a day across every panel.

Records marked “sourced — not yet independently verified” carry a real citation but have not yet completed formal review. Always confirm against the manufacturer's current documentation before acting on site.

Got the panel in front of you? Look the fault up.

Search fault records by panel, each showing its review status and the source document where one is cited, and ask the assistant when a message is not listed. A free account needs no card and includes 5 assistant questions and 20 fault searches a day.