Zeta SmartConnect fault codes

11 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from.

Fault codes and messages

11 records

Earth Positive Fault

Source-checked

Positive-side earth fault

Something is shorting to earth on the positive side (usually through a cable screen). Most earth faults occur on the addressable loop — disconnect all loop connections and reset the panel; if no earth fault is reported the fault is on the loop, and can be located by splitting the loop in half and sub-dividing the bad section. Note that connecting other mains-powered equipment (e.g. a laptop) to the panel can itself give an earth fault.

System Fault

Source-checked

Abnormal microprocessor running condition

A system fault is an abnormal microprocessor running condition caused by various unexpected phenomena. The panel attempts to correct itself; while the fault is present the System Fault LED, General Fault LED, General Fault relay and internal fault buzzer are constantly active. Clear via the system fault reset button underneath the PCB. If the fault does not clear, consult the distributor.

Ask about the Zeta SmartConnect — free, no account

One question, answered from the fault records above. If they don't cover it, we'll say so. Sign up free for 5 questions a day across every panel.

Recorded standards

maximumNodeDistanceStandardFireCableMetres
100