Advanced MxPro 5 fault codes

19 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from.

Fault codes and messages

19 records

AUX LOAD TOO HIGH

Source-checked

Auxiliary Output Load Too High

The panel's auxiliary 24V output current draw is above its normal operating range (0-500mA) — an overload on equipment powered from the AUX terminals. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22-23, Document 680-166 Revision 04), which lists "Aux Load" as one of the panel's monitored internal circuits with a "Too High" possible state.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), Document 680-166 Revision 04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

BATTERY LOW

Source-checked

Battery Voltage Too Low

The standby battery voltage has dropped below the panel's normal operating band (nominally 27.6V). From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as one of the possible circuit states (Normal / Too High / Too Low / Open Circuit / Short Circuit) the panel reports for this circuit. This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165), so it confirms the condition and its general meaning but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

BATTERY TOO HIGH

Source-checked

Battery Voltage Too High

The standby battery voltage is above the panel's normal operating band. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as one of the possible circuit states (Normal / Too High / Too Low / Open Circuit / Short Circuit) the panel reports for this circuit. This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165), so it confirms the condition and its general meaning but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

CHARGER TOO HIGH

Source-checked

Charger Output Too High

The battery charger's output voltage reading is above the normal operating band. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as one of the possible circuit states (Normal / Too High / Too Low / Open Circuit / Short Circuit) the panel reports for this circuit. This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165), so it confirms the condition and its general meaning but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

CHARGER TOO LOW

Source-checked

Charger Output Too Low

The battery charger's output voltage reading is below the normal operating band (nominally 28.0V). From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as one of the possible circuit states (Normal / Too High / Too Low / Open Circuit / Short Circuit) the panel reports for this circuit. This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165), so it confirms the condition and its general meaning but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

DEVICE CONTAMINATION

Not yet verified

Device Contamination / Drift Fault

Raised against an analogue loop device once its measured compensation-drift value exceeds a preset limit — typically dust or contamination affecting a detector's chamber over time. Preceded by a non-fault "Warning" state as the device gets progressively dirtier (see the User Manual's "View - Warnings" section, 3.9.10). From the official MxPro 5 – Argus Vega Devices Application Note (Document 680-169, Rev 01, section 2.1.1 "Loop – Calibrate" — this application note is not paginated, so it is cited by section rather than page).

Device Missing

Source-checked

MxPro 5: Device Missing

The panel display shows the affected zone and device text with "DEVICE MISSING" alongside the device type (e.g. "(MULTI.SENSOR)"), from a worked example in the official Advanced MxPro5 User Manual (section 3.3, Fault Condition). This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165), so it confirms the display wording but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

Earth fault

Source-checked

Earth Fault (Earth Volts Too High / Too Low)

The panel's internal earth-monitoring circuit (Earth Volts) reads outside its normal band. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists Too High / Too Low as possible states for Earth Volts (0V–30V range, normal 2.5V/14.5V depending on configuration). This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165), so it confirms the condition and its general meaning but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

Fire Routing Fault

Source-checked

MxPro 5: Fire Routing Fault

Yellow LED indicator. Indicates that there is a fault condition in the Fire Brigade signalling equipment. From the official Advanced MxPro5 User Manual (LED Status Indicators table, section 2.2). This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165) the panel itself references for full programming/fault detail, so it names the indicator and its general meaning but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

LOOP LOAD TOO HIGH

Source-checked

Loop Load Too High

The loop current reading is above the normal operating range — an overload condition on the detection loop. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as one of the possible circuit states (Normal / Too High / Too Low / Open Circuit / Short Circuit) the panel reports for this circuit. This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165), so it confirms the condition and its general meaning but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

LOOP OPEN CIRCUIT

Source-checked

Loop Open Circuit

The loop current reading indicates an open-circuit state on the detection loop. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists Open Circuit as one of the possible states (Normal / Too High / Too Low / Open Circuit / Short Circuit) reported for the 1st Loop Load circuit. This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165), so it confirms the condition and its general meaning but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

LOOP SHORT CIRCUIT

Source-checked

Loop Short Circuit

The loop current reading indicates a short-circuit state on the detection loop. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as one of the possible circuit states (Normal / Too High / Too Low / Open Circuit / Short Circuit) the panel reports for this circuit. This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165), so it confirms the condition and its general meaning but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

SERVICE DUE

Source-checked

Service Due Fault

The panel raises this fault once the programmed "next service due" date is reached, alerting the site operator that a maintenance visit is overdue. It clears automatically once a new service date is entered. From the official MxPro5 Remote Terminal Product Manual (Document 680-185, Revision 02, section 4.3.7.4 "Service Due Date").

SOUNDER CIRCUIT OPEN CIRCUIT

Source-checked

Sounder Circuit Open Circuit

A supervised sounder output circuit (Sounder A/B, and C/D on the 5400) reads open circuit. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as one of the possible circuit states (Normal / Too High / Too Low / Open Circuit / Short Circuit) the panel reports for this circuit. This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165), so it confirms the condition and its general meaning but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

SOUNDER CIRCUIT SHORT CIRCUIT

Source-checked

Sounder Circuit Short Circuit

A supervised sounder output circuit reads short circuit. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as one of the possible circuit states (Normal / Too High / Too Low / Open Circuit / Short Circuit) the panel reports for this circuit. This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165), so it confirms the condition and its general meaning but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

Sounder Fault

Source-checked

MxPro 5: Sounder Fault

Yellow LED indicator. Indicates the presence of a fault in one or more sounder wiring circuits. From the official Advanced MxPro5 User Manual (LED Status Indicators table, section 2.2). This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165) the panel itself references for full programming/fault detail, so it names the indicator and its general meaning but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

SOUNDER LOAD TOO HIGH

Source-checked

Sounder Load Too High

A sounder circuit's load current is above the normal operating range. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as one of the possible circuit states (Normal / Too High / Too Low / Open Circuit / Short Circuit) the panel reports for this circuit. This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165), so it confirms the condition and its general meaning but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

System Fault

Source-checked

MxPro 5: System Fault

Yellow LED indicator. Indicates the presence of a system fault. From the official Advanced MxPro5 User Manual (LED Status Indicators table, section 2.2). This is the User Manual, not the fuller Installation and Commissioning Manual (Document 680-165) the panel itself references for full programming/fault detail, so it names the indicator and its general meaning but not every underlying wiring-level cause.

Verified against a cited sourceAdvanced MxPro5 Fire Alarm Panels User Manual (5000/5000V/5000N series), applicable from Software Version 5000-050-04(archived copy)— original no longer reachable (checked 30 Oct 2026); this record was verified against it on 29 Sept 2026

Ask about the Advanced MxPro 5 — free, no account

One question, answered from the fault records above. If they don't cover it, we'll say so. Sign up free for 5 questions a day across every panel.

Records marked “sourced — not yet independently verified” carry a real citation but have not yet completed formal review. Always confirm against the manufacturer's current documentation before acting on site.

Got the panel in front of you? Look the fault up.

Search fault records by panel, each showing its review status and the source document where one is cited, and ask the assistant when a message is not listed. A free account needs no card and includes 5 assistant questions and 20 fault searches a day.