10 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from. Two-wire fire alarm panel using C-TEC AlarmSense analogue-style detectors, sounders and call points on a conventional zone-circuit wiring topology. Models CFP702-2 (2 zone), CFP704-2 (4 zone), CFP708-2 (8 zone).
Flashes yellow when there is a fault on any part of the fire alarm system. It is always lit together with at least one other Fault light that shows the precise type of fault detected. The panel's fault output also activates (unless disabled).
Indicates one or more of: the mains supply is too low or has failed completely; the mains fuse (F1) has ruptured; the battery fuse (F2) has ruptured; the battery supply voltage is too low or the batteries are in poor condition; or the panel's power supply unit is faulty.
Flashes yellow when there is a fault on the output's auxiliary 24V supply — typically because the 24V auxiliary output (used to supply relays switched by the remote output) is overloaded and its protection fuse has tripped. Repairing the fault resets the fuse and clears the light.
Flashes yellow when the master panel cannot communicate with one or more repeater panels (if fitted). Access level three fault diagnosis shows which repeater(s) are in fault, by zone light.
The Sounder Status light pulses yellow when either a conventional sounder circuit has a fault, or an AlarmSense sounder on a zone circuit has a fault (in which case the relevant Zone Fault light also pulses). All sounder circuits are monitored for open and short circuit faults unless disabled or in an alarm condition. An unpolarised conventional sounder will also show a sounder fault.
If the green Supply Present light is not lit, either both the mains supply and standby batteries have failed, or the Power Supply PCB, the Main Control PCB, or the cable connecting them is faulty.
Occurs as a result of a momentary disturbance in the panel's microprocessor. In access level three fault diagnosis this shows as Zone 3's Fault light lit.
Occurs when site-specific data held in the panel's microprocessor is found to be corrupt. In access level three fault diagnosis this shows as Zone 2's Fault light lit.
Occurs when the panel's microprocessor has failed to operate correctly; the watchdog circuit attempts to restart it. If it cannot, the General Fault and System Fault lights cycle continuously and the internal sounder activates. In access level three fault diagnosis this shows as Zone 1's Fault light lit. System faults do not clear automatically when rectified.
Zone Fault light (open/short circuit or detector removed)
All zone circuits (up to eight) are monitored for open circuit and short circuit faults and detector head removal, unless the zone is in an alarm condition or is in test or disabled. The relevant Zone Fault light pulses yellow, and the Sounder Status light also pulses yellow if AlarmSense sounders are fitted to that zone. Access level 3 fault diagnosis (HEAD OUT CIRCUIT / OPEN CIRCUIT / SHORT CIRCUIT lights) identifies which of the three fault types is present per zone.
Ask about the C-TEC CFP AlarmSense (2/4/8 Zone) — free, no account