Skip to main content
Fire

C-TEC CFP AlarmSense (2/4/8 Zone) fault records

10 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from. Two-wire fire alarm panel using C-TEC AlarmSense analogue-style detectors, sounders and call points on a conventional zone-circuit wiring topology. Models CFP702-2 (2 zone), CFP704-2 (4 zone), CFP708-2 (8 zone).

Fault records

10 records

Sounder Fault

Not yet verified

Sounder Fault (Sounder Status light)

The Sounder Status light pulses yellow when either a conventional sounder circuit has a fault, or an AlarmSense sounder on a zone circuit has a fault (in which case the relevant Zone Fault light also pulses). All sounder circuits are monitored for open and short circuit faults unless disabled or in an alarm condition. An unpolarised conventional sounder will also show a sounder fault.

System Fault: Watchdog

Not yet verified

System Fault: Watchdog Fault

Occurs when the panel's microprocessor has failed to operate correctly; the watchdog circuit attempts to restart it. If it cannot, the General Fault and System Fault lights cycle continuously and the internal sounder activates. In access level three fault diagnosis this shows as Zone 1's Fault light lit. System faults do not clear automatically when rectified.

Zone Fault

Not yet verified

Zone Fault light (open/short circuit or detector removed)

All zone circuits (up to eight) are monitored for open circuit and short circuit faults and detector head removal, unless the zone is in an alarm condition or is in test or disabled. The relevant Zone Fault light pulses yellow, and the Sounder Status light also pulses yellow if AlarmSense sounders are fitted to that zone. Access level 3 fault diagnosis (HEAD OUT CIRCUIT / OPEN CIRCUIT / SHORT CIRCUIT lights) identifies which of the three fault types is present per zone.

Ask about the C-TEC CFP AlarmSense (2/4/8 Zone) — free, no account

One question, answered from the fault records above. If they don't cover it, we'll say so. Sign up free for 5 questions a day across every panel.

Records marked “sourced — not yet independently verified” carry a real citation but have not yet completed formal review. Always confirm against the manufacturer's current documentation before acting on site.

Got the panel in front of you? Look the fault up.

Search fault records by panel, each showing its review status and the source document where one is cited, and ask the assistant when a message is not listed. A free account needs no card and includes 5 assistant questions and 20 fault searches a day.