C-TEC FP Range (2-14 Zone) Conventional Fire Alarm Panel fault records

3 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from. Older-generation C-TEC conventional fire alarm panel range, 2 to 14 zones, with separate internal Open Circuit / Short Circuit fault indicator lamps alongside the main Zone Fault indicator. Distinct product from the MFP range, CFP and CFP AlarmSense ranges.

Fault records

3 records

Power Supply Fault

Not yet verified

Power Supply Fault indicator

Lit, with the warning beeper sounding, whenever the mains supply is off or the standby batteries are disconnected or flat. Extinguishes, and the beeper silences, once mains power is restored and the batteries are connected and adequately charged. Note: deteriorated battery cells will still show a fault even when connected and charged.

Sourced — not yet independently verifiedFP2-14 Zone Fire Panel: Approved Document, p. 1

Sounder Fault

Not yet verified

Sounder Fault indicator

Lit, with the warning beeper sounding, on either an open circuit or short circuit fault on a sounder circuit. Pressing Silence Fault Sounders silences the beeper but the indicator stays lit until the circuit fault is corrected.

Sourced — not yet independently verifiedFP2-14 Zone Fire Panel: Approved Document, p. 1

Zone Fault

Not yet verified

Zone Fault indicator (open/short circuit)

The Zone Fault indicator lights together with a separate internal Open Circuit Fault or Short Circuit Fault indicator lamp specific to the affected zone, depending on which condition is present. The warning beeper also sounds. Detector monitoring circuits can otherwise be in a Normal or Fire condition.

Sourced — not yet independently verifiedFP2-14 Zone Fire Panel: Approved Document, p. 1

Ask about the C-TEC FP Range (2-14 Zone) Conventional Fire Alarm Panel — free, no account

One question, answered from the fault records above. If they don't cover it, we'll say so. Sign up free for 5 questions a day across every panel.

Records marked “sourced — not yet independently verified” carry a real citation but have not yet completed formal review. Always confirm against the manufacturer's current documentation before acting on site.

Got the panel in front of you? Look the fault up.

Search fault records by panel, each showing its review status and the source document where one is cited, and ask the assistant when a message is not listed. A free account needs no card and includes 5 assistant questions and 20 fault searches a day.