C-TEC MFP Range (4-28 Zone) Conventional Fire Alarm Panel fault records

5 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from. Older-generation C-TEC conventional fire alarm panel range, models MFP4/8/12/16/20/24/28, using pulse-coded Zone Fault light indication (1 pulse = short circuit, 2 = head removed, 3 = open circuit; steady = zone disabled). Distinct product from the newer CFP and CFP AlarmSense ranges.

Fault records

5 records

Battery/Power Supply Fault

Not yet verified

Permanent Battery/Power Supply Fault

Check: (1) the MAINS ON light is illuminated — if not, check the mains supply and fuse next to the transformer; (2) the battery leads are connected the correct way round (reversed leads blow the battery fuse F5 and can cause a permanent, non-resettable power fault); (3) two 12V batteries of the correct size are connected in series; (4) the wiring loom is properly seated on PL4; (5) the transformer leads are properly connected. If the fault persists with the mains light lit, the batteries may be heavily discharged or have failed — try a known-good, fully charged pair.

Processor Fault

Not yet verified

Processor Fault light lit

Accompanied by a permanent fault beeper tone. Indicates the panel's microprocessor failed to execute its programme correctly and a safety circuit restarted it — can be caused by a sudden interruption of all power, high-powered interference (e.g. a lightning strike), or misconnection or failure of circuit boards and peripheral equipment. To clear, turn the keyswitch to Arm Controls and press RESET/TEST/SCROLL. If the light returns, check inter-board connections and the power supply; if the fault persists, return the panel to the dealer. Note: on a processor restart, any previously disabled functions are re-enabled (a fail-safe feature).

Sounder Fault

Not yet verified

Permanent Sounder Fault

Check the sounder circuit fuses (F1, F2, F3, F4) on the PCB and replace if necessary. Check the correct end-of-line resistor (6800 ohms; blue, grey, red, gold) is fitted — disconnect the relevant zone from the terminal block and refit the end-of-line resistor only; if the fault clears, there is a wiring fault on that circuit.

Zone Fault

Not yet verified

Zone Fault light (pulse-coded: short/head removed/open circuit)

The number of pulses of the Zone Fault light indicates the fault type: 1 pulse = short circuit, 2 pulses = head removed, 3 pulses = open circuit. A steady (non-pulsing) light means the zone has been disabled rather than faulted. Manual call points and other normally-open switches will cause a short circuit fault (1 pulse) if triggered without a call point resistor fitted in series.

Ask about the C-TEC MFP Range (4-28 Zone) Conventional Fire Alarm Panel — free, no account

One question, answered from the fault records above. If they don't cover it, we'll say so. Sign up free for 5 questions a day across every panel.

Records marked “sourced — not yet independently verified” carry a real citation but have not yet completed formal review. Always confirm against the manufacturer's current documentation before acting on site.

Got the panel in front of you? Look the fault up.

Search fault records by panel, each showing its review status and the source document where one is cited, and ask the assistant when a message is not listed. A free account needs no card and includes 5 assistant questions and 20 fault searches a day.