Addressable fire alarm control panel family

C-TEC XFP fault codes

9 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from. C-TEC XFP addressable fire panel family. Capacity and protocol are model-specific; the single-loop 16-zone and one/two-loop 32-zone generations are recorded separately in the technical catalogue.

Fault codes and messages

9 records

Earth fault

Source-checked

The XFP earth-fault monitoring has detected an abnormal connection between the fire system and earth.

Verified against a cited sourceXFP Engineering Manual DFU2200510 Rev 2

Fault conditions (what the display shows, including Device Missing example)

Source-checked

XFP: fault conditions

Per the user manual, if part of the fire alarm system fails (for example detector failure or a wiring fault), one or more of the panel's fault indicators flash, the internal sounder (if enabled) pulses, and the display shows an appropriate fault message; for a faulty manual call point the zone it is on is shown. Pressing the more information button shows more detail, and for device-specific faults the actual device is shown: the manual's example shows a Reception Call Point with the status Device Missing, and pressing more information again shows the device's unique ID code and address location for service engineers. If there is more than one fault the top right of the display reads More and the faults can be scrolled through. The manual tells the designated responsible person to mute the internal beeper (new faults restart it), note the nature of the fault in the log book, and take steps to have it rectified.

Investigating a device with INTENSIVE DEVICE MONITOR

Source-checked

XFP: Intensive Device Monitor (engineer function)

Per the manual, this function monitors one addressable point under intensive, repeated polls from the panel, and reports how many good and bad polls occur between the panel and the device, which can help pinpoint loop wiring or communication faults and faulty devices. While it runs, the panel suspends all other system activity, so fires are not flagged and the manual says to use it with care. The engineer selects the loop, the device address and an output bit sequence, so that a device can be monitored while in a particular output state (for example when an I/O unit reports faults only after an output channel is asserted).

Locating loop open or short circuits: BLINK DETECTOR LEDS

Source-checked

XFP: Blink Detector LEDs (engineer function)

Per the manual, this engineering function momentarily asserts the LED outputs of loop devices in one continual sweep, and is useful for locating open or short circuit faults on the loop wiring. LEDs are asserted step by step (about one second each), and the test can be run from End A, End B or both ends. In the manual's example for an open circuit between devices 17 and 18, End A lights devices 1 to 17 and End B lights devices 18 to 23, identifying the break between 17 and 18. For a short circuit, End A lights devices 1 to 14 (the isolator between 14 and 15 having operated) and End B lights devices 21 to 23 (the isolator between 20 and 21 having operated), identifying a short somewhere between the two isolators containing devices 15 to 20.

PSU fault

Source-checked

Power supply fault

The XFP power-supply monitoring indicates a supply, battery or earth-monitoring problem.

Verified against a cited sourceXFP Engineering Manual DFU2200510 Rev 2

Ask about the C-TEC XFP — free, no account