Gent by Honeywell Vigilon fault records

12 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from. Gent Vigilon analogue addressable fire alarm panel — widely installed in large commercial and industrial premises across the UK.

Fault records

12 records

Device Battery fault

Not yet verified

Vigilon: Device Battery fault

Message shown on the Vigilon panel. Meaning per the manual: the battery supply at an interface unit, repeat panel or mimic panel has failed the load test. Indications listed: Fault. Action listed in the manual: check the battery and replace if necessary.

Interface input OC /SC

Not yet verified

Vigilon: Interface input OC /SC

Message shown on the Vigilon panel. Meaning per the manual: there is an open or short circuit on the input line of an interface. Indications listed: Fault. Action listed in the manual: locate and remove the wiring fault, and ensure the end of line device is connected in the circuit.

Lost Device

Not yet verified

Vigilon: Lost Device

Message shown on the Vigilon panel. Meaning per the manual: the device is not communicating with the control panel via the loop. An additional Sounder indication is given if it is a sounder device. Indications listed: Fault (plus Sounder for a sounder device). Action listed in the manual: check the connections to the device.

Master Alarm(s) OC or SC n

Not yet verified

Vigilon: Master Alarm(s) OC or SC n

Message shown on the Vigilon panel. Meaning per the manual: there is an open or short circuit fault on the master alarm wiring. Indications listed: Fault and Sounder. Action listed in the manual: check the wiring and ensure the end-of-line device is connected in the circuit.

Monitored line input OC or SC

Not yet verified

Vigilon: Monitored line input OC or SC

Message shown on the Vigilon panel. Meaning per the manual: the monitored line input has an open or short circuit fault. Indications listed: Fault. Action listed in the manual: check the wiring and ensure the end of line device is connected in the circuit.

Wiring changed SC at card n

Not yet verified

Vigilon: Wiring changed SC at card n

Message shown on the Vigilon panel. Meaning per the manual: there is a short circuit on the loop n wiring. Indications listed: Fault. Action listed in the manual: identify the device where a cable fault has occurred and remove the fault.