12 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from. Gent Vigilon analogue addressable fire alarm panel — widely installed in large commercial and industrial premises across the UK.
Message shown on the Vigilon panel. Meaning per the manual: the battery supply to the control panel has been fully discharged. Indications listed: Fault and Power fault. Action listed in the manual: check the battery and replace if necessary.
Message shown on the Vigilon panel. Meaning per the manual: the battery supply to the control panel has been disconnected. Indications listed: Fault and Power fault. Action listed in the manual: reconnect the battery.
Message shown on the Vigilon panel. Meaning per the manual: the battery supply at an interface unit, repeat panel or mimic panel has failed the load test. Indications listed: Fault. Action listed in the manual: check the battery and replace if necessary.
Message shown on the Vigilon panel. Meaning per the manual: there is a mains supply failure at an interface unit, repeat or mimic panel. Indications listed: Fault. Action listed in the manual: check the fuse and mains supply to the equipment.
Message shown on the Vigilon panel. Meaning per the manual: there is an open or short circuit on the input line of an interface. Indications listed: Fault. Action listed in the manual: locate and remove the wiring fault, and ensure the end of line device is connected in the circuit.
Message shown on the Vigilon panel. Meaning per the manual: the device is not communicating with the control panel via the loop. An additional Sounder indication is given if it is a sounder device. Indications listed: Fault (plus Sounder for a sounder device). Action listed in the manual: check the connections to the device.
Message shown on the Vigilon panel. Meaning per the manual: the mains supply to the control panel has failed. Indications listed: Fault and Power fault. Action listed in the manual: restore the mains supply to the control panel.
Message shown on the Vigilon panel. Meaning per the manual: there is an open or short circuit fault on the master alarm wiring. Indications listed: Fault and Sounder. Action listed in the manual: check the wiring and ensure the end-of-line device is connected in the circuit.
Message shown on the Vigilon panel. Meaning per the manual: the monitored line input has an open or short circuit fault. Indications listed: Fault. Action listed in the manual: check the wiring and ensure the end of line device is connected in the circuit.
Message shown on the Vigilon panel. Meaning per the manual: the integral printer is not 'seen' by the control panel. Indications listed: Fault. Action listed in the manual: check the connections to the printer and check that the paper is feeding correctly.
Message shown on the Vigilon panel. Meaning per the manual: the device indicated is not functioning correctly. Indications listed: Fault. Action listed in the manual: the device needs replacing.
Message shown on the Vigilon panel. Meaning per the manual: there is a short circuit on the loop n wiring. Indications listed: Fault. Action listed in the manual: identify the device where a cable fault has occurred and remove the fault.