Battery discharged
Source-checkedControl panel battery fully discharged
The battery supply at the Control Panel is fully discharged. Check the battery and replace if necessary.
11 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from.
11 records
Control panel battery fully discharged
The battery supply at the Control Panel is fully discharged. Check the battery and replace if necessary.
Control panel battery disconnected
The battery supply to the Control Panel has been disconnected. Reconnect the battery.
Battery load test failed at an interface unit, repeat panel or mimic panel
The battery supply at an interface unit, repeat panel or mimic panel has failed the load test. Check the battery and replace if necessary.
Mains supply failure at an interface unit, repeat panel or mimic panel
There is a mains supply failure at an interface unit, repeat panel or mimic panel. Check the fuse and mains supply to the equipment.
Fire Alarm Routing Equipment fault
The Fire Alarm Routing Equipment (FARE) is faulty. Check for a short circuit or signal transmission failure at the FARE.
Open or short circuit on an interface input line
There is an open or short circuit on the input line of an interface. Locate and remove the wiring fault, and ensure the end-of-line device is connected in the circuit.
Mains supply to the control panel has failed
The mains supply to the control panel has failed. Restore the mains supply to the control panel.
Open or short circuit on the master alarm wiring
There is an open or short circuit fault on the master alarm wiring. Check the wiring and ensure the end-of-line device is connected in the circuit.
Open or short circuit on a monitored line input
The monitored line input has an open or short circuit fault. Check the wiring and ensure the end-of-line device is connected in the circuit.
Indicated device not functioning correctly
The device indicated is not functioning correctly. The device needs replacing.
Short circuit on the loop wiring
There is a short circuit on the loop wiring. Identify the device where a cable fault has occurred and remove the fault.