Haes Systems Esento Eclipse 2-4 Zone fault records

12 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from. Haes Technologies 2 to 4 zone conventional fire control panel (Esento Eclipse, ECL-2/4).

Fault records

12 records

Sounder circuit open circuit

Not yet verified

Sounder circuit open circuit (fault diagnosis mode)

In fault diagnosis mode (press and hold ENTER), a Zone 1 or Zone 2 Fire LED steady after pressing ENTER indicates an open circuit on sounder circuit 1 or 2 (Main PCB SNDR 1 and SNDR 2). The LED going off after pressing ENTER means that circuit is OK.

Sounder circuit short circuit

Not yet verified

Sounder circuit short circuit (fault diagnosis mode)

When a fault is showing, press and hold ENTER (works only when the panel is not in a fire condition and controls are not active). The Zone 1 or Zone 2 Fire LED that is off before pressing ENTER pulses for a short circuit on sounder circuit 1 or 2 respectively (Main PCB SNDR 1 and SNDR 2).

System fault: display board

Not yet verified

System Fault LED only, continuous buzzer (display board halted)

A system fault is a processor watchdog time out or processor failure. With only the System Fault LED continuous and a continuous buzzer, display board TPCA02 is halted and no other indication or control is possible. The fault relay and fault output are activated. If a fire occurs, alarm sounders and outputs still function.

Zone disabled or in test mode

Not yet verified

Zone Fault/Disabled/Test LED steady: zone disabled or in test mode

A steady Zone 1 to 4 Fault/Disabled/Test LED (not pulsing) means that zone is disabled or in test mode; pressing ENTER in fault diagnosis mode does not show a fault type for it. The LED going off after pressing ENTER is listed as 'Zone # disabled or in test mode'.

Ask about the Haes Systems Esento Eclipse 2-4 Zone — free, no account

One question, answered from the fault records above. If they don't cover it, we'll say so. Sign up free for 5 questions a day across every panel.

Records marked “sourced — not yet independently verified” carry a real citation but have not yet completed formal review. Always confirm against the manufacturer's current documentation before acting on site.

Got the panel in front of you? Look the fault up.

Search fault records by panel, each showing its review status and the source document where one is cited, and ask the assistant when a message is not listed. A free account needs no card and includes 5 assistant questions and 20 fault searches a day.