Haes Systems Esprit Apollo Addressable fault records

11 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from. Haes Technologies one to four loop addressable fire alarm control panel (ESPRiT-Apollo).

Fault records

11 records

General Fault LED pulsing (fault condition)

Not yet verified

Fault condition: display shows number and nature of faults

When the panel detects a fault the display indicates the number and nature of the fault(s), the internal buzzer sounds an intermittent tone and the amber General Fault LED pulses, with any other specific Fault LEDs lit. Scroll the list with the arrow keys. Mute Buzzer silences the buzzer and turns the General Fault LED steady. Faults are non-latching (except System Fault) and clear automatically when remedied, or press Reset System to clear. A silenced buzzer re-sounds when a new fault occurs.

Power Supply Fault on connecting mains before batteries

Not yet verified

Power Supply Fault for up to 1 minute at power-up

If the mains is connected before the batteries, the panel shows a Power Supply Fault for up to 1 minute until the monitoring cycle has finished polling. The manual says this is normal, and to check connections if the fault does not clear after 1 minute.

System fault: display board (main control board)

Not yet verified

System Fault LED only, continuous buzzer

A system fault is a processor watchdog time-out or processor failure. With only the System Fault LED lit and a continuous buzzer, the display board (main control board) is halted and no other indication or control is possible. The fault relay is activated.

System fault: power supply board

Not yet verified

System Fault, General Fault and Power Supply Fault LEDs pulsing

With the System Fault, General Fault and Power Supply Fault LEDs all pulsing, the fault relay is activated. Mains or battery power will still operate the panel, but batteries will not be charging. The indications remain until the fault is rectified and the panel is reset.

Ask about the Haes Systems Esprit Apollo Addressable — free, no account

One question, answered from the fault records above. If they don't cover it, we'll say so. Sign up free for 5 questions a day across every panel.

Records marked “sourced — not yet independently verified” carry a real citation but have not yet completed formal review. Always confirm against the manufacturer's current documentation before acting on site.

Got the panel in front of you? Look the fault up.

Search fault records by panel, each showing its review status and the source document where one is cited, and ask the assistant when a message is not listed. A free account needs no card and includes 5 assistant questions and 20 fault searches a day.