Haes Systems Esento Excel 2-12 Zone fault records

17 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from. Haes Technologies 2 to 12 zone conventional fire control panel (Esento Excel, XLEN-2/4/6/8/12).

Fault records

17 records

Power supply fault on connecting mains before batteries

Not yet verified

Power Supply fault for up to 1 minute at power-up

If the mains is connected before the batteries, the panel shows a Power Supply fault for up to 1 minute until the monitoring cycle has finished polling. The manual says this is normal, and to check connections if the fault does not clear after 1 minute.

Power supply fault: battery failure or high impedance

Not yet verified

Power Supply Fault LED: battery failure or high impedance

With the Power Supply Fault LED pulsing, press and hold ENTER (fault diagnosis mode): the LED steady after pressing ENTER means battery failure or high impedance. The specification table (printed page 9) gives the battery high impedance fault (Batt Hi Z) as resistance of 1 ohm or greater, with a 1 hour reporting time.

Repeater fault: faulty repeater

Not yet verified

Repeater Fault LED slow flash

When a repeater fault is displayed, press and hold ENTER: a slow flash of the Repeater Fault LED indicates a faulty repeater. Red fire LEDs 1 to 8 show which repeater was offline, and amber fault LEDs 1 to 8 show which repeater had a PSU fault.

Sounder circuit open circuit

Not yet verified

Sounder circuit open circuit (fault diagnosis mode)

In fault diagnosis mode (press and hold ENTER), a Zone 1 to 6 Fire LED that is steady after pressing ENTER indicates an open circuit on the matching sounder circuit (Zone 1 and 2 = Main PCB SNDR 1 and 2; Zones 3 to 6 = High Spec Extension Zone Card). A Fire LED that goes off after pressing ENTER means that sounder circuit is OK.

Sounder circuit short circuit

Not yet verified

Sounder circuit short circuit (fault diagnosis mode)

When a fault is showing, press and hold ENTER (works only when the panel is not in a fire condition). The Zone 1 to 6 Fire LED that is off before you press ENTER pulses for a short circuit on that sounder circuit: Zone 1 = sounder circuit 1 and Zone 2 = sounder circuit 2 (Main PCB SNDR 1 and 2); Zones 3 to 6 = sounder circuits 3 to 6 on the High Spec Extension Zone Card.

System fault recovery

Not yet verified

System Fault LED and General Fault LED pulsing with pulsed fault buzzer

System Fault LED pulsing and General Fault LED pulsing along with a pulsed (fault tone) buzzer means a system fault has occurred and the affected board has recovered. The indication remains until the panel is reset.

System fault: display board

Not yet verified

System Fault LED only, continuous buzzer (display board halted)

A system fault is indicated when a processor controlling a function in the panel has a watchdog time out or processor failure. With only the System Fault LED continuous and a continuous buzzer, display board TPCA03 is halted and no other indication or control is possible. The fault relay and fault output are activated. If a fire occurs, alarm sounders and outputs still function.

System fault: main board or zone extender board

Not yet verified

System Fault LED continuous, General Fault LED pulsing, continuous buzzer

Per the manual, a continuous System Fault LED with the General Fault LED pulsing and a continuous buzzer means the main board, or the extender card if fitted, is halted. The fault relay is activated, and alarms may be activated on the unaffected board.

System fault: repeater comms board

Not yet verified

System Fault LED continuous, General Fault LED pulsing, Repeater Fault LED continuous

A continuous System Fault LED with the General Fault LED pulsing and the Repeater Fault LED continuous means Comms Board TPCA05 is halted. The fault relay and output are active and repeater panels cease to function. Fire alarms can still be detected and controlled by the panel.

Zone detector removed

Not yet verified

Detection zone: detector removed (fault diagnosis mode)

For zones 1 to 4 on the Main PCB, in fault diagnosis mode (press and hold ENTER) the Zone Fault/Disabled/Test LED going off after pressing ENTER, with a slow pulse shown in the table, means a detector has been removed on that zone.

Zone disabled or in test mode

Not yet verified

Zone Fault/Disabled/Test LED steady: zone disabled or in test mode

A steady Zone 1 to 4 Fault/Disabled/Test LED (not pulsing) means that zone is disabled or in test mode; pressing ENTER in fault diagnosis mode does not show a fault type for it (N/A for pulsing and steady). The LED going off after pressing ENTER is listed as 'Zone # disabled or in test mode'.

Ask about the Haes Systems Esento Excel 2-12 Zone — free, no account

One question, answered from the fault records above. If they don't cover it, we'll say so. Sign up free for 5 questions a day across every panel.

Records marked “sourced — not yet independently verified” carry a real citation but have not yet completed formal review. Always confirm against the manufacturer's current documentation before acting on site.

Got the panel in front of you? Look the fault up.

Search fault records by panel, each showing its review status and the source document where one is cited, and ask the assistant when a message is not listed. A free account needs no card and includes 5 assistant questions and 20 fault searches a day.