Ziton ZP3 fault records

7 fault records for this panel, each labelled with its review status and, where one is cited, the source document it comes from. Ziton ZP3 analogue addressable fire control panel.

Fault records

7 records

Fuse ratings on the power supply board

Not yet verified

ZP3: Fuse ratings on the power supply board

The legend lists: F6 auxiliary 24 V DC supply, F4AL250V (20 x 5 mm, 4.0 A fast-blow); F1 battery fuse, S6300mAL250V (20 x 5 mm, 6.3 A slow-blow); F8 and F7 monitor sound, F1AL250V (1.0 A fast-blow); F5 RMC FLT alarm, F1AL250V (1.0 A fast-blow); F2 and F3 monitor sounders, F1AL250V (1.0 A fast-blow); F9 PSU 24 V DC supply, S6300mAL250V (6.3 A slow-blow); F10 PSU 5 V DC logic (internal), S500mAL250V (500 mA slow-blow); FM mains fuse, F5AL250VAC (BS1362).

Internal supply LEDs 37, 15, 14, 8, 7, 2 and 4

Not yet verified

ZP3: Internal supply LEDs 37, 15, 14, 8, 7, 2 and 4

The legend lists these green LEDs as supply indicators: on means the supply is on and off means the supply is faulty. LED 37: internal 24 V DC supply. LED 15: internal supply for the CPU (5 V DC). LED 14: internal supply for logic (5 V DC). LED 8: internal supply for RS232 (12 V DC -ve). LED 7: internal supply for RS232 (12 V DC +ve). LED 2: internal supply for the ZP3AB-SCB-D control bus driver. LED 4: mains 230 V AC supply.

Ask about the Ziton ZP3 — free, no account

One question, answered from the fault records above. If they don't cover it, we'll say so. Sign up free for 5 questions a day across every panel.

Records marked “sourced — not yet independently verified” carry a real citation but have not yet completed formal review. Always confirm against the manufacturer's current documentation before acting on site.

Got the panel in front of you? Look the fault up.

Search fault records by panel, each showing its review status and the source document where one is cited, and ask the assistant when a message is not listed. A free account needs no card and includes 5 assistant questions and 20 fault searches a day.