Notifier by Honeywell ID3000

Incompatible or faulty sensor installed

Not yet verified

No separate cause description is given beyond the message name. Action: For IPX sensors, replace with SDX751TEM or equivalent. For other MULTI and SMART sensors, replace (sensor is faulty).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

SENSOR FAULT

Not yet verified

For VIEW, MULTI (Optiplex), or SMART sensors: the analogue reading is below the Chamber fault threshold, or below the Maintenance Urgent threshold, or a Maintenance Alert has existed for longer than 100 days without any…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

System Fault 64 - CPU Watchdog not enabled

Not yet verified

This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…

View on the Notifier by Honeywell ID3000 page

Ziton ZP2-FR

Firenet panel offline

Not yet verified

If a control panel previously configured to be in the fire network is not detected, a fault message indicating the offline status (with the Firenet ID) is reported. From the ZP2 Series Installation Manual, "Firenet…

View on the Ziton ZP2-FR page

Kentec Syncro AS

ZONE FAULT

Legacy record reviewed

A conventional zone circuit has reported an open or short circuit fault. Kentec Syncro AS monitors zone wiring with end-of-line resistors (EOLR).

View on the Kentec Syncro AS page

Notifier by Honeywell ID3000

Dev#0 Present

Not yet verified

This indicates that a device has been installed without setting a valid address, i.e. left at factory default of '00'. No separate remedial action is stated beyond this cause in the source.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Earth Fault

Not yet verified

The earth fault monitor detects the presence of an earth on the positive or negative sides of the system. Should this condition occur, disconnect the field circuit wiring one cable at a time and view the LED at the top…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 47 - CPU/Display hardware fault

Not yet verified

Communications fault between the CPU and the display. Action: Change the CPU PCB assembly (PN: 020-569) and/or the Display PCB/Membrane Keypad (PN: 020-571-XXX).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 71 - Config. needs Expansion Card

Not yet verified

This fault message can only appear when ID3000 panels are networked with earlier compatible panels; it is not applicable to the 'local' ID3000 Series panel. Where it is applicable, an Extension Chassis with Display…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Channel 1 Link Fault

Not yet verified

Most likely to occur in the event of a broken network connection, i.e. short or open circuit cable or broken optical fibre. May also indicate an NGM PCB hardware fault. There would normally be two fault messages, one at…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Channel 2 Link Fault

Not yet verified

The source states this fault has the same cause and remedy as 'ID2net: Channel 1 Link Fault' — see that entry.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Network startup fault

Not yet verified

Displayed if either: a. the NGM PCB fails to start initially, or b. the NGM PCB fails to start after the occurrence of a runtime fault, such as a panel/NGM PCB communication loss. Action (shared with Network runtime…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Panel Fault 49 - CPU Watchdog timer fault

Not yet verified

This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Power Fault, ID2net Booster n

Not yet verified

This message indicates an open circuit on the power fault input of the NGM. Action: Check for missing or broken wiring. Check that the PSU is not faulty.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

PSU/Charger Fault

Not yet verified

These faults indicate the occurrence of one or more of: a. Faulty or disconnected batteries (if discharged batteries are connected, they may remain in Battery Low Voltage for a period until the voltage is raised by the…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Sounder Cct.X OPEN-CIRCUIT

Not yet verified

Parameterised message covering sounder circuits 1-4 (X = 1, 2, 3 or 4), as printed in the source. Indicates an open circuit (disconnection condition) fault on the sounder circuit wiring. Action: For circuits 3 and 4,…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

System Fault 40 - Main CPU Watchdog Operated

Not yet verified

This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

System Fault 41 - EPROM Memory Checksum

Not yet verified

This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

System Fault 42 - E2PROM Memory Write Error

Not yet verified

This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

System Fault 43 - FLASH Memory Checksum

Not yet verified

This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

System Fault 45 - FLASH Memory Write Error

Not yet verified

This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

System Fault 46 - Software error

Not yet verified

This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

System Fault 66 - CPU Clock Monitor Failure

Not yet verified

This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

System Fault 67 - CPU Illegal Instruction

Not yet verified

This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Terminal Link Fault

Not yet verified

This fault indicates that the peripheral unit connected to the third-party-protocol RS232 port has not responded to the enquiry code sent, or the link to the third-party equipment is not connected (this would normally…

View on the Notifier by Honeywell ID3000 page

Advanced MxPro 4

Fire Routing Fault

Not yet verified

Applies only when the Routing Interface is set to Monitored (Section 3.3.15.8). Function LED3 (Yellow) indicates a fault in the transmission path of the fire routing connection, and also illuminates if there is a fault…

View on the Advanced MxPro 4 page

Advanced MxPro 5

Earth fault

Not yet verified

The panel's internal earth-monitoring circuit reads outside its normal band, typically indicating cable insulation breakdown or earth leakage. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic…

View on the Advanced MxPro 5 page

Advanced MxPro 5

Fire Routing Fault

Not yet verified

Yellow LED indicator. Indicates that there is a fault condition in the Fire Brigade signalling equipment. From the official Advanced MxPro5 User Manual (LED Status Indicators table, section 2.2). This is the User…

View on the Advanced MxPro 5 page

Advanced MxPro 5

LOOP OPEN CIRCUIT

Not yet verified

The loop current reading indicates an open-circuit state — a break, loose terminal or removed device on the detection loop. All devices beyond the break will be reported as missing; short circuit isolators (SCIs), if…

View on the Advanced MxPro 5 page

Advanced MxPro 5

Sounder Fault

Not yet verified

Yellow LED indicator. Indicates the presence of a fault in one or more sounder wiring circuits. From the official Advanced MxPro5 User Manual (LED Status Indicators table, section 2.2). This is the User Manual, not the…

View on the Advanced MxPro 5 page