Notifier by Honeywell ID3000
Incompatible or faulty sensor installed
No separate cause description is given beyond the message name. Action: For IPX sensors, replace with SDX751TEM or equivalent. For other MULTI and SMART sensors, replace (sensor is faulty).
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
SENSOR FAULT
For VIEW, MULTI (Optiplex), or SMART sensors: the analogue reading is below the Chamber fault threshold, or below the Maintenance Urgent threshold, or a Maintenance Alert has existed for longer than 100 days without any…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
System Fault 64 - CPU Watchdog not enabled
This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…
View on the Notifier by Honeywell ID3000 pageZiton ZP2-FR
Firenet panel offline
If a control panel previously configured to be in the fire network is not detected, a fault message indicating the offline status (with the Firenet ID) is reported. From the ZP2 Series Installation Manual, "Firenet…
View on the Ziton ZP2-FR pageKentec Syncro AS
ZONE FAULT
A conventional zone circuit has reported an open or short circuit fault. Kentec Syncro AS monitors zone wiring with end-of-line resistors (EOLR).
View on the Kentec Syncro AS pageNotifier by Honeywell ID3000
Dev#0 Present
This indicates that a device has been installed without setting a valid address, i.e. left at factory default of '00'. No separate remedial action is stated beyond this cause in the source.
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Earth Fault
The earth fault monitor detects the presence of an earth on the positive or negative sides of the system. Should this condition occur, disconnect the field circuit wiring one cable at a time and view the LED at the top…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Fault 47 - CPU/Display hardware fault
Communications fault between the CPU and the display. Action: Change the CPU PCB assembly (PN: 020-569) and/or the Display PCB/Membrane Keypad (PN: 020-571-XXX).
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Fault 71 - Config. needs Expansion Card
This fault message can only appear when ID3000 panels are networked with earlier compatible panels; it is not applicable to the 'local' ID3000 Series panel. Where it is applicable, an Extension Chassis with Display…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
ID2net: Channel 1 Link Fault
Most likely to occur in the event of a broken network connection, i.e. short or open circuit cable or broken optical fibre. May also indicate an NGM PCB hardware fault. There would normally be two fault messages, one at…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
ID2net: Channel 2 Link Fault
The source states this fault has the same cause and remedy as 'ID2net: Channel 1 Link Fault' — see that entry.
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
ID2net: Network startup fault
Displayed if either: a. the NGM PCB fails to start initially, or b. the NGM PCB fails to start after the occurrence of a runtime fault, such as a panel/NGM PCB communication loss. Action (shared with Network runtime…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Panel Fault 49 - CPU Watchdog timer fault
This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Power Fault, ID2net Booster n
This message indicates an open circuit on the power fault input of the NGM. Action: Check for missing or broken wiring. Check that the PSU is not faulty.
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
PSU/Charger Fault
These faults indicate the occurrence of one or more of: a. Faulty or disconnected batteries (if discharged batteries are connected, they may remain in Battery Low Voltage for a period until the voltage is raised by the…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Sounder Cct.X OPEN-CIRCUIT
Parameterised message covering sounder circuits 1-4 (X = 1, 2, 3 or 4), as printed in the source. Indicates an open circuit (disconnection condition) fault on the sounder circuit wiring. Action: For circuits 3 and 4,…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
System Fault 40 - Main CPU Watchdog Operated
This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
System Fault 41 - EPROM Memory Checksum
This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
System Fault 42 - E2PROM Memory Write Error
This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
System Fault 43 - FLASH Memory Checksum
This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
System Fault 45 - FLASH Memory Write Error
This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
System Fault 46 - Software error
This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
System Fault 66 - CPU Clock Monitor Failure
This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
System Fault 67 - CPU Illegal Instruction
This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Terminal Link Fault
This fault indicates that the peripheral unit connected to the third-party-protocol RS232 port has not responded to the enquiry code sent, or the link to the third-party equipment is not connected (this would normally…
View on the Notifier by Honeywell ID3000 pageAdvanced MxPro 4
Fire Routing Fault
Applies only when the Routing Interface is set to Monitored (Section 3.3.15.8). Function LED3 (Yellow) indicates a fault in the transmission path of the fire routing connection, and also illuminates if there is a fault…
View on the Advanced MxPro 4 pageAdvanced MxPro 5
Earth fault
The panel's internal earth-monitoring circuit reads outside its normal band, typically indicating cable insulation breakdown or earth leakage. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
Fire Routing Fault
Yellow LED indicator. Indicates that there is a fault condition in the Fire Brigade signalling equipment. From the official Advanced MxPro5 User Manual (LED Status Indicators table, section 2.2). This is the User…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
LOOP OPEN CIRCUIT
The loop current reading indicates an open-circuit state — a break, loose terminal or removed device on the detection loop. All devices beyond the break will be reported as missing; short circuit isolators (SCIs), if…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
Sounder Fault
Yellow LED indicator. Indicates the presence of a fault in one or more sounder wiring circuits. From the official Advanced MxPro5 User Manual (LED Status Indicators table, section 2.2). This is the User Manual, not the…
View on the Advanced MxPro 5 pagePanels
Notifier by Honeywell
ID3000
49 sourced fault records
View fault recordsAdvanced Electronics
Advanced MxPro 4
15 sourced fault records
View fault recordsAdvanced Electronics
Advanced MxPro 5
19 sourced fault records
View fault recordsZiton
ZP2-FR
15 sourced fault records
View fault recordsKentec Electronics
Kentec Syncro AS
7 sourced fault records
View fault recordsProtec
Protec 6500
38 sourced fault records
View fault records