Advanced MxPro 5
AUX LOAD TOO HIGH
The panel's auxiliary 24V output current draw is above its normal operating range (0-500mA) — an overload on equipment powered from the AUX terminals. From the official Advanced MxPro5 User Manual's Local Hardware…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
BATTERY LOW
The standby battery voltage has dropped below the panel's normal operating band (nominally 27.6V). From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
BATTERY TOO HIGH
The standby battery voltage is above the panel's normal operating band. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as one of the…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
CHARGER TOO HIGH
The battery charger's output voltage reading is above the normal operating band. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as one of…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
CHARGER TOO LOW
The battery charger's output voltage reading is below the normal operating band (nominally 28.0V). From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
Device Missing
The panel display shows the affected zone and device text with "DEVICE MISSING" alongside the device type (e.g. "(MULTI.SENSOR)"), from a worked example in the official Advanced MxPro5 User Manual (section 3.3, Fault…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
Earth fault
The panel's internal earth-monitoring circuit (Earth Volts) reads outside its normal band. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists Too…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
Fire Routing Fault
Yellow LED indicator. Indicates that there is a fault condition in the Fire Brigade signalling equipment. From the official Advanced MxPro5 User Manual (LED Status Indicators table, section 2.2). This is the User…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
LOOP LOAD TOO HIGH
The loop current reading is above the normal operating range — an overload condition on the detection loop. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23),…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
LOOP OPEN CIRCUIT
The loop current reading indicates an open-circuit state on the detection loop. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists Open Circuit as…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
LOOP SHORT CIRCUIT
The loop current reading indicates a short-circuit state on the detection loop. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as one of the…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
SOUNDER CIRCUIT OPEN CIRCUIT
A supervised sounder output circuit (Sounder A/B, and C/D on the 5400) reads open circuit. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
SOUNDER CIRCUIT SHORT CIRCUIT
A supervised sounder output circuit reads short circuit. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as one of the possible circuit…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
Sounder Fault
Yellow LED indicator. Indicates the presence of a fault in one or more sounder wiring circuits. From the official Advanced MxPro5 User Manual (LED Status Indicators table, section 2.2). This is the User Manual, not the…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
SOUNDER LOAD TOO HIGH
A sounder circuit's load current is above the normal operating range. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as one of the possible…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
System Fault
Yellow LED indicator. Indicates the presence of a system fault. From the official Advanced MxPro5 User Manual (LED Status Indicators table, section 2.2). This is the User Manual, not the fuller Installation and…
View on the Advanced MxPro 5 pageAdvanced MxPro 4
Aux Supply Too High
From the panel's own "View - Panel" diagnostic table: Aux Supply is monitored 0mA-500mA; the panel reports Too High when the current exceeds the expected range.
View on the Advanced MxPro 4 pageAdvanced MxPro 4
Battery Too High
From the panel's own "View - Panel" diagnostic table: Battery is monitored 0V-30V, normal >25.0V; the panel reports Too High when the reading exceeds the expected range.
View on the Advanced MxPro 4 pageAdvanced MxPro 4
Battery Too Low
From the panel's own "View - Panel" diagnostic table: Battery is monitored 0V-30V, normal >25.0V under full load. Per the manual's own note, the voltage shown is measured under full load conditions; if it falls below…
View on the Advanced MxPro 4 pageAdvanced MxPro 4
Charger Too High
From the panel's own "View - Panel" diagnostic table: Charger is monitored 0V-30V, normal 27.6V; the panel reports Too High when the reading exceeds the expected range.
View on the Advanced MxPro 4 pageAdvanced MxPro 4
Charger Too Low
From the panel's own "View - Panel" diagnostic table: Charger is monitored 0V-30V, normal 27.6V; the panel reports Too Low when the reading falls below the expected range.
View on the Advanced MxPro 4 pageAdvanced MxPro 4
DEVICE MISSING
Shown against the specific loop address, zone and location text on the display, e.g. "1 004.0 DEVICE MISSING" under the zone's fault list. Indicates the panel is no longer receiving a response from that addressed device.
View on the Advanced MxPro 4 pageAdvanced MxPro 4
Earth Monitor Too High
From the panel's own "View - Panel" diagnostic table: Earth Monitor is monitored 0V-30V, normal 1.3V; the panel reports Too High when the reading exceeds the expected range.
View on the Advanced MxPro 4 pageAdvanced MxPro 4
Earth Monitor Too Low
From the panel's own "View - Panel" diagnostic table: Earth Monitor is monitored 0V-30V, normal 1.3V; the panel reports Too Low when the reading falls below the expected range.
View on the Advanced MxPro 4 pageAdvanced MxPro 4
Fire Routing Fault
Applies only when the Routing Interface is set to Monitored (Section 3.3.15.8). Function LED3 (Yellow) indicates a fault in the transmission path of the fire routing connection, and also illuminates if there is a fault…
View on the Advanced MxPro 4 pageAdvanced MxPro 4
Loop Load Too High
From the panel's own "View - Panel" diagnostic table: each loop's load is monitored 0mA-500mA; the panel reports Too High when the current exceeds the expected range.
View on the Advanced MxPro 4 pageAdvanced MxPro 4
Loop Open Circuit
From the panel's own "View - Panel" diagnostic table: each loop's load is monitored 0mA-500mA; the panel reports Open Circuit when the reading falls outside that range in the open direction. Loop Load, V.Out and V.In…
View on the Advanced MxPro 4 pageAdvanced MxPro 4
Loop Short Circuit
From the panel's own "View - Panel" diagnostic table: each loop's load is monitored 0mA-500mA; the panel reports Short Circuit when the reading falls outside that range in the short direction.
View on the Advanced MxPro 4 pageAdvanced MxPro 4
Sounder Load Too High
From the panel's own "View - Panel" diagnostic table: Sounder A/B Load is monitored 0mA-1000mA; the panel reports Too High when the loop current exceeds the expected range.
View on the Advanced MxPro 4 pageAdvanced MxPro 4
Sounder Open Circuit
From the panel's own "View - Panel" diagnostic table: Sounder A/B is monitored 0V-14V, normal 5.5V; the panel reports Open Circuit when the reading falls outside that range in the open direction.
View on the Advanced MxPro 4 page