Notifier by Honeywell ID3000
Dev#0 Present
This indicates that a device has been installed without setting a valid address, i.e. left at factory default of '00'. No separate remedial action is stated beyond this cause in the source.
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Incompatible or faulty sensor installed
No separate cause description is given beyond the message name. Action: For IPX sensors, replace with SDX751TEM or equivalent. For other MULTI and SMART sensors, replace (sensor is faulty).
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
SENSOR FAULT
For VIEW, MULTI (Optiplex), or SMART sensors: the analogue reading is below the Chamber fault threshold, or below the Maintenance Urgent threshold, or a Maintenance Alert has existed for longer than 100 days without any…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Sounder Cct.X OPEN-CIRCUIT
Parameterised message covering sounder circuits 1-4 (X = 1, 2, 3 or 4), as printed in the source. Indicates an open circuit (disconnection condition) fault on the sounder circuit wiring. Action: For circuits 3 and 4,…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
System Fault 64 - CPU Watchdog not enabled
This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…
View on the Notifier by Honeywell ID3000 pageAdvanced MxPro 4
Loop Open Circuit
From the panel's own "View - Panel" diagnostic table: each loop's load is monitored 0mA-500mA; the panel reports Open Circuit when the reading falls outside that range in the open direction. Loop Load, V.Out and V.In…
View on the Advanced MxPro 4 pageAdvanced MxPro 4
Sounder Open Circuit
From the panel's own "View - Panel" diagnostic table: Sounder A/B is monitored 0V-14V, normal 5.5V; the panel reports Open Circuit when the reading falls outside that range in the open direction.
View on the Advanced MxPro 4 pageAdvanced MxPro 5
LOOP OPEN
An open circuit has been detected on a detection loop: a wiring break or a disconnected device.
View on the Advanced MxPro 5 pageAdvanced MxPro 5
LOOP OPEN CIRCUIT
The loop current reading indicates an open-circuit state — a break, loose terminal or removed device on the detection loop. All devices beyond the break will be reported as missing; short circuit isolators (SCIs), if…
View on the Advanced MxPro 5 pageAdvanced MxPro 5
SOUNDER CIRCUIT OPEN CIRCUIT
A supervised sounder output circuit (Sounder A/B, and C/D on the 5400) reads open circuit. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as…
View on the Advanced MxPro 5 pageZiton ZP2-FR
Firenet panel offline
If a control panel previously configured to be in the fire network is not detected, a fault message indicating the offline status (with the Firenet ID) is reported. From the ZP2 Series Installation Manual, "Firenet…
View on the Ziton ZP2-FR pageProtec 6500
Network - Short A Leg To Screen
There is a short circuit fault in the network between CH1+ and the screen. Not available on some panel options.
View on the Protec 6500 pageProtec 6500
Network - Short B Leg To Screen
There is a short circuit fault in the network between CH1- and the screen. Not available on some panel options.
View on the Protec 6500 pageZiton ZP2-FR
Battery charger: compensation
The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery charger: sensor HI
The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Battery charger: sensor LO
The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…
View on the Ziton ZP2-FR pageProtec 6500
Loop Drive Open Circuit
The loop has a break in its wiring. The fault threshold is set to 100Ω.
View on the Protec 6500 pageKentec Syncro AS
ZONE FAULT
A conventional zone circuit has reported an open or short circuit fault. Kentec Syncro AS monitors zone wiring with end-of-line resistors (EOLR).
View on the Kentec Syncro AS pageAdvanced MxPro 4
Aux Supply Too High
From the panel's own "View - Panel" diagnostic table: Aux Supply is monitored 0mA-500mA; the panel reports Too High when the current exceeds the expected range.
View on the Advanced MxPro 4 pageAdvanced MxPro 4
Loop Load Too High
From the panel's own "View - Panel" diagnostic table: each loop's load is monitored 0mA-500mA; the panel reports Too High when the current exceeds the expected range.
View on the Advanced MxPro 4 pageKentec Syncro AS
BATTERY LOW VOLTAGE
The monitored standby battery voltage has fallen to the panel low-voltage threshold.
View on the Kentec Syncro AS pageKentec Syncro AS
SOUNDER FAULT
A monitored sounder or bell circuit has reported an open or short circuit. The circuit is monitored at rest to ensure sounders will function when called on.
View on the Kentec Syncro AS pageNotifier by Honeywell ID3000
Battery Failure
These faults indicate the occurrence of one or more of: a. Faulty or disconnected batteries (if discharged batteries are connected, they may remain in Battery Low Voltage for a period until the voltage is raised by the…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Battery Low Voltage
These faults indicate the occurrence of one or more of: a. Faulty or disconnected batteries (if discharged batteries are connected, they may remain in Battery Low Voltage for a period until the voltage is raised by the…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Earth Fault
The earth fault monitor detects the presence of an earth on the positive or negative sides of the system. Should this condition occur, disconnect the field circuit wiring one cable at a time and view the LED at the top…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Fault 47 - CPU/Display hardware fault
Communications fault between the CPU and the display. Action: Change the CPU PCB assembly (PN: 020-569) and/or the Display PCB/Membrane Keypad (PN: 020-571-XXX).
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Fault 48 - Base PCB/Expansion h/w fault
No separate cause description is given for this message beyond its name. Action: Change the Base PCB (PN: 020-568) or Extension Chassis with Display Module Kit (PN: 020-559-XXX).
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Fault 71 - Config. needs Expansion Card
This fault message can only appear when ID3000 panels are networked with earlier compatible panels; it is not applicable to the 'local' ID3000 Series panel. Where it is applicable, an Extension Chassis with Display…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Fault 72 - Config. needs RS485 Card
Missing PCB — the panel is configured for network but no RS485 PCB is present. Fit Isolated RS485 Module Kit (PN: 020-479) or change configuration.
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Fault 73 - Config. needs RS232 Card
Missing PCB — the panel is configured for 3rd-party protocol but no RS232 PCB is present (does not apply to other modes of the port). Fit Isolated RS232 Module Kit (PN: 020-478) or change configuration.
View on the Notifier by Honeywell ID3000 pagePanels
Notifier by Honeywell
ID3000
49 sourced fault records
View fault recordsAdvanced Electronics
Advanced MxPro 4
15 sourced fault records
View fault recordsAdvanced Electronics
Advanced MxPro 5
19 sourced fault records
View fault recordsZiton
ZP2-FR
15 sourced fault records
View fault recordsKentec Electronics
Kentec Syncro AS
7 sourced fault records
View fault recordsProtec
Protec 6500
38 sourced fault records
View fault records