Fault records for a small, deliberately staged set of panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from. More panels are added as more records go through source review.

Searches 148 records across 6 panels.

30+ partial matches for “Axis EN”

Nothing matched every word, so these match some of them. Check the record and panel before relying on it.

Notifier by Honeywell ID3000

Dev#0 Present

Not yet verified

This indicates that a device has been installed without setting a valid address, i.e. left at factory default of '00'. No separate remedial action is stated beyond this cause in the source.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Incompatible or faulty sensor installed

Not yet verified

No separate cause description is given beyond the message name. Action: For IPX sensors, replace with SDX751TEM or equivalent. For other MULTI and SMART sensors, replace (sensor is faulty).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

SENSOR FAULT

Not yet verified

For VIEW, MULTI (Optiplex), or SMART sensors: the analogue reading is below the Chamber fault threshold, or below the Maintenance Urgent threshold, or a Maintenance Alert has existed for longer than 100 days without any…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Sounder Cct.X OPEN-CIRCUIT

Not yet verified

Parameterised message covering sounder circuits 1-4 (X = 1, 2, 3 or 4), as printed in the source. Indicates an open circuit (disconnection condition) fault on the sounder circuit wiring. Action: For circuits 3 and 4,…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

System Fault 64 - CPU Watchdog not enabled

Not yet verified

This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…

View on the Notifier by Honeywell ID3000 page

Advanced MxPro 4

Loop Open Circuit

Not yet verified

From the panel's own "View - Panel" diagnostic table: each loop's load is monitored 0mA-500mA; the panel reports Open Circuit when the reading falls outside that range in the open direction. Loop Load, V.Out and V.In…

View on the Advanced MxPro 4 page

Advanced MxPro 4

Sounder Open Circuit

Not yet verified

From the panel's own "View - Panel" diagnostic table: Sounder A/B is monitored 0V-14V, normal 5.5V; the panel reports Open Circuit when the reading falls outside that range in the open direction.

View on the Advanced MxPro 4 page

Advanced MxPro 5

LOOP OPEN

Legacy record reviewed

An open circuit has been detected on a detection loop: a wiring break or a disconnected device.

View on the Advanced MxPro 5 page

Advanced MxPro 5

LOOP OPEN CIRCUIT

Not yet verified

The loop current reading indicates an open-circuit state — a break, loose terminal or removed device on the detection loop. All devices beyond the break will be reported as missing; short circuit isolators (SCIs), if…

View on the Advanced MxPro 5 page

Advanced MxPro 5

SOUNDER CIRCUIT OPEN CIRCUIT

Not yet verified

A supervised sounder output circuit (Sounder A/B, and C/D on the 5400) reads open circuit. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as…

View on the Advanced MxPro 5 page

Ziton ZP2-FR

Firenet panel offline

Not yet verified

If a control panel previously configured to be in the fire network is not detected, a fault message indicating the offline status (with the Firenet ID) is reported. From the ZP2 Series Installation Manual, "Firenet…

View on the Ziton ZP2-FR page

Protec 6500

Network - Short A Leg To Screen

Not yet verified

There is a short circuit fault in the network between CH1+ and the screen. Not available on some panel options.

View on the Protec 6500 page

Protec 6500

Network - Short B Leg To Screen

Not yet verified

There is a short circuit fault in the network between CH1- and the screen. Not available on some panel options.

View on the Protec 6500 page

Ziton ZP2-FR

Battery charger: compensation

Not yet verified

The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…

View on the Ziton ZP2-FR page

Ziton ZP2-FR

Battery charger: sensor HI

Not yet verified

The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…

View on the Ziton ZP2-FR page

Ziton ZP2-FR

Battery charger: sensor LO

Not yet verified

The source lists this as one of five additional battery charger fault messages that may display, beyond the four in Table 66, but gives no individual cause or remedy text for any of the five beyond the message name…

View on the Ziton ZP2-FR page

Protec 6500

Loop Drive Open Circuit

Not yet verified

The loop has a break in its wiring. The fault threshold is set to 100Ω.

View on the Protec 6500 page

Kentec Syncro AS

ZONE FAULT

Legacy record reviewed

A conventional zone circuit has reported an open or short circuit fault. Kentec Syncro AS monitors zone wiring with end-of-line resistors (EOLR).

View on the Kentec Syncro AS page

Advanced MxPro 4

Aux Supply Too High

Not yet verified

From the panel's own "View - Panel" diagnostic table: Aux Supply is monitored 0mA-500mA; the panel reports Too High when the current exceeds the expected range.

View on the Advanced MxPro 4 page

Advanced MxPro 4

Loop Load Too High

Not yet verified

From the panel's own "View - Panel" diagnostic table: each loop's load is monitored 0mA-500mA; the panel reports Too High when the current exceeds the expected range.

View on the Advanced MxPro 4 page

Kentec Syncro AS

BATTERY LOW VOLTAGE

verified

The monitored standby battery voltage has fallen to the panel low-voltage threshold.

View on the Kentec Syncro AS page

Kentec Syncro AS

SOUNDER FAULT

Legacy record reviewed

A monitored sounder or bell circuit has reported an open or short circuit. The circuit is monitored at rest to ensure sounders will function when called on.

View on the Kentec Syncro AS page

Notifier by Honeywell ID3000

Battery Failure

Not yet verified

These faults indicate the occurrence of one or more of: a. Faulty or disconnected batteries (if discharged batteries are connected, they may remain in Battery Low Voltage for a period until the voltage is raised by the…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Battery Low Voltage

Not yet verified

These faults indicate the occurrence of one or more of: a. Faulty or disconnected batteries (if discharged batteries are connected, they may remain in Battery Low Voltage for a period until the voltage is raised by the…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Earth Fault

Not yet verified

The earth fault monitor detects the presence of an earth on the positive or negative sides of the system. Should this condition occur, disconnect the field circuit wiring one cable at a time and view the LED at the top…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 47 - CPU/Display hardware fault

Not yet verified

Communications fault between the CPU and the display. Action: Change the CPU PCB assembly (PN: 020-569) and/or the Display PCB/Membrane Keypad (PN: 020-571-XXX).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 48 - Base PCB/Expansion h/w fault

Not yet verified

No separate cause description is given for this message beyond its name. Action: Change the Base PCB (PN: 020-568) or Extension Chassis with Display Module Kit (PN: 020-559-XXX).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 71 - Config. needs Expansion Card

Not yet verified

This fault message can only appear when ID3000 panels are networked with earlier compatible panels; it is not applicable to the 'local' ID3000 Series panel. Where it is applicable, an Extension Chassis with Display…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 72 - Config. needs RS485 Card

Not yet verified

Missing PCB — the panel is configured for network but no RS485 PCB is present. Fit Isolated RS485 Module Kit (PN: 020-479) or change configuration.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 73 - Config. needs RS232 Card

Not yet verified

Missing PCB — the panel is configured for 3rd-party protocol but no RS232 PCB is present (does not apply to other modes of the port). Fit Isolated RS232 Module Kit (PN: 020-478) or change configuration.

View on the Notifier by Honeywell ID3000 page