Siemens Fire Safety Cerberus PRO FC726

Fault of a component

Source-checked

Listed in the fault-message table on the row after System Fault (LED 5), with no LED number of its own. Action: Restart the 'Station'; when the fault is still indicated, exchange the module.

View on the Siemens Fire Safety Cerberus PRO FC726 page

Morley-IAS DX (Dimension Series DX1e/DX2e/DX4e)

INPUT OPEN CIRCUIT

Source-checked

Panel fault text shown on the DX display. The manual's example shows it as an input open circuit on 'Monitored Input 1' registered at 12:15, as one of three panel-related faults. The manual gives it only as an example…

View on the Morley-IAS DX (Dimension Series DX1e/DX2e/DX4e) page

Haes Systems Esento Excel 2-12 Zone

Sounder circuit open circuit

Source-checked

In fault diagnosis mode (press and hold ENTER), a Zone 1 to 6 Fire LED that is steady after pressing ENTER indicates an open circuit on the matching sounder circuit (Zone 1 and 2 = Main PCB SNDR 1 and 2; Zones 3 to 6 =…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

System fault: main board or zone extender board

Source-checked

Per the manual, a continuous System Fault LED with the General Fault LED pulsing and a continuous buzzer means the main board, or the extender card if fitted, is halted. The fault relay is activated, and alarms may be…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Zone open circuit

Source-checked

For zones 1 to 4 on the Main PCB, in fault diagnosis mode (press and hold ENTER) the Zone Fault/Disabled/Test LED steady after pressing ENTER means that zone has an open circuit.

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Eclipse 2-4 Zone

Sounder circuit open circuit

Source-checked

In fault diagnosis mode (press and hold ENTER), a Zone 1 or Zone 2 Fire LED steady after pressing ENTER indicates an open circuit on sounder circuit 1 or 2 (Main PCB SNDR 1 and SNDR 2). The LED going off after pressing…

View on the Haes Systems Esento Eclipse 2-4 Zone page

Haes Systems Esento Eclipse 2-4 Zone

Zone open circuit

Source-checked

For zones 1 to 4 on the Main PCB, in fault diagnosis mode (press and hold ENTER) the Zone Fault/Disabled/Test LED steady after pressing ENTER means that zone has an open circuit.

View on the Haes Systems Esento Eclipse 2-4 Zone page

C-TEC CFP (2/4/8 Zone Standard Conventional)

General Fault

Source-checked

Flashes yellow when there is a fault on any part of the fire alarm system. It is always lit together with at least one other Fault light that shows the precise type of fault detected.

View on the C-TEC CFP (2/4/8 Zone Standard Conventional) page

C-TEC CFP (2/4/8 Zone Standard Conventional)

Supply Present light not lit

Source-checked

If the green Supply Present light is not lit, either both the mains supply and standby batteries have failed, or the Power Supply PCB, the Main Control PCB, or the cable connecting them is faulty.

View on the C-TEC CFP (2/4/8 Zone Standard Conventional) page

C-TEC CFP AlarmSense (2/4/8 Zone)

General Fault

Source-checked

Flashes yellow when there is a fault on any part of the fire alarm system. It is always lit together with at least one other Fault light that shows the precise type of fault detected. The panel's fault output also…

View on the C-TEC CFP AlarmSense (2/4/8 Zone) page

C-TEC CFP AlarmSense (2/4/8 Zone)

Supply Present light not lit

Source-checked

If the green Supply Present light is not lit, either both the mains supply and standby batteries have failed, or the Power Supply PCB, the Main Control PCB, or the cable connecting them is faulty.

View on the C-TEC CFP AlarmSense (2/4/8 Zone) page

C-TEC MFP Range (4-28 Zone) Conventional Fire Alarm Panel

General Fault

Source-checked

Lit whenever any fault condition exists on the panel. One documented specific cause: if the buzzer sounds and the General Fault light is lit steadily with no other cause found, the panel has been left in a test mode —…

View on the C-TEC MFP Range (4-28 Zone) Conventional Fire Alarm Panel page

Notifier by Honeywell ID3000

Dev#0 Present

Source-checked

This indicates that a device has been installed without setting a valid address, i.e. left at factory default of '00'. No separate remedial action is stated beyond this cause in the source.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Incompatible or faulty sensor installed

Source-checked

No separate cause description is given beyond the message name. Action: For IPX sensors, replace with SDX751TEM or equivalent. For other MULTI and SMART sensors, replace (sensor is faulty).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

SENSOR FAULT

Source-checked

For VIEW, MULTI (Optiplex), or SMART sensors: the analogue reading is below the Chamber fault threshold, or below the Maintenance Urgent threshold, or a Maintenance Alert has existed for longer than 100 days without any…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Sounder Cct.X OPEN-CIRCUIT

Source-checked

Parameterised message covering sounder circuits 1-4 (X = 1, 2, 3 or 4), as printed in the source. Indicates an open circuit (disconnection condition) fault on the sounder circuit wiring. Action: For circuits 3 and 4,…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

System Fault 64 - CPU Watchdog not enabled

Source-checked

This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…

View on the Notifier by Honeywell ID3000 page

Advanced MxPro 4

Loop Open Circuit

Source-checked

From the panel's own "View - Panel" diagnostic table: each loop's load is monitored 0mA-500mA; the panel reports Open Circuit when the reading falls outside that range in the open direction. Loop Load, V.Out and V.In…

View on the Advanced MxPro 4 page

Advanced MxPro 4

Sounder Open Circuit

Source-checked

From the panel's own "View - Panel" diagnostic table: Sounder A/B is monitored 0V-14V, normal 5.5V; the panel reports Open Circuit when the reading falls outside that range in the open direction.

View on the Advanced MxPro 4 page

Advanced MxPro 5

LOOP OPEN CIRCUIT

Source-checked

The loop current reading indicates an open-circuit state on the detection loop. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists Open Circuit as…

View on the Advanced MxPro 5 page

Advanced MxPro 5

SOUNDER CIRCUIT OPEN CIRCUIT

Source-checked

A supervised sounder output circuit (Sounder A/B, and C/D on the 5400) reads open circuit. From the official Advanced MxPro5 User Manual's Local Hardware diagnostic table (section 3.9.7.2, pp.22–23), which lists this as…

View on the Advanced MxPro 5 page

Ziton ZP2-FR

Firenet panel offline

Source-checked

If a control panel previously configured to be in the fire network is not detected, a fault message indicating the offline status (with the Firenet ID) is reported. From the ZP2 Series Installation Manual, "Firenet…

View on the Ziton ZP2-FR page

Protec 6500

Network - Short A Leg To Screen

Not yet verified

There is a short circuit fault in the network between CH1+ and the screen. Not available on some panel options.

View on the Protec 6500 page

Protec 6500

Network - Short B Leg To Screen

Not yet verified

There is a short circuit fault in the network between CH1- and the screen. Not available on some panel options.

View on the Protec 6500 page

Gent by Honeywell Vigilon

Sensor out of specification

Source-checked

Message shown on the Vigilon panel. Meaning per the manual: the device indicated is not functioning correctly. Indications listed: Fault. Action listed in the manual: the device needs replacing.

View on the Gent by Honeywell Vigilon page

Fike Twinflex

SYSTEM FAULT LED (flashing, write enable)

Source-checked

Yellow SYSTEM FAULT indicator, flashing: the manual says this LED is also illuminated if the write protect / write enable switch is left on while the system is not in the engineer menu. In access levels 1 and 2 a system…

View on the Fike Twinflex page

Zeta Simpo

Alarm Confirm Input Open

Source-checked

Circuit broken at input 'Alarm Confirmation'.

View on the Zeta Simpo page

Zeta Simpo

EXT Output Open

Source-checked

Event message on the SIMPO addressable panel. The manual's Appendix A table describes it as: Circuit broken at Extinguishing output. The manual gives no cause or action for this message.

View on the Zeta Simpo page

Zeta Simpo

Fault Output Open

Source-checked

Event message on the SIMPO addressable panel. The manual's Appendix A table describes it as: Circuit broken at Fault output. The manual gives no cause or action for this message.

View on the Zeta Simpo page

Zeta Simpo

Fault Protection Panel Input Open

Source-checked

Circuit broken at input 'Protection Panel Fault'.

View on the Zeta Simpo page