Fault records by panel
Fault records for a small, deliberately staged set of panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from. More panels are added as more records go through source review.
Searches 148 records across 6 panels.
30+ matches for “C-TEC”
Protec 6500
Fire Protection Fault
The "Fire Protection Fault" LED on the 6500 panel's indicator strip, covering fire protection outputs (e.g. suppression or protection-related outputs) configured on the system. This is one of the labelled LED indicators…
View on the Protec 6500 pageZiton ZP2-FR
Fire protection fault
The yellow Fire Protection Fault/Disabled/Test LED indicates a fire protection fault, disablement, or test. A flashing LED indicates a fault; a steady LED indicates a disablement or a test. From the ZP2 Series…
View on the Ziton ZP2-FR pageProtec 6500
Alarm Fault
The "Alarm Fault" LED on the 6500 panel's indicator strip. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from Protec's own product photography. The brochure…
View on the Protec 6500 pageProtec 6500
Alarm Routing Fault
The "Alarm Routing Fault" LED on the 6500 panel's indicator strip, covering the alarm signalling/routing path (e.g. to an ARC or monitoring centre). This is one of the labelled LED indicators on the 6500 control panel's…
View on the Protec 6500 pageProtec 6500
Aux Supply Fault
The "Aux Supply Fault" LED on the 6500 panel's indicator strip, covering the panel's auxiliary power supply. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from…
View on the Protec 6500 pageProtec 6500
Loop Drive Processor Fault
The loop driver processor has reported a fault. Take the reporting panel offline then back online to attempt to clear it; if it persists, report the fault to Protec technical support.
View on the Protec 6500 pageProtec 6500
Network - Duplicate Master
Two master panels have been detected on the network — either two panels were assigned as master in their configuration data (correct via the PC commissioning software), or a double break in the network wiring left two…
View on the Protec 6500 pageProtec 6500
Network Fault
The "Network Fault" LED on the 6500 panel's indicator strip, covering the panel-to-panel network connection used when multiple 6500 panels are networked together. This is one of the labelled LED indicators on the 6500…
View on the Protec 6500 pageProtec 6500
Power Fault
The "Power Fault" LED on the 6500 panel's indicator strip, covering the panel's own power supply. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from Protec's own…
View on the Protec 6500 pageProtec 6500
System Fault
The "System Fault" LED on the 6500 panel's indicator strip. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from Protec's own product photography. The brochure…
View on the Protec 6500 pageProtec 6500
Loop Drive Open Circuit
The loop has a break in its wiring. The fault threshold is set to 100Ω.
View on the Protec 6500 pageProtec 6500
Loop Drive Overload Fault
The loop cannot be driven due to an overload condition.
View on the Protec 6500 pageProtec 6500
Loop Drive Parallel Fault
There is a low resistance between loop '+' and loop '-'. The fault threshold is 200Ω (Issue E) or 120Ω (Issue F). This fault can also occur if more than ten loop device repeater LEDs are turned on at the same time.
View on the Protec 6500 pageProtec 6500
Loop Drive Series Fault
There is a high resistance in the loop wiring. The fault threshold is 80Ω (Issue E) or 50Ω (Issue F), though any value greater than 32Ω is considered high. The loop current calculator in the commissioning software…
View on the Protec 6500 pageProtec 6500
Loop Drive Short Circuit
The loop has a short in its wiring — most likely in the wiring between loop side 'A' and the first device with an isolator, or between loop side 'B' and the last device with an isolator.
View on the Protec 6500 pageProtec 6500
Network - Break Panel X - Panel Y
There is a break in the network between Panel X and Panel Y, where X and Y are the panel numbers.
View on the Protec 6500 pageProtec 6500
Network - CH1 Shutdown Fault
A network fault has occurred causing the panel to ignore data from network CH1. Not available on some panel options.
View on the Protec 6500 pageProtec 6500
Network - CH2 PSU Fault
There is a fault in the network card's isolated power supply; replace the card.
View on the Protec 6500 pageProtec 6500
Network - CH2 Shutdown Fault
A network fault has occurred causing the panel to ignore data from network CH2. Not available on some panel options.
View on the Protec 6500 pageProtec 6500
Network - Configuration Fault
The configuration data received by the network card is corrupt.
View on the Protec 6500 pageProtec 6500
Network - Duplicate Panel(s)
The network has initialised with two panels sharing the same number; correct this using the PC commissioning software. Neither panel is allowed to transmit an event, so each will eventually also display a Slave CTS…
View on the Protec 6500 pageProtec 6500
Network - Failed
The network is not operational because there are too many faults.
View on the Protec 6500 pageProtec 6500
Network - I2C Link Fault
The communications link between the local network card and the core network card is faulty. Not available on some panel options.
View on the Protec 6500 pageProtec 6500
Network - Map Fault
The physical order of the panels does not match the order downloaded to the master panel.
View on the Protec 6500 pageProtec 6500
Network - Missing Panel
One or more panels in the master panel's network configuration data is missing.
View on the Protec 6500 pageProtec 6500
Network - Reverse Wiring Fault
One or more panels has its network CH1 and CH2 wiring reversed.
View on the Protec 6500 pageProtec 6500
Network - RS485 CH1- Partial O/C
There is a high resistance in the CH1- cable. Not available on some panel options.
View on the Protec 6500 pageProtec 6500
Network - RS485 CH1+ Partial O/C
There is a high resistance in the CH1+ cable. Not available on some panel options.
View on the Protec 6500 pageProtec 6500
Network - Running On Processor B
Processor 'B' is the backup processor and is only used when processor 'A' has failed. Not available on some panel options.
View on the Protec 6500 pageProtec 6500
Network - Short A Leg To B Leg
There is a short circuit fault in the network between CH1+ and CH1-. Not available on some panel options.
View on the Protec 6500 pagePanels
Notifier by Honeywell
ID3000
49 sourced fault records
View fault recordsAdvanced Electronics
Advanced MxPro 4
15 sourced fault records
View fault recordsAdvanced Electronics
Advanced MxPro 5
19 sourced fault records
View fault recordsZiton
ZP2-FR
15 sourced fault records
View fault recordsKentec Electronics
Kentec Syncro AS
7 sourced fault records
View fault recordsProtec
Protec 6500
38 sourced fault records
View fault records