Fault codes by panel
Search fault records across 49 panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from.
Searches 608 records across 49 panels — 573 of them source-verified. Signed in, your dashboard fault search covers only the fully source-verified records, on any plan.
Want to test yourself? Try the free daily fault challenge.
30+ matches for “C-TEC”
Protec 6500
Fire Protection Fault
The "Fire Protection Fault" LED on the 6500 panel's indicator strip, covering fire protection outputs (e.g. suppression or protection-related outputs) configured on the system. This is one of the labelled LED indicators…
View on the Protec 6500 pageZiton ZP2-FR
Fire protection fault
The yellow Fire Protection Fault/Disabled/Test LED indicates a fire protection fault, disablement, or test. A flashing LED indicates a fault; a steady LED indicates a disablement or a test. From the ZP2 Series…
View on the Ziton ZP2-FR pageZeta Simpo
Fault Protection Panel Input Open
Circuit broken at input 'Protection Panel Fault'.
View on the Zeta Simpo pageZeta Simpo
Fault Protection Panel Input Short
Short circuit detected at input 'Protection Panel Fault'.
View on the Zeta Simpo pageZeta Simpo
Protection Alarm Confirm Open
Circuit broken at input 'Protection Alarm Confirmation'.
View on the Zeta Simpo pageZeta Simpo
Protection Alarm Confirm Short
Short circuit detected at input 'Protection Alarm Confirmation'.
View on the Zeta Simpo pageC-TEC XFP
Locating loop open or short circuits: BLINK DETECTOR LEDS
Per the manual, this engineering function momentarily asserts the LED outputs of loop devices in one continual sweep, and is useful for locating open or short circuit faults on the loop wiring. LEDs are asserted step by…
View on the C-TEC XFP pageHaes Systems Esento Excel 2-12 Zone
Zone detector removed
For zones 1 to 4 on the Main PCB, in fault diagnosis mode (press and hold ENTER) the Zone Fault/Disabled/Test LED going off after pressing ENTER, with a slow pulse shown in the table, means a detector has been removed…
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Eclipse 2-4 Zone
Zone detector removed
For zones 1 to 4 on the Main PCB, in fault diagnosis mode (press and hold ENTER) the Zone Fault/Disabled/Test LED going off after pressing ENTER, with a slow pulse shown in the table, means a detector has been removed…
View on the Haes Systems Esento Eclipse 2-4 Zone pageGlobal Fire Equipment OCTO+
No nodes detected
Given in the source only as an illustrative example ("Example: 'No nodes detected'") of the network status/error text shown by programming function 8-5-3 "Installation Status", which reports the status of the network.…
View on the Global Fire Equipment OCTO+ pageProtec 6500
Alarm Fault
The "Alarm Fault" LED on the 6500 panel's indicator strip. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from Protec's own product photography. The brochure…
View on the Protec 6500 pageProtec 6500
Alarm Routing Fault
The "Alarm Routing Fault" LED on the 6500 panel's indicator strip, covering the alarm signalling/routing path (e.g. to an ARC or monitoring centre). This is one of the labelled LED indicators on the 6500 control panel's…
View on the Protec 6500 pageProtec 6500
Aux Supply Fault
The "Aux Supply Fault" LED on the 6500 panel's indicator strip, covering the panel's auxiliary power supply. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from…
View on the Protec 6500 pageProtec 6500
Loop Drive Processor Fault
The loop driver processor has reported a fault. Take the reporting panel offline then back online to attempt to clear it; if it persists, report the fault to Protec technical support.
View on the Protec 6500 pageProtec 6500
Network - Duplicate Master
Two master panels have been detected on the network — either two panels were assigned as master in their configuration data (correct via the PC commissioning software), or a double break in the network wiring left two…
View on the Protec 6500 pageProtec 6500
Network Fault
The "Network Fault" LED on the 6500 panel's indicator strip, covering the panel-to-panel network connection used when multiple 6500 panels are networked together. This is one of the labelled LED indicators on the 6500…
View on the Protec 6500 pageProtec 6500
Power Fault
The "Power Fault" LED on the 6500 panel's indicator strip, covering the panel's own power supply. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from Protec's own…
View on the Protec 6500 pageProtec 6500
System Fault
The "System Fault" LED on the 6500 panel's indicator strip. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from Protec's own product photography. The brochure…
View on the Protec 6500 pageProtec 6100
Aux. Supply Fault (24 V output)
The manual says a fault has been detected with the auxiliary 24 V supply output of the 6100. There may no longer be an auxiliary supply to external devices, or the auxiliary devices are drawing too much current. The…
View on the Protec 6100 pageProtec 6100
Fire link Fault (monitored fire link path)
The manual says a fault has been detected on the monitored fire link path. This may be a wiring fault or a fire link interface fault. The connection to the fire station link is no longer reliable, and expert advice…
View on the Protec 6100 pageProtec 6100
General fault handling
The manual says that when the 6100 detects a fault in any of the critical operating paths it shows it on the front panel display and the internal buzzer pulses slowly. The General Fault indicator is illuminated and is…
View on the Protec 6100 pageProtec 6100
Repeat Panel Fault
The manual says a fault has been detected on a repeat panel connected to the 6100, or the wiring to the repeat panel is faulty. The General Fault indicator is illuminated accompanied by the Repeat Fault indicator.
View on the Protec 6100 pageProtec 6100
Supply Fault
The manual says a fault has been detected in the power supply of the 6100. This may be because the local mains supply has failed, or because the internal stand-by batteries or circuitry are faulty. The General Fault…
View on the Protec 6100 pageProtec 6100
System Faults
The manual says the 6100 performs regular self tests to ensure the software is working correctly. If a fault is detected in software operation a System Fault is declared. It is a latching fault and can only be cleared…
View on the Protec 6100 pageC-TEC CFP (2/4/8 Zone Standard Conventional)
Zone Fault
All zone circuits are monitored for open- and short-circuit faults and detector head removal (unless the zone is in alarm, test or disabled). The relevant Zone Fault light pulses yellow. Access level three fault…
View on the C-TEC CFP (2/4/8 Zone Standard Conventional) pageC-TEC CFP AlarmSense (2/4/8 Zone)
Zone Fault
All zone circuits (up to eight) are monitored for open circuit and short circuit faults and detector head removal, unless the zone is in an alarm condition or is in test or disabled. The relevant Zone Fault light pulses…
View on the C-TEC CFP AlarmSense (2/4/8 Zone) pageProtec 6500
Loop Drive Open Circuit
The loop has a break in its wiring. The fault threshold is set to 100Ω.
View on the Protec 6500 pageProtec 6500
Loop Drive Overload Fault
The loop cannot be driven due to an overload condition.
View on the Protec 6500 pageProtec 6500
Loop Drive Parallel Fault
There is a low resistance between loop '+' and loop '-'. The fault threshold is 200Ω (Issue E) or 120Ω (Issue F). This fault can also occur if more than ten loop device repeater LEDs are turned on at the same time.
View on the Protec 6500 pageProtec 6500
Loop Drive Series Fault
There is a high resistance in the loop wiring. The fault threshold is 80Ω (Issue E) or 50Ω (Issue F), though the manual adds that "any value greater than 32 is considered high" (no unit given). The loop current…
View on the Protec 6500 page