Protec 6500
Network - Duplicate Master
Two master panels have been detected on the network — either two panels were assigned as master in their configuration data (correct via the PC commissioning software), or a double break in the network wiring left two…
View on the Protec 6500 pageProtec 6500
Loop Drive Series Fault
There is a high resistance in the loop wiring. The fault threshold is 80Ω (Issue E) or 50Ω (Issue F), though any value greater than 32Ω is considered high. The loop current calculator in the commissioning software…
View on the Protec 6500 pageProtec 6500
Network - Duplicate Panel(s)
The network has initialised with two panels sharing the same number; correct this using the PC commissioning software. Neither panel is allowed to transmit an event, so each will eventually also display a Slave CTS…
View on the Protec 6500 pagePanels
Notifier by Honeywell
ID3000
49 sourced fault records
View fault recordsAdvanced Electronics
Advanced MxPro 4
15 sourced fault records
View fault recordsAdvanced Electronics
Advanced MxPro 5
19 sourced fault records
View fault recordsZiton
ZP2-FR
15 sourced fault records
View fault recordsKentec Electronics
Kentec Syncro AS
7 sourced fault records
View fault recordsProtec
Protec 6500
38 sourced fault records
View fault records