Fault codes by panel
Search fault records across 49 panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from.
Searches 608 records across 49 panels — 573 of them source-verified. Signed in, your dashboard fault search covers only the fully source-verified records, on any plan.
Want to test yourself? Try the free daily fault challenge.
20 matches for “CFP”
C-TEC CFP (2/4/8 Zone Standard Conventional)
General Fault
Flashes yellow when there is a fault on any part of the fire alarm system. It is always lit together with at least one other Fault light that shows the precise type of fault detected.
View on the C-TEC CFP (2/4/8 Zone Standard Conventional) pageC-TEC CFP (2/4/8 Zone Standard Conventional)
Power Supply Fault
Indicates one or more of: the mains supply is too low or has failed completely; the mains fuse (F1) has ruptured; the battery fuse (F2) has ruptured; the battery supply voltage is too low; or the panel's power supply…
View on the C-TEC CFP (2/4/8 Zone Standard Conventional) pageC-TEC CFP (2/4/8 Zone Standard Conventional)
Remote Output Fault
Flashes yellow when there is a fault on the output's auxiliary 24V supply — typically because the 24V auxiliary output (used to supply relays switched by the remote output) is overloaded and its protection fuse has…
View on the C-TEC CFP (2/4/8 Zone Standard Conventional) pageC-TEC CFP (2/4/8 Zone Standard Conventional)
Repeater Fault
Flashes yellow when the master panel cannot communicate with one or more repeater panels (if fitted). Access level three fault diagnosis shows which repeater(s), by zone light, are in fault.
View on the C-TEC CFP (2/4/8 Zone Standard Conventional) pageC-TEC CFP (2/4/8 Zone Standard Conventional)
Sounder Fault
All sounder circuits are monitored periodically for open- and short-circuit faults (unless disabled or in an alarm condition). If a fault is detected, this light pulses yellow. An unpolarised sounder will also show a…
View on the C-TEC CFP (2/4/8 Zone Standard Conventional) pageC-TEC CFP (2/4/8 Zone Standard Conventional)
Supply Present light not lit
If the green Supply Present light is not lit, either both the mains supply and standby batteries have failed, or the Power Supply PCB, the Main Control PCB, or the cable connecting them is faulty.
View on the C-TEC CFP (2/4/8 Zone Standard Conventional) pageC-TEC CFP (2/4/8 Zone Standard Conventional)
System Fault: PLL
Occurs as a result of a momentary disturbance in the panel's microprocessor. In access level three fault diagnosis this shows as Zone 3's Fault light lit.
View on the C-TEC CFP (2/4/8 Zone Standard Conventional) pageC-TEC CFP (2/4/8 Zone Standard Conventional)
System Fault: Site Memory Corruption
Occurs when site-specific data held in the panel's microprocessor is found to be corrupt. In access level three fault diagnosis this shows as Zone 2's Fault light lit.
View on the C-TEC CFP (2/4/8 Zone Standard Conventional) pageC-TEC CFP (2/4/8 Zone Standard Conventional)
System Fault: Watchdog
Occurs when the panel's microprocessor has failed to operate correctly; the watchdog circuit attempts to restart it. If it cannot, the General Fault and System Fault lights cycle continuously and the internal sounder…
View on the C-TEC CFP (2/4/8 Zone Standard Conventional) pageC-TEC CFP (2/4/8 Zone Standard Conventional)
Zone Fault
All zone circuits are monitored for open- and short-circuit faults and detector head removal (unless the zone is in alarm, test or disabled). The relevant Zone Fault light pulses yellow. Access level three fault…
View on the C-TEC CFP (2/4/8 Zone Standard Conventional) pageC-TEC CFP AlarmSense (2/4/8 Zone)
General Fault
Flashes yellow when there is a fault on any part of the fire alarm system. It is always lit together with at least one other Fault light that shows the precise type of fault detected. The panel's fault output also…
View on the C-TEC CFP AlarmSense (2/4/8 Zone) pageC-TEC CFP AlarmSense (2/4/8 Zone)
Power Supply Fault
Indicates one or more of: the mains supply is too low or has failed completely; the mains fuse (F1) has ruptured; the battery fuse (F2) has ruptured; the battery supply voltage is too low or the batteries are in poor…
View on the C-TEC CFP AlarmSense (2/4/8 Zone) pageC-TEC CFP AlarmSense (2/4/8 Zone)
Remote Output Fault
Flashes yellow when there is a fault on the output's auxiliary 24V supply — typically because the 24V auxiliary output (used to supply relays switched by the remote output) is overloaded and its protection fuse has…
View on the C-TEC CFP AlarmSense (2/4/8 Zone) pageC-TEC CFP AlarmSense (2/4/8 Zone)
Repeater Fault
Flashes yellow when the master panel cannot communicate with one or more repeater panels (if fitted). Access level three fault diagnosis shows which repeater(s) are in fault, by zone light.
View on the C-TEC CFP AlarmSense (2/4/8 Zone) pageC-TEC CFP AlarmSense (2/4/8 Zone)
Sounder Fault
The Sounder Status light pulses yellow when either a conventional sounder circuit has a fault, or an AlarmSense sounder on a zone circuit has a fault (in which case the relevant Zone Fault light also pulses). All…
View on the C-TEC CFP AlarmSense (2/4/8 Zone) pageC-TEC CFP AlarmSense (2/4/8 Zone)
Supply Present light not lit
If the green Supply Present light is not lit, either both the mains supply and standby batteries have failed, or the Power Supply PCB, the Main Control PCB, or the cable connecting them is faulty.
View on the C-TEC CFP AlarmSense (2/4/8 Zone) pageC-TEC CFP AlarmSense (2/4/8 Zone)
System Fault: PLL
Occurs as a result of a momentary disturbance in the panel's microprocessor. In access level three fault diagnosis this shows as Zone 3's Fault light lit.
View on the C-TEC CFP AlarmSense (2/4/8 Zone) pageC-TEC CFP AlarmSense (2/4/8 Zone)
System Fault: Site Memory Corruption
Occurs when site-specific data held in the panel's microprocessor is found to be corrupt. In access level three fault diagnosis this shows as Zone 2's Fault light lit.
View on the C-TEC CFP AlarmSense (2/4/8 Zone) pageC-TEC CFP AlarmSense (2/4/8 Zone)
System Fault: Watchdog
Occurs when the panel's microprocessor has failed to operate correctly; the watchdog circuit attempts to restart it. If it cannot, the General Fault and System Fault lights cycle continuously and the internal sounder…
View on the C-TEC CFP AlarmSense (2/4/8 Zone) pageC-TEC CFP AlarmSense (2/4/8 Zone)
Zone Fault
All zone circuits (up to eight) are monitored for open circuit and short circuit faults and detector head removal, unless the zone is in an alarm condition or is in test or disabled. The relevant Zone Fault light pulses…
View on the C-TEC CFP AlarmSense (2/4/8 Zone) page