Notifier by Honeywell ID50 / ID60

AUXILIARY SUPPLY FAULT

Source-checked

Message shown on the ID50/ID60 panel. The manual's Appendix 3 gives the meaning as: A fault with the auxiliary supply has been detected. Action listed in the manual: Check the auxiliary voltage and any associated wiring.

View on the Notifier by Honeywell ID50 / ID60 page

Zeta Simpo

Fault Power AUX

Source-checked

As given in the source's own event table: "Short circuit (the mains power supply is lost)" — the source's wording for this entry is terse and possibly abbreviated; quoted as written rather than expanded.

View on the Zeta Simpo page

Notifier by Honeywell ID3000

Aux. Output X Fault

Source-checked

Parameterised message covering auxiliary outputs 1 and 2 (X = 1 or 2), as printed in the source ('Aux. Output 1 Fault'; 'Aux. Output 2 Fault'). Indicates a failure of the auxiliary drive circuits, not the attached…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

SENSOR FAULT

Source-checked

For VIEW, MULTI (Optiplex), or SMART sensors: the analogue reading is below the Chamber fault threshold, or below the Maintenance Urgent threshold, or a Maintenance Alert has existed for longer than 100 days without any…

View on the Notifier by Honeywell ID3000 page

Protec 6500

Alarm Fault

Source-checked

The "Alarm Fault" LED on the 6500 panel's indicator strip. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from Protec's own product photography. The brochure…

View on the Protec 6500 page

Protec 6500

Alarm Routing Fault

Source-checked

The "Alarm Routing Fault" LED on the 6500 panel's indicator strip, covering the alarm signalling/routing path (e.g. to an ARC or monitoring centre). This is one of the labelled LED indicators on the 6500 control panel's…

View on the Protec 6500 page

Protec 6500

Aux Supply Fault

Source-checked

The "Aux Supply Fault" LED on the 6500 panel's indicator strip, covering the panel's auxiliary power supply. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from…

View on the Protec 6500 page

Protec 6500

Fire Protection Fault

Source-checked

The "Fire Protection Fault" LED on the 6500 panel's indicator strip, covering fire protection outputs (e.g. suppression or protection-related outputs) configured on the system. This is one of the labelled LED indicators…

View on the Protec 6500 page

Protec 6500

Network Fault

Source-checked

The "Network Fault" LED on the 6500 panel's indicator strip, covering the panel-to-panel network connection used when multiple 6500 panels are networked together. This is one of the labelled LED indicators on the 6500…

View on the Protec 6500 page

Protec 6500

Power Fault

Source-checked

The "Power Fault" LED on the 6500 panel's indicator strip, covering the panel's own power supply. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from Protec's own…

View on the Protec 6500 page

Protec 6500

System Fault

Source-checked

The "System Fault" LED on the 6500 panel's indicator strip. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from Protec's own product photography. The brochure…

View on the Protec 6500 page

Morley-IAS ZXSe

Earth Fault

Source-checked

Yellow Earth Fault indicator on the ZX series panel: an earth connection fault has occurred on a cable. To clear it, correct the fault condition and then perform a panel reset (page 7). The alphanumeric display shows a…

View on the Morley-IAS ZXSe page

Fike Twinflex

EARTH FAULT LED

Source-checked

Yellow EARTH FAULT indicator, flashing: the manual says an earth fault has been detected where a path exists from the circuit wiring to earth. Remove circuits one at a time to discover which one, and then rectify.

View on the Fike Twinflex page

Fike Twinflex

SYSTEM FAULT LED (continuous)

Source-checked

Yellow SYSTEM FAULT indicator, continuous: the manual says it indicates the presence of a processor or a checksum error. To clear it, power the system down, reprogram all settings and test the system. During a system…

View on the Fike Twinflex page

Nittan Evolution

Zone fault LED

Source-checked

The manual lists several reasons for the zone fault LED to light: a device has been removed from that zone; a device has been changed for one of a different type; there is a double address in the zone; or a device in…

View on the Nittan Evolution page

Siemens Fire Safety Cerberus PRO FC726

Control function Fault / Off (LED 12)

Source-checked

'Fire control line' fault. Action: Check the line for open line/short-circuit; check the function of the external control devices; check the function of any existing feedback switch.

View on the Siemens Fire Safety Cerberus PRO FC726 page

Protec 6100

Aux. Supply Fault (24 V output)

Source-checked

The manual says a fault has been detected with the auxiliary 24 V supply output of the 6100. There may no longer be an auxiliary supply to external devices, or the auxiliary devices are drawing too much current. The…

View on the Protec 6100 page

Fike Safety Technology CIE-A-200

Earth Fault

Source-checked

Per the manual, if the panel detects a short circuit or leakage current to earth/screen from one of its supply rails (0 V or +Ve) an Earth Fault is displayed. The normal voltage between 0 V and Earth SCRN is 1.7 V; the…

View on the Fike Safety Technology CIE-A-200 page

Fike Safety Technology Quadnet

Earth Fault

Source-checked

Per the manual, if the panel detects a short circuit to earth/screen from one of its supply rails (0 V or +ve) an Earth Fault is displayed. Remove the circuit cables one at a time and reset the system: when the faulty…

View on the Fike Safety Technology Quadnet page

Fike Safety Technology Quadnet

EARTH FAULT LED

Source-checked

Yellow EARTH FAULT indicator, flashing: the manual says an earth fault has been detected where a path exists from the circuit wiring to earth; remove circuits one at a time to discover which one, and then rectify. An…

View on the Fike Safety Technology Quadnet page

Global Fire Equipment Orion (2/4/8 Zone)

AUX. SUPPLY FAULT

Source-checked

This indicates the auxiliary supply has a fault.

View on the Global Fire Equipment Orion (2/4/8 Zone) page

C-TEC CFP (2/4/8 Zone Standard Conventional)

Remote Output Fault

Source-checked

Flashes yellow when there is a fault on the output's auxiliary 24V supply — typically because the 24V auxiliary output (used to supply relays switched by the remote output) is overloaded and its protection fuse has…

View on the C-TEC CFP (2/4/8 Zone Standard Conventional) page

C-TEC CFP AlarmSense (2/4/8 Zone)

Remote Output Fault

Source-checked

Flashes yellow when there is a fault on the output's auxiliary 24V supply — typically because the 24V auxiliary output (used to supply relays switched by the remote output) is overloaded and its protection fuse has…

View on the C-TEC CFP AlarmSense (2/4/8 Zone) page

C-TEC MFP Range (4-28 Zone) Conventional Fire Alarm Panel

General Fault

Source-checked

Lit whenever any fault condition exists on the panel. One documented specific cause: if the buzzer sounds and the General Fault light is lit steadily with no other cause found, the panel has been left in a test mode —…

View on the C-TEC MFP Range (4-28 Zone) Conventional Fire Alarm Panel page

Ziton ZP2-FR

System Overload

Source-checked

Added to the event log when one or more event types (alarm, zone alarm, fault, condition, etc.) exceed the maximum limit of 512 events per type — this limit applies at panel level and per system, including repeater…

View on the Ziton ZP2-FR page

Fike Safety Technology CIE-A-200

Addressable circuit: -ve open circuit

Source-checked

Per the manual, if the system faces a loop -ve open circuit during initialisation, initialisation does not fail at that point but continues to the end of the loop and all devices are operational (as long as no other…

View on the Fike Safety Technology CIE-A-200 page

Fike Safety Technology CIE-A-200

Loop not complete (loop +ve to -ve short circuit or +ve open circuit at initialisation)

Source-checked

Per the manual, if the system faces a loop +ve to -ve short circuit or a loop +ve open circuit during initialisation, initialisation fails at that point and a message of Loop not complete is displayed. Devices up to…

View on the Fike Safety Technology CIE-A-200 page

Fike Safety Technology Quadnet

Addressable circuit: -ve open circuit

Source-checked

Per the manual, if the system faces a loop -ve open circuit during initialisation, initialisation continues to the end of the loop and all devices are operational (as long as no other faults exist). A message of…

View on the Fike Safety Technology Quadnet page