Advanced MxPro 4
DEVICE MISSING
Shown against the specific loop address, zone and location text on the display, e.g. "1 004.0 DEVICE MISSING" under the zone's fault list. Indicates the panel is no longer receiving a response from that addressed device.
View on the Advanced MxPro 4 pageZeta Simpo
Loop Device Fault
The device does not respond (lost or damaged).
View on the Zeta Simpo pageZeta Simpo
Periphery Device Fault
The device is not responding (the device is lost or failed).
View on the Zeta Simpo pageHochiki HFP AP-1AS/2AS
Loop open circuit or short circuit (how the panel responds)
Per the manual, power is driven from the LOOP OUT terminals and returned to the LOOP IN terminals, where it is monitored for loop continuity. If the loop is open circuit (a cable fault, or a short circuit isolator…
View on the Hochiki HFP AP-1AS/2AS pageSimplex 2050FS / 2250FS Foundation Series
NO ANSWER
The operation guide uses NO ANSWER for a stored loop device that is not responding and provides a controlled same-type replacement workflow.
View on the Simplex 2050FS / 2250FS Foundation Series pageZeta Premier
The Fault Condition (general response)
Per the manual, a fault is indicated if any part of the system enters an abnormal condition. The COMMON FAULT LED pulses (and the ALARM FAULT/DISABLEMENT LED also pulses if the fault is with an alarm circuit), the…
View on the Zeta Premier pageNotifier by Honeywell ID3000
Panel Fault 17 - Card Missing
Loop PCB missing or failed to respond. Possible causes are: a. Wrong ribbon cable connected; b. Ribbon cable disconnected; c. Loop PCB failure. Action: For the last case, change the loop PCB (PN: 020-588).
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Sounder Cct.X OPEN-CIRCUIT
Parameterised message covering sounder circuits 1-4 (X = 1, 2, 3 or 4), as printed in the source. Indicates an open circuit (disconnection condition) fault on the sounder circuit wiring. Action: For circuits 3 and 4,…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Sounder Cct.X SHORT-CCT.
Parameterised message covering sounder circuits 1-4 (X = 1, 2, 3 or 4), as printed in the source. Indicates a short circuit fault on the corresponding sounder circuit wiring. Action: For circuits 3 and 4, check that the…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID3000
Terminal Link Fault
This fault indicates that the peripheral unit connected to the third-party-protocol RS232 port has not responded to the enquiry code sent, or the link to the third-party equipment is not connected (this would normally…
View on the Notifier by Honeywell ID3000 pageZiton ZP2-FR
Earth fault
The yellow Earth Fault LED indicates an earth isolation fault. Earth fault reporting can be switched off under Panel setup > Other settings > Fault notification ("Earth", available on fire alarm control panels and…
View on the Ziton ZP2-FR pageFireClass FC501
REPEATER COMMUNIC.
A repeater on the RS485 does not respond
View on the FireClass FC501 pageSiemens Fire Safety Cerberus PRO FC726
'Zone', 'Serial no. ("ID-Nr.")', 'Dev.location fault'
Displayed for each swapped C-NET device if the C-NET detector line was restarted after devices of the same type were swapped over in their bases. To clear, at least the device types in the corresponding bases must be…
View on the Siemens Fire Safety Cerberus PRO FC726 pageC-TEC ZFP
Displaying and clearing fault conditions
Per the manual, when a fault occurs one or more Fault indicators flash yellow, the internal buzzer sounds (if enabled) and the fault button on the touchscreen changes from blue to yellow with the number of faults shown.…
View on the C-TEC ZFP pageC-TEC XFP
Fault conditions (what the display shows, including Device Missing example)
Per the user manual, if part of the fire alarm system fails (for example detector failure or a wiring fault), one or more of the panel's fault indicators flash, the internal sounder (if enabled) pulses, and the display…
View on the C-TEC XFP pageFike Safety Technology CIE-A-200
Loop not complete (loop +ve to -ve short circuit or +ve open circuit at initialisation)
Per the manual, if the system faces a loop +ve to -ve short circuit or a loop +ve open circuit during initialisation, initialisation fails at that point and a message of Loop not complete is displayed. Devices up to…
View on the Fike Safety Technology CIE-A-200 pageNotifier by Honeywell ID50 / ID60
DEVICE FAILED AUTO HIGH TEST
Message shown on the ID50/ID60 panel. The manual's Appendix 3 gives the meaning as: During automatic testing of loop devices a specific device did not respond as expected. Action listed in the manual: Change device.
View on the Notifier by Honeywell ID50 / ID60 pageNotifier by Honeywell ID50 / ID60
DOUBLE ADDRESS
Message shown on the ID50/ID60 panel. The manual's Appendix 3 gives the meaning as: Two loop addresses are responding to the same address. Action listed in the manual: Change one of the two devices to a different…
View on the Notifier by Honeywell ID50 / ID60 pageNotifier by Honeywell ID50 / ID60
NO REPLY FROM DEVICE
Message shown on the ID50/ID60 panel. The manual's Appendix 3 gives the meaning as: A loop device at a specific address is not responding, possibly missing or incorrect panel configuration. Action listed in the manual:…
View on the Notifier by Honeywell ID50 / ID60 pageZeta Premier Elite (4 to 8 zone)
Faults are non-latching (system fault excepted)
The manual says most faults need checking by an engineer, but the system can be checked for a removed detector by the responsible person. All faults in the Premier Elite are non-latching: they cannot be reset with the…
View on the Zeta Premier Elite (4 to 8 zone) pageZeta Premier
RMVD
LCD event text on the Zeta Premier AL. The manual's Appendix D describes it as: Removed: the loop device is not responding.
View on the Zeta Premier pageHaes Systems Esprit Apollo Addressable
Battery high impedance fault (Batt Hi Z)
The power supply specification lists the battery high impedance fault (Batt Hi Z) as resistance above 1 ohm, with a 1-hour reporting time.
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
General Fault LED pulsing (fault condition)
When the panel detects a fault the display indicates the number and nature of the fault(s), the internal buzzer sounds an intermittent tone and the amber General Fault LED pulses, with any other specific Fault LEDs lit.…
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
Loop fault: short circuit or interruption
If a fault occurs on a transmission path (short circuit or interruption), the manual says the function of the remaining operational devices is re-established within 300 seconds of the fault, compliant with EN 54-2…
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
Power Supply Fault LED
The Power Supply Fault LED pulsing indicates a power supply fault on the mains power input or battery. Steady indicates the same fault with the buzzer muted.
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
Power Supply Fault on connecting mains before batteries
If the mains is connected before the batteries, the panel shows a Power Supply Fault for up to 1 minute until the monitoring cycle has finished polling. The manual says this is normal, and to check connections if the…
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
Sounder Status LED pulsing
The Sounder Status LED pulsing indicates a fault on one or more sounder circuits. The same LED steady indicates sounder circuits have been disabled or are in test mode.
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
System Fault LED
The System Fault LED steady indicates a system failure, that the panel is not functional, or that the internal PCB configuration has not been set up correctly. Pulsing indicates the panel has recovered from a system…
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
System fault recovery
System Fault LED pulsing, General Fault LED pulsing and a pulsed (fault tone) buzzer indicate a system fault has occurred and the affected board has recovered. The indication remains until the panel is reset.
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
System fault: display board (main control board)
A system fault is a processor watchdog time-out or processor failure. With only the System Fault LED lit and a continuous buzzer, the display board (main control board) is halted and no other indication or control is…
View on the Haes Systems Esprit Apollo Addressable page