Nittan Evolution
Break in -ve wire (ISOLATOR FAULT)
Reported as an ISOLATOR FAULT with a description. The manual says to use the same method to locate the break (re-run the loop search and check the detailed loop report). In its example, the break is between address 150,…
View on the Nittan Evolution pageNittan Evolution
Break in +ve wire (ISOLATOR FAULT)
The manual says the panel's loop isolator monitors the addressable loop for open and short circuit faults, reported as ISOLATOR FAULTS with a description. For a break in the positive wire, it says to locate the cable…
View on the Nittan Evolution pageNittan Evolution
Short circuit on side A of the loop (ISOLATOR FAULT)
If the panel reports a loop short on side A, the manual says there is a short circuit fault on the loop somewhere between the panel (side A) and the first device with a short circuit isolator on the loop.
View on the Nittan Evolution pageNittan Evolution
Short circuit on side B of the loop (ISOLATOR FAULT)
If the panel reports a loop short on side B, the manual says there is a short circuit fault on the loop somewhere between the panel (side B) and the last device with a short circuit isolator on the loop.
View on the Nittan Evolution pageNittan Evolution
Zone fault LED
The manual lists several reasons for the zone fault LED to light: a device has been removed from that zone; a device has been changed for one of a different type; there is a double address in the zone; or a device in…
View on the Nittan Evolution pageNittan Evolution
Earth Negative Fault
Something is shorting to earth on the negative side. Located using the same method as an Earth Positive Fault, but looking for shorts to loop negative rather than positive.
View on the Nittan Evolution pageNittan Evolution
Earth Positive Fault
Something is shorting to earth on the positive side (usually through a cable screen). Most earth faults occur on the addressable loop — disconnect all loop connections and reset the panel; if no earth fault is reported…
View on the Nittan Evolution pageNittan Evolution
System Fault
A system fault is an abnormal microprocessor running condition caused by various unexpected phenomena. The panel attempts to correct itself; while the fault is present the System Fault LED, General Fault LED, General…
View on the Nittan Evolution pageNittan Evolution
Battery high impedance fault
The panel has measured the battery internal resistance and determined it is too high. The batteries will need to be replaced.
View on the Nittan Evolution pageNittan Evolution
Charger Fault
The panel has determined that the power supply is not charging the batteries. This is likely to be a problem with the Charger PCB — contact the supplier to arrange a replacement.
View on the Nittan Evolution pageNittan Evolution
DOUBLE ADDRESS FAULT
Two or more devices may have the same address setting. All devices with the same address will answer at the same time and the panel will not be able to understand the reply it receives. Search the detailed loop report…
View on the Nittan Evolution pageNittan Evolution
Mains Supply Fault
Check if mains power is present, and check for 29.5V DC at the PSU cage output.
View on the Nittan Evolution page