Siemens Fire Safety Cerberus PRO FC726

Alarm device Fault / Off (LED 10)

Source-checked

'Acoustic control line' fault. Action: Check the line for open line/short-circuit, or a missing/defective end-of-line element (EOL).

View on the Siemens Fire Safety Cerberus PRO FC726 page

Siemens Fire Safety Cerberus PRO FC726

Communication fault of a networked 'Station'

Source-checked

Action: Check the transmission line; check the faulty 'Station'.

View on the Siemens Fire Safety Cerberus PRO FC726 page

Siemens Fire Safety Cerberus PRO FC726

Control function Fault / Off (LED 12)

Source-checked

'Fire control line' fault. Action: Check the line for open line/short-circuit; check the function of the external control devices; check the function of any existing feedback switch.

View on the Siemens Fire Safety Cerberus PRO FC726 page

Siemens Fire Safety Cerberus PRO FC726

Control panel communication fault

Source-checked

An FC726S or FC726S-10 cannot communicate correctly with other control panels on the documented FC-NET/SASF-NET system.

View on the Siemens Fire Safety Cerberus PRO FC726 page

Siemens Fire Safety Cerberus PRO FC726

FAULT (LED 1)

Source-checked

The 'Site' has a fault. Action: Check whether another fault LED is flashing; if not, check the display, and check whether the 'Fault' control input is activated.

View on the Siemens Fire Safety Cerberus PRO FC726 page

Siemens Fire Safety Cerberus PRO FC726

Fault of a component

Source-checked

Listed in the fault-message table on the row after System Fault (LED 5), with no LED number of its own. Action: Restart the 'Station'; when the fault is still indicated, exchange the module.

View on the Siemens Fire Safety Cerberus PRO FC726 page

Siemens Fire Safety Cerberus PRO FC726

Line (card) fault

Source-checked

The FC726S or FC726S-10 has detected a line-card, address, C-NET communications/power-line or field-device condition.

View on the Siemens Fire Safety Cerberus PRO FC726 page

Siemens Fire Safety Cerberus PRO FC726

Power supply fault

Source-checked

The FC726S or FC726S-10 has detected a power-supply condition covered by the commissioning guide.

View on the Siemens Fire Safety Cerberus PRO FC726 page

Siemens Fire Safety Cerberus PRO FC726

Remote alarm Fault / Off (LED 8)

Source-checked

Transmission equipment has a 'Fault'. Action: Check remote transmission.

View on the Siemens Fire Safety Cerberus PRO FC726 page

Siemens Fire Safety Cerberus PRO FC726

'Zone', 'Serial no. ("ID-Nr.")', 'Dev.location fault'

Source-checked

Displayed for each swapped C-NET device if the C-NET detector line was restarted after devices of the same type were swapped over in their bases. To clear, at least the device types in the corresponding bases must be…

View on the Siemens Fire Safety Cerberus PRO FC726 page

Siemens Fire Safety Cerberus PRO FC726

System Fault (LED 5)

Source-checked

Failure of the main CPU. Action: Visual check of the cable connections; check whether the red LED H37 on the operating unit FCM72xx is on — if so, exchange the PMI & mainboard.

View on the Siemens Fire Safety Cerberus PRO FC726 page

Siemens Fire Safety Cerberus PRO FC726

'Zone', 'Serial no. ("ID-Nr.")', 'Device missing'

Source-checked

Shown on the Person Machine Interface display for each C-NET device that has been swapped over with another non-stationary device of the same type in its base (e.g. during work on the line), leaving the 'Line' not…