Fault records by panel
Search fault records across 49 panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from.
Searches 608 records across 49 panels — 573 of them source-verified. Signed in, your dashboard fault search covers only the fully source-verified records, on any plan.
Want to test yourself? Try the free daily fault challenge.
30+ partial matches for “Fike manuals”
Nothing matched every word, so these match some of them. Check the record and panel before relying on it.
Fike Twinflex
Display blank and no LEDs showing
The manual says that if the display is blank and no LEDs are showing, either the unit is not powered or the mains has failed and the batteries are lower than 21 V. To recover from the low-battery shut-off, power down…
View on the Fike Twinflex pageFike Twinflex
EARTH FAULT LED
Yellow EARTH FAULT indicator, flashing: the manual says an earth fault has been detected where a path exists from the circuit wiring to earth. Remove circuits one at a time to discover which one, and then rectify.
View on the Fike Twinflex pageFike Twinflex
FAULT LED
Yellow FAULT indicator, continuous: the manual says the control panel is in the fault state and other indicators will show the origin. The indication can also be confirmed from the message in the panel information…
View on the Fike Twinflex pageFike Twinflex
FIRE OUTPUT fault LED
Yellow FIRE OUTPUT indicator, flashing: the manual says a fault condition is present on a monitored relay circuit. Continuous means a device or an action associated with the monitored relay circuit has been disabled.
View on the Fike Twinflex pageFike Twinflex
POWER FAULT LED (continuous)
Yellow POWER FAULT indicator, continuous: the manual says a battery fault has been detected, and to check the batteries and the in-line battery fuse.
View on the Fike Twinflex pageFike Twinflex
POWER FAULT LED (flashing)
Yellow POWER FAULT indicator, flashing: the manual says a mains supply fault has been detected, and to check for a 230 V AC supply on the incoming AC terminals.
View on the Fike Twinflex pageFike Twinflex
SOUNDER fault LED
Yellow SOUNDER indicator, flashing: the manual says a fault condition is present on a monitored sounder circuit. Continuous means a device or an action associated with the monitored sounder circuits has been disabled.
View on the Fike Twinflex pageFike Twinflex
SYSTEM FAULT LED (continuous)
Yellow SYSTEM FAULT indicator, continuous: the manual says it indicates the presence of a processor or a checksum error. To clear it, power the system down, reprogram all settings and test the system. During a system…
View on the Fike Twinflex pageFike Twinflex
SYSTEM FAULT LED (flashing, write enable)
Yellow SYSTEM FAULT indicator, flashing: the manual says this LED is also illuminated if the write protect / write enable switch is left on while the system is not in the engineer menu. In access levels 1 and 2 a system…
View on the Fike Twinflex pageFike Twinflex
ZONE fault LED
Yellow ZONE indicator, flashing: the manual says a fault condition is present on one of the zones or on a device connected to that zone. Continuous means a device or an action associated with a zone has been disabled.
View on the Fike Twinflex pageFike Safety Technology CIE-A-400
DEVICE QUANTITY MISMATCH
The number of devices found during CIE-A-400 loop initialisation does not match the number programmed in the approved OSP configuration.
View on the Fike Safety Technology CIE-A-400 pageFike Safety Technology CIE-A-400
Earth Fault
The CIE-A-400 has detected a short or leakage path between earth or screen and either 0 V or a positive circuit conductor.
View on the Fike Safety Technology CIE-A-400 pageFike Safety Technology CIE-A-400
Loop O/C
The CIE-A-400 has recorded an intermittent or recurrent open-circuit condition on an addressable loop.
View on the Fike Safety Technology CIE-A-400 pageFike Safety Technology CIE-A-400
LP "X" OPEN CCT -VE CORE
The CIE-A-400 has identified an open circuit on the negative core of the indicated loop during initialisation.
View on the Fike Safety Technology CIE-A-400 pageFike Safety Technology CIE-A-400
Smoke Sensor Failed - Signal High
The CIE-A-400 has received an abnormally high smoke-sensor signal from the identified Sita detector.
View on the Fike Safety Technology CIE-A-400 pageFike Safety Technology CIE-A-200
Addressable circuit: -ve open circuit
Per the manual, if the system faces a loop -ve open circuit during initialisation, initialisation does not fail at that point but continues to the end of the loop and all devices are operational (as long as no other…
View on the Fike Safety Technology CIE-A-200 pageFike Safety Technology CIE-A-200
Device faults during initialisation
Per the manual, if the system detects a device fault or fire activation during initialisation, initialisation does not fail at that point. Beyond certain limits initialisation will fail and the various fault or fire…
View on the Fike Safety Technology CIE-A-200 pageFike Safety Technology CIE-A-200
Device Quantity Mismatch
Per the manual, a device mismatch occurs if a device or devices have been physically removed from or added to the system and the changes have not been updated in the OSP and downloaded into the panel; the panel expects…
View on the Fike Safety Technology CIE-A-200 pageFike Safety Technology CIE-A-200
Earth Fault
Per the manual, if the panel detects a short circuit or leakage current to earth/screen from one of its supply rails (0 V or +Ve) an Earth Fault is displayed. The normal voltage between 0 V and Earth SCRN is 1.7 V; the…
View on the Fike Safety Technology CIE-A-200 pageFike Safety Technology CIE-A-200
FAULT LED
Yellow FAULT indicator, continuous: the manual says the control panel is in the fault state and other indicators will show the origin.
View on the Fike Safety Technology CIE-A-200 pageFike Safety Technology CIE-A-200
FIRE OUTPUT FAULT LED
Yellow FIRE OUTPUT FAULT indicator, continuous: the manual says a fault condition is present on a monitored fire output circuit or on the addressable device loop outputs.
View on the Fike Safety Technology CIE-A-200 pageFike Safety Technology CIE-A-200
Loop not complete (loop +ve to -ve short circuit or +ve open circuit at initialisation)
Per the manual, if the system faces a loop +ve to -ve short circuit or a loop +ve open circuit during initialisation, initialisation fails at that point and a message of Loop not complete is displayed. Devices up to…
View on the Fike Safety Technology CIE-A-200 pageFike Safety Technology CIE-A-200
POWER FAULT LED
Yellow POWER FAULT indicator, continuous: the manual says the mains supply or standby battery supply has failed, and to check the fuses, battery and the 230 V AC supply.
View on the Fike Safety Technology CIE-A-200 pageFike Safety Technology CIE-A-200
SOUNDER FAULT LED
Yellow SOUNDER FAULT indicator, continuous: the manual says a fault condition is present on a monitored sounder circuit or on the addressable device loop sounders.
View on the Fike Safety Technology CIE-A-200 pageFike Safety Technology CIE-A-200
SYSTEM FAULT LED
Yellow SYSTEM FAULT indicator, continuous: the manual says it indicates the presence of a processor or a checksum error. Power the system down to clear, reprogram all settings and test the system.
View on the Fike Safety Technology CIE-A-200 pageFike Safety Technology Quadnet
Addressable circuit: -ve open circuit
Per the manual, if the system faces a loop -ve open circuit during initialisation, initialisation continues to the end of the loop and all devices are operational (as long as no other faults exist). A message of…
View on the Fike Safety Technology Quadnet pageFike Safety Technology Quadnet
Device Quantity Mismatch
Per the manual, after initialising the loop, if the number of devices initialised does not match the number programmed, a DEVICE QUANTITY MISMATCH screen appears showing the number found and programmed. A mismatch…
View on the Fike Safety Technology Quadnet pageFike Safety Technology Quadnet
Device(s) Lost
Per the manual, if no obvious causes are apparent, replace the device. It also notes that a short circuit between cores with a value between 3 k and 300 ohms can corrupt data on the loop even though no short circuit…
View on the Fike Safety Technology Quadnet pageFike Safety Technology Quadnet
Earth Fault
Per the manual, if the panel detects a short circuit to earth/screen from one of its supply rails (0 V or +ve) an Earth Fault is displayed. Remove the circuit cables one at a time and reset the system: when the faulty…
View on the Fike Safety Technology Quadnet pageFike Safety Technology Quadnet
EARTH FAULT LED
Yellow EARTH FAULT indicator, flashing: the manual says an earth fault has been detected where a path exists from the circuit wiring to earth; remove circuits one at a time to discover which one, and then rectify. An…
View on the Fike Safety Technology Quadnet page