EMS Fire FireCell

Battery Fault (device)

Source-checked

In the device Fault Status menu, this shows the device has either a low battery (minimum operational life 7-30 days remaining) or a battery missing.

View on the EMS Fire FireCell page

EMS Fire FireCell

Battery Fault (Hub/RCC)

Source-checked

In the Hub/RCC Fault Status menu, this indicates either no battery present, a low battery, or a battery charger failure on an RCC.

View on the EMS Fire FireCell page

EMS Fire FireCell

Head Fault

Source-checked

In the device Fault Status menu, this indicates a detector's head has a fault, i.e. no communication between the head and the wireless base.

View on the EMS Fire FireCell page

EMS Fire FireCell

Mains Fault

Source-checked

In the Hub/RCC Fault Status menu, this indicates there is no mains present on the Radio Cluster Communicator (RCC).

View on the EMS Fire FireCell page

EMS Fire FireCell

PSU Fault LED

Source-checked

The PSU's Fault LED illuminates whilst any fault is present at the PSU.

View on the EMS Fire FireCell page

EMS Fire FireCell

Signal Fault

Source-checked

In the device Fault Status menu, this is shown for two reasons: there has been no communication between the device and its Radio Cluster Communicator (RCC) for 300 seconds, or the signalling path is poor and…

View on the EMS Fire FireCell page

EMS Fire FireCell

Aerial Tamper

Source-checked

In the Hub/RCC Fault Status menu, this indicates a remote aerial on the RCC or Radio Hub is not attached or is damaged (monitoring resistance of 47 kΩ not present). The manual separately notes the Radio Hub's…

View on the EMS Fire FireCell page

EMS Fire FireCell

Checksum Error

Source-checked

In the Hub/RCC Fault Status menu, this message is displayed if an error is detected in either the software program or the configuration data. The manual separately notes the Radio Hub's front-plate yellow System Fault…

View on the EMS Fire FireCell page

EMS Fire FireCell

DEV Ch1 RFI Det

Source-checked

In the Hub/RCC Fault Status menu, this indicates radio-frequency interference has been detected on radio channel 1 of the radio device-to-RCC communication path.

View on the EMS Fire FireCell page

EMS Fire FireCell

DEV Ch2 RFI Det

Source-checked

In the Hub/RCC Fault Status menu, this indicates radio-frequency interference has been detected on radio channel 2 of the radio device-to-RCC communication path.

View on the EMS Fire FireCell page

EMS Fire FireCell

Head Dirty

Source-checked

In the device Fault Status menu, this shows the detector's head is deemed dirty or contaminated.

View on the EMS Fire FireCell page

EMS Fire FireCell

Head Missing

Source-checked

In the device Fault Status menu, this indicates the detector's head, sounder, strobe-only or sounder/strobe head is not currently fitted on the wireless base.

View on the EMS Fire FireCell page

EMS Fire FireCell

In Tamper

Source-checked

In the device Fault Status menu on the Radio Hub, this indicates the device's tamper switch is not currently making contact against the ceiling- or wall-mounted base plate.

View on the EMS Fire FireCell page

EMS Fire FireCell

No Signal/PSU

Source-checked

In the Hub/RCC Fault Status menu, this indicates there has been no communication between the Radio Hub and an RCC for 300 seconds, or communication is being achieved but not at an acceptable level; it may also indicate…

View on the EMS Fire FireCell page

EMS Fire FireCell

No Sndr Audio

Source-checked

In the device Fault Status menu: the primary and secondary stage sounder tones can be monitored; if enabled and no audio is detected within 10 seconds of sounder activation, this fault is indicated.

View on the EMS Fire FireCell page

EMS Fire FireCell

Open Circuit

Source-checked

In the device Fault Status menu, this indicates an open-circuit wiring fault on the input of an Input/Output (I/O) unit.

View on the EMS Fire FireCell page

EMS Fire FireCell

Processor Fail

Source-checked

In the Hub/RCC Fault Status menu, this indicates the on-board processor on an RCC or the Radio Hub is in a failure condition.

View on the EMS Fire FireCell page

EMS Fire FireCell

RCC Ch1 RFI Det

Source-checked

In the Hub/RCC Fault Status menu, this indicates radio-frequency interference has been detected on radio channel 1 of the RCC network communication path.

View on the EMS Fire FireCell page

EMS Fire FireCell

RCC Ch2 RFI Det

Source-checked

In the Hub/RCC Fault Status menu, this indicates radio-frequency interference has been detected on radio channel 2 of the RCC network communication path.

View on the EMS Fire FireCell page

EMS Fire FireCell

Receiver Fail

Source-checked

In the Hub/RCC Fault Status menu, this indicates one of the on-board wireless receivers on an RCC or the Radio Hub is in a failure condition.

View on the EMS Fire FireCell page

EMS Fire FireCell

Short Circuit

Source-checked

In the device Fault Status menu, this indicates a short-circuit wiring fault on the input of an Input/Output (I/O) unit.

View on the EMS Fire FireCell page

EMS Fire FireCell

Unassigned

Source-checked

In the device Fault Status menu, this indicates the device is not yet assigned to the system. Assign it via the rotary control or the Assign Devices menu option.

View on the EMS Fire FireCell page