Siemens Fire Safety Cerberus PRO FC726
Control function Fault / Off (LED 12)
'Fire control line' fault. Action: Check the line for open line/short-circuit; check the function of the external control devices; check the function of any existing feedback switch.
View on the Siemens Fire Safety Cerberus PRO FC726 pageSiemens Fire Safety Cerberus PRO FC726
Control panel communication fault
An FC726S or FC726S-10 cannot communicate correctly with other control panels on the documented FC-NET/SASF-NET system.
View on the Siemens Fire Safety Cerberus PRO FC726 pageBosch Security Systems AVENAR panel 2000
BCM Battery Controller Module fault
No individual cause or remedy is stated beyond the message name; the source only states that the FPP-5000-TI13 Communication Interface transmits this fault to the panel. No cause is asserted here beyond what the source…
View on the Bosch Security Systems AVENAR panel 2000 pageBosch Security Systems AVENAR panel 8000
BCM Battery Controller Module fault
No individual cause or remedy is stated beyond the message name; the source only states that the FPP-5000-TI13 Communication Interface transmits this fault to the panel. No cause is asserted here beyond what the source…
View on the Bosch Security Systems AVENAR panel 8000 pageHaes Systems Esprit Apollo Addressable
System fault: display board (main control board)
A system fault is a processor watchdog time-out or processor failure. With only the System Fault LED lit and a continuous buzzer, the display board (main control board) is halted and no other indication or control is…
View on the Haes Systems Esprit Apollo Addressable pageZiton ZP2-FR
Earth fault
The yellow Earth Fault LED indicates an earth isolation fault. Earth fault reporting can be switched off under Panel setup > Other settings > Fault notification ("Earth", available on fire alarm control panels and…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Fire protection fault
The yellow Fire Protection Fault/Disabled/Test LED indicates a fire protection fault, disablement, or test. A flashing LED indicates a fault; a steady LED indicates a disablement or a test. From the ZP2 Series…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Mains / mains fuse fault
The yellow Supply Fault LED indicates a power supply fault. A steady LED indicates a mains or mains fuse fault (a flashing LED indicates a battery fault). From the ZP2 Series Installation Manual, Table 3 "Common…
View on the Ziton ZP2-FR pageZiton ZP2-FR
Sounder fault
The yellow Sounder Fault/Disabled/Test LED indicates a sounder fault, disablement, or test. A flashing LED indicates a fault; a steady LED indicates a disablement or a test. From the ZP2 Series Installation Manual,…
View on the Ziton ZP2-FR pageKentec Syncro AS
Double address (fault announced at loop initialisation)
Per the manual, the control panel can detect devices that have been set to the same address and will announce a “Double address” fault if it finds any. It cannot tell which devices are double addressed. To help find…
View on the Kentec Syncro AS pageProtec 6500
Alarm Fault
The "Alarm Fault" LED on the 6500 panel's indicator strip. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from Protec's own product photography. The brochure…
View on the Protec 6500 pageProtec 6500
Alarm Routing Fault
The "Alarm Routing Fault" LED on the 6500 panel's indicator strip, covering the alarm signalling/routing path (e.g. to an ARC or monitoring centre). This is one of the labelled LED indicators on the 6500 control panel's…
View on the Protec 6500 pageProtec 6500
Aux Supply Fault
The "Aux Supply Fault" LED on the 6500 panel's indicator strip, covering the panel's auxiliary power supply. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from…
View on the Protec 6500 pageProtec 6500
Fire Protection Fault
The "Fire Protection Fault" LED on the 6500 panel's indicator strip, covering fire protection outputs (e.g. suppression or protection-related outputs) configured on the system. This is one of the labelled LED indicators…
View on the Protec 6500 pageProtec 6500
Network Fault
The "Network Fault" LED on the 6500 panel's indicator strip, covering the panel-to-panel network connection used when multiple 6500 panels are networked together. This is one of the labelled LED indicators on the 6500…
View on the Protec 6500 pageProtec 6500
Power Fault
The "Power Fault" LED on the 6500 panel's indicator strip, covering the panel's own power supply. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from Protec's own…
View on the Protec 6500 pageProtec 6500
System Fault
The "System Fault" LED on the 6500 panel's indicator strip. This is one of the labelled LED indicators on the 6500 control panel's front fascia, confirmed directly from Protec's own product photography. The brochure…
View on the Protec 6500 pageFike Twinflex
FAULT LED
Yellow FAULT indicator, continuous: the manual says the control panel is in the fault state and other indicators will show the origin. The indication can also be confirmed from the message in the panel information…
View on the Fike Twinflex pageSiemens Fire Safety Cerberus PRO FC726
Alarm device Fault / Off (LED 10)
'Acoustic control line' fault. Action: Check the line for open line/short-circuit, or a missing/defective end-of-line element (EOL).
View on the Siemens Fire Safety Cerberus PRO FC726 pageSiemens Fire Safety Cerberus PRO FC726
FAULT (LED 1)
The 'Site' has a fault. Action: Check whether another fault LED is flashing; if not, check the display, and check whether the 'Fault' control input is activated.
View on the Siemens Fire Safety Cerberus PRO FC726 pageC-TEC ZFP
System Fault LED (steady yellow)
Per the manual, a steady yellow System Fault indicator means a system error, such as a microprocessor fault, has occurred, and it remains lit even if the system fault clears. It can only be cleared by pressing the…
View on the C-TEC ZFP pageFike Safety Technology CIE-A-200
FAULT LED
Yellow FAULT indicator, continuous: the manual says the control panel is in the fault state and other indicators will show the origin.
View on the Fike Safety Technology CIE-A-200 pageZeta Premier Elite (4 to 8 zone)
System fault
Per the manual, a system fault is an abnormal microprocessor running condition due to various unexpected phenomena, and the panel attempts to correct itself. The System Fault LED, General Fault LED, General Fault relay…
View on the Zeta Premier Elite (4 to 8 zone) pageHochiki HFP AP-1AS/2AS
Double address (fault announced at loop initialisation)
Per the manual, the control panel can detect devices set to the same address and will announce a “Double address” fault if it finds any. It cannot tell which devices are double addressed. To help find them, go to access…
View on the Hochiki HFP AP-1AS/2AS pageZeta Premier
The Fault Condition (general response)
Per the manual, a fault is indicated if any part of the system enters an abnormal condition. The COMMON FAULT LED pulses (and the ALARM FAULT/DISABLEMENT LED also pulses if the fault is with an alarm circuit), the…
View on the Zeta Premier pageHaes Systems Esento Excel 2-12 Zone
System fault: display board
A system fault is indicated when a processor controlling a function in the panel has a watchdog time out or processor failure. With only the System Fault LED continuous and a continuous buzzer, display board TPCA03 is…
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
System fault: repeater comms board
A continuous System Fault LED with the General Fault LED pulsing and the Repeater Fault LED continuous means Comms Board TPCA05 is halted. The fault relay and output are active and repeater panels cease to function.…
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esprit Apollo Addressable
System fault: extension LED board
On the optional extension LED board, a continuous System Fault LED with the General Fault LED pulsing means the extension LED board is halted. The fault relay is active, and fire alarms can still be detected and…
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esento Eclipse 2-4 Zone
System fault: display board
A system fault is a processor watchdog time out or processor failure. With only the System Fault LED continuous and a continuous buzzer, display board TPCA02 is halted and no other indication or control is possible. The…
View on the Haes Systems Esento Eclipse 2-4 Zone pageC-TEC MFP Range (4-28 Zone) Conventional Fire Alarm Panel
Processor Fault
Accompanied by a permanent fault beeper tone. Indicates the panel's microprocessor failed to execute its programme correctly and a safety circuit restarted it — can be caused by a sudden interruption of all power,…
View on the C-TEC MFP Range (4-28 Zone) Conventional Fire Alarm Panel page