Search fault records across 49 panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from.

Searches 608 records across 49 panels — 573 of them source-verified. Signed in, your dashboard fault search covers only the fully source-verified records, on any plan.

Want to test yourself? Try the free daily fault challenge.

30+ matches for “G-One”

Zeta Premier Elite (4 to 8 zone)

Zone fault: open circuit

Source-checked

Per the manual, an open circuit zone fault: check that the correct end-of-line diode (1N4002) has been fitted; check there are no breaks in the cable and all screw connections are secure; check no detectors have been…

View on the Zeta Premier Elite (4 to 8 zone) page

Zeta Premier Elite (4 to 8 zone)

Zone fault: short circuit (Gen S/C LED lit)

Source-checked

Per the manual, a short circuit zone fault lights the Gen S/C LED. Check that the correct end of line (1N4002 diode) has been fitted and not backwards (stripe to +ve); check that no equipment other than detectors or…

View on the Zeta Premier Elite (4 to 8 zone) page

Haes Systems Esento Excel 2-12 Zone

Zone detector removed

Source-checked

For zones 1 to 4 on the Main PCB, in fault diagnosis mode (press and hold ENTER) the Zone Fault/Disabled/Test LED going off after pressing ENTER, with a slow pulse shown in the table, means a detector has been removed…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Zone disabled or in test mode

Source-checked

A steady Zone 1 to 4 Fault/Disabled/Test LED (not pulsing) means that zone is disabled or in test mode; pressing ENTER in fault diagnosis mode does not show a fault type for it (N/A for pulsing and steady). The LED…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Zone open circuit

Source-checked

For zones 1 to 4 on the Main PCB, in fault diagnosis mode (press and hold ENTER) the Zone Fault/Disabled/Test LED steady after pressing ENTER means that zone has an open circuit.

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Zone short circuit

Source-checked

For zones 1 to 4 on the Main PCB, the Zone Fault/Disabled/Test LED pulses when there is a fault. In fault diagnosis mode (press and hold ENTER), the LED pulsing after pressing ENTER means that zone has a short circuit.

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Eclipse 2-4 Zone

Zone detector removed

Source-checked

For zones 1 to 4 on the Main PCB, in fault diagnosis mode (press and hold ENTER) the Zone Fault/Disabled/Test LED going off after pressing ENTER, with a slow pulse shown in the table, means a detector has been removed…

View on the Haes Systems Esento Eclipse 2-4 Zone page

Haes Systems Esento Eclipse 2-4 Zone

Zone disabled or in test mode

Source-checked

A steady Zone 1 to 4 Fault/Disabled/Test LED (not pulsing) means that zone is disabled or in test mode; pressing ENTER in fault diagnosis mode does not show a fault type for it. The LED going off after pressing ENTER is…

View on the Haes Systems Esento Eclipse 2-4 Zone page

Haes Systems Esento Eclipse 2-4 Zone

Zone open circuit

Source-checked

For zones 1 to 4 on the Main PCB, in fault diagnosis mode (press and hold ENTER) the Zone Fault/Disabled/Test LED steady after pressing ENTER means that zone has an open circuit.

View on the Haes Systems Esento Eclipse 2-4 Zone page

Haes Systems Esento Eclipse 2-4 Zone

Zone short circuit

Source-checked

For zones 1 to 4 on the Main PCB, the Zone Fault/Disabled/Test LED pulses when there is a fault. In fault diagnosis mode (press and hold ENTER), the LED pulsing after pressing ENTER means that zone has a short circuit.

View on the Haes Systems Esento Eclipse 2-4 Zone page

Global Fire Equipment Orion (2/4/8 Zone)

Zone/input fault

Source-checked

Individual zone and monitored input indicators are provided for both fire/alarm and fault conditions. A flashing zone/input Fault LED together with the general FAULT LED indicates a fault in that zone. The same…

View on the Global Fire Equipment Orion (2/4/8 Zone) page

C-TEC CFP (2/4/8 Zone Standard Conventional)

Zone Fault

Source-checked

All zone circuits are monitored for open- and short-circuit faults and detector head removal (unless the zone is in alarm, test or disabled). The relevant Zone Fault light pulses yellow. Access level three fault…

View on the C-TEC CFP (2/4/8 Zone Standard Conventional) page

C-TEC CFP AlarmSense (2/4/8 Zone)

Zone Fault

Source-checked

All zone circuits (up to eight) are monitored for open circuit and short circuit faults and detector head removal, unless the zone is in an alarm condition or is in test or disabled. The relevant Zone Fault light pulses…

View on the C-TEC CFP AlarmSense (2/4/8 Zone) page

C-TEC MFP Range (4-28 Zone) Conventional Fire Alarm Panel

Zone Fault

Source-checked

The number of pulses of the Zone Fault light indicates the fault type: 1 pulse = short circuit, 2 pulses = head removed, 3 pulses = open circuit. A steady (non-pulsing) light means the zone has been disabled rather than…

View on the C-TEC MFP Range (4-28 Zone) Conventional Fire Alarm Panel page

C-TEC FP Range (2-14 Zone) Conventional Fire Alarm Panel

Zone Fault

Source-checked

The Zone Fault indicator lights together with a separate internal Open Circuit Fault or Short Circuit Fault indicator lamp specific to the affected zone, depending on which condition is present. The warning beeper also…

View on the C-TEC FP Range (2-14 Zone) Conventional Fire Alarm Panel page

Morley-IAS ZXSe

Zone Fault

Source-checked

Front-panel indicator on the ZX series panel. Function per the manual: flashing means the zone contains faulty devices; steady means the zone is either disabled or in test mode (yellow zone indicator). How to clear, per…

View on the Morley-IAS ZXSe page

Fike Twinflex

ZONE fault LED

Source-checked

Yellow ZONE indicator, flashing: the manual says a fault condition is present on one of the zones or on a device connected to that zone. Continuous means a device or an action associated with a zone has been disabled.

View on the Fike Twinflex page

Nittan Evolution

Zone fault LED

Source-checked

The manual lists several reasons for the zone fault LED to light: a device has been removed from that zone; a device has been changed for one of a different type; there is a double address in the zone; or a device in…

View on the Nittan Evolution page

FireClass FC501

Telephone line

Source-checked

Telephone line fault

View on the FireClass FC501 page

Protec 6100

Zone Faults (indicators)

Source-checked

The manual says the 6100 displays any faults in the first 16 zones on the multifunction zone indicators, and all zone faults are also displayed on the LCD. The General Fault indicator is illuminated with the relevant…

View on the Protec 6100 page

Simplex 2008FS Foundation Series

IDC ZONE TROUBLE

Source-checked

The operation guide states that the affected initiating device circuit zone TROUBLE indicator flashes when an IDC zone trouble is present.

View on the Simplex 2008FS Foundation Series page

Siemens Fire Safety Cerberus PRO FC726

'Zone', 'Serial no. ("ID-Nr.")', 'Dev.location fault'

Source-checked

Displayed for each swapped C-NET device if the C-NET detector line was restarted after devices of the same type were swapped over in their bases. To clear, at least the device types in the corresponding bases must be…

View on the Siemens Fire Safety Cerberus PRO FC726 page

Siemens Fire Safety Cerberus PRO FC726

'Zone', 'Serial no. ("ID-Nr.")', 'Device missing'

Source-checked

Shown on the Person Machine Interface display for each C-NET device that has been swapped over with another non-stationary device of the same type in its base (e.g. during work on the line), leaving the 'Line' not…

View on the Siemens Fire Safety Cerberus PRO FC726 page

Siemens Fire Safety Cerberus PRO FC726

Fault of a component

Source-checked

Listed in the fault-message table on the row after System Fault (LED 5), with no LED number of its own. Action: Restart the 'Station'; when the fault is still indicated, exchange the module.

View on the Siemens Fire Safety Cerberus PRO FC726 page

Zeta Simpo

Double Address

Source-checked

More than one device with the same address in the loop.

View on the Zeta Simpo page

Haes Systems Esento Excel 2-12 Zone

System fault: main board or zone extender board

Source-checked

Per the manual, a continuous System Fault LED with the General Fault LED pulsing and a continuous buzzer means the main board, or the extender card if fitted, is halted. The fault relay is activated, and alarms may be…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esprit Apollo Addressable

Sounder Status LED pulsing

Source-checked

The Sounder Status LED pulsing indicates a fault on one or more sounder circuits. The same LED steady indicates sounder circuits have been disabled or are in test mode.

View on the Haes Systems Esprit Apollo Addressable page

Notifier by Honeywell ID3000

Battery Failure

Source-checked

These faults indicate the occurrence of one or more of: a. Faulty or disconnected batteries (if discharged batteries are connected, they may remain in Battery Low Voltage for a period until the voltage is raised by the…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Battery Low Voltage

Source-checked

These faults indicate the occurrence of one or more of: a. Faulty or disconnected batteries (if discharged batteries are connected, they may remain in Battery Low Voltage for a period until the voltage is raised by the…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Earth Fault

Source-checked

The earth fault monitor detects the presence of an earth on the positive or negative sides of the system. Should this condition occur, disconnect the field circuit wiring one cable at a time and view the LED at the top…

View on the Notifier by Honeywell ID3000 page