Notifier by Honeywell ID3000
OPTIPLEX incompatible with LIB software
An Optiplex sensor has been found on the loop but the LIB software does not support it. Action: Replace the Base PCB and LIB PCBs with revisions that have LIB software version 8.0 or above (as shown in lamp test).
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID50 / ID60
MAINTENANCE URGENT
Message shown on the ID50/ID60 panel. The manual's Appendix 3 gives the meaning as: The optical smoke chamber of a multi-criteria device has reached 100% drift compensation. Action listed in the manual: Urgent…
View on the Notifier by Honeywell ID50 / ID60 pageNotifier by Honeywell ID3000
System Fault 46 - Software error
This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…
View on the Notifier by Honeywell ID3000 pageNotifier by Honeywell ID50 / ID60
SOFTWARE CHECKSUM FAILURE
Message shown on the ID50/ID60 panel. The manual's Appendix 3 gives the meaning as: Continual internal checking of the program memory has found some corruption. Action listed in the manual: The base board should be…
View on the Notifier by Honeywell ID50 / ID60 pageGent by Honeywell Vigilon
Printer Lost
Message shown on the Vigilon panel. Meaning per the manual: the integral printer is not 'seen' by the control panel. Indications listed: Fault. Action listed in the manual: check the connections to the printer and check…
View on the Gent by Honeywell Vigilon pageNotifier by Honeywell ID50 / ID60
CONFIGURATION CHECKSUM FAILURE
Message shown on the ID50/ID60 panel. The manual's Appendix 3 gives the meaning as: Some form of corruption has been detected within the configuration settings. This can occur following a software upgrade if the memory…
View on the Notifier by Honeywell ID50 / ID60 pageNotifier by Honeywell ID3000
SENSOR FAULT
For VIEW, MULTI (Optiplex), or SMART sensors: the analogue reading is below the Chamber fault threshold, or below the Maintenance Urgent threshold, or a Maintenance Alert has existed for longer than 100 days without any…
View on the Notifier by Honeywell ID3000 pageGent by Honeywell Vigilon
Battery discharged n
Message shown on the Vigilon panel. Meaning per the manual: the battery supply to the control panel has been fully discharged. Indications listed: Fault and Power fault. Action listed in the manual: check the battery…
View on the Gent by Honeywell Vigilon pageGent by Honeywell Vigilon
Battery disconnected
Message shown on the Vigilon panel. Meaning per the manual: the battery supply to the control panel has been disconnected. Indications listed: Fault and Power fault. Action listed in the manual: reconnect the battery.
View on the Gent by Honeywell Vigilon pageGent by Honeywell Vigilon
Device Battery fault
Message shown on the Vigilon panel. Meaning per the manual: the battery supply at an interface unit, repeat panel or mimic panel has failed the load test. Indications listed: Fault. Action listed in the manual: check…
View on the Gent by Honeywell Vigilon pageGent by Honeywell Vigilon
Device Mains failed
Message shown on the Vigilon panel. Meaning per the manual: there is a mains supply failure at an interface unit, repeat or mimic panel. Indications listed: Fault. Action listed in the manual: check the fuse and mains…
View on the Gent by Honeywell Vigilon pageGent by Honeywell Vigilon
Interface input OC /SC
Message shown on the Vigilon panel. Meaning per the manual: there is an open or short circuit on the input line of an interface. Indications listed: Fault. Action listed in the manual: locate and remove the wiring…
View on the Gent by Honeywell Vigilon pageGent by Honeywell Vigilon
Lost Device
Message shown on the Vigilon panel. Meaning per the manual: the device is not communicating with the control panel via the loop. An additional Sounder indication is given if it is a sounder device. Indications listed:…
View on the Gent by Honeywell Vigilon pageGent by Honeywell Vigilon
Mains failed
Message shown on the Vigilon panel. Meaning per the manual: the mains supply to the control panel has failed. Indications listed: Fault and Power fault. Action listed in the manual: restore the mains supply to the…
View on the Gent by Honeywell Vigilon pageGent by Honeywell Vigilon
Master Alarm(s) OC or SC n
Message shown on the Vigilon panel. Meaning per the manual: there is an open or short circuit fault on the master alarm wiring. Indications listed: Fault and Sounder. Action listed in the manual: check the wiring and…
View on the Gent by Honeywell Vigilon pageGent by Honeywell Vigilon
Monitored line input OC or SC
Message shown on the Vigilon panel. Meaning per the manual: the monitored line input has an open or short circuit fault. Indications listed: Fault. Action listed in the manual: check the wiring and ensure the end of…
View on the Gent by Honeywell Vigilon pageGent by Honeywell Vigilon
Sensor out of specification
Message shown on the Vigilon panel. Meaning per the manual: the device indicated is not functioning correctly. Indications listed: Fault. Action listed in the manual: the device needs replacing.
View on the Gent by Honeywell Vigilon pageGent by Honeywell Vigilon
Wiring changed SC at card n
Message shown on the Vigilon panel. Meaning per the manual: there is a short circuit on the loop n wiring. Indications listed: Fault. Action listed in the manual: identify the device where a cable fault has occurred and…
View on the Gent by Honeywell Vigilon page