Search fault records across 49 panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from.

Searches 608 records across 49 panels — 573 of them source-verified. Signed in, your dashboard fault search covers only the fully source-verified records, on any plan.

Want to test yourself? Try the free daily fault challenge.

19 matches for “Global Fire Equipment”

Global Fire Equipment Orion (2/4/8 Zone)

Zone/input fault

Source-checked

Individual zone and monitored input indicators are provided for both fire/alarm and fault conditions. A flashing zone/input Fault LED together with the general FAULT LED indicates a fault in that zone. The same…

View on the Global Fire Equipment Orion (2/4/8 Zone) page

Global Fire Equipment Orion (2/4/8 Zone)

AUX. SUPPLY FAULT

Source-checked

This indicates the auxiliary supply has a fault.

View on the Global Fire Equipment Orion (2/4/8 Zone) page

Global Fire Equipment Orion (2/4/8 Zone)

BATTERY FAULT

Source-checked

This indicates there is a low voltage level on the batteries, or the battery charger circuit has failed.

View on the Global Fire Equipment Orion (2/4/8 Zone) page

Global Fire Equipment Orion (2/4/8 Zone)

EARTH FAULT

Source-checked

When this indicator is on, there is leakage current flowing between the earth connection/wiring and any other wire connected to the panel.

View on the Global Fire Equipment Orion (2/4/8 Zone) page

Global Fire Equipment Orion (2/4/8 Zone)

FAULT

Source-checked

This LED indicates any fault condition present on the panel. If there is a communication fault between the ORION and an ORION MINI-REP, a Sounder/Relay module or a GFE-ADLI V2 module, this LED flashes once per second.…

View on the Global Fire Equipment Orion (2/4/8 Zone) page

Global Fire Equipment Orion (2/4/8 Zone)

RM FAULT

Source-checked

If there is an RM output circuit fault, the general FAULT LED is lit and the DISABLE SELECTED ZONES LED in the Disablements section flashes.

View on the Global Fire Equipment Orion (2/4/8 Zone) page

Global Fire Equipment Orion (2/4/8 Zone)

SOUNDER FAULT

Source-checked

If there is a conventional sounder output circuit fault, the general FAULT LED is lit and the DISABLE SOUNDERS LED in the Disablements section flashes.

View on the Global Fire Equipment Orion (2/4/8 Zone) page

Global Fire Equipment Orion (2/4/8 Zone)

SUPPLY FAULT

Source-checked

This LED is on whenever the main supply has been removed or has dropped below 20 volts.

View on the Global Fire Equipment Orion (2/4/8 Zone) page

Global Fire Equipment Orion (2/4/8 Zone)

SYSTEM FAULT

Source-checked

This LED is lit whenever there is a processor failure or corruption of the panel firmware.

View on the Global Fire Equipment Orion (2/4/8 Zone) page

Global Fire Equipment G-One

Battery Fault

Source-checked

Displayed when the battery connection is broken (the manual's own test procedure is to temporarily remove the link wire between the batteries). After a short delay the SUPPLY FAULT LED comes on, the panel buzzer sounds,…

View on the Global Fire Equipment G-One page

Global Fire Equipment G-One

DEVICE NEEDS SERVICE

Source-checked

Reported via the normal fault mechanism (and logged) when programming function 6-3-5 "Check for Devices Needing Service" finds a ZEOS-protocol device close to its drift-compensation limit. No further cause or remedy…

View on the Global Fire Equipment G-One page

Global Fire Equipment G-One

NO COMMS TO PANEL

Source-checked

Shown on a remote Chameleon Display (not the main panel itself) when, after initialization, serial communication between the panel and the display has not been established. The FAULT LED on the display is also lit. The…

View on the Global Fire Equipment G-One page

Global Fire Equipment G-One

PANEL CONFIGURATION MISMATCH

Source-checked

The G-One has detected that Chameleon network panels do not hold the same system configuration or operating mode.

View on the Global Fire Equipment G-One page

Global Fire Equipment G-One

Primary Supply Fault

Source-checked

Displayed when the mains AC supply to the panel fails or is switched off. After a short delay the amber SUPPLY FAULT LED comes on and the fault buzzer sounds. Cleared when mains is restored and SYSTEM RESET is pressed.

View on the Global Fire Equipment G-One page

Global Fire Equipment OCTO+

Battery Fault

Source-checked

Displayed when the battery connection is broken (the manual's own test procedure is to temporarily remove the wire linking the batteries). After a short delay the SUPPLY FAULT LED comes on, the panel buzzer sounds, and…

View on the Global Fire Equipment OCTO+ page

Global Fire Equipment OCTO+

NO COMMS TO PANEL

Not yet verified

Shown on a remote Chameleon Display (not the main panel itself) when, after initialization, serial communication between the panel and the display has not been established. The FAULT LED on the display is also lit.…

View on the Global Fire Equipment OCTO+ page

Global Fire Equipment OCTO+

No nodes detected

Source-checked

Given in the source only as an illustrative example ("Example: 'No nodes detected'") of the network status/error text shown by programming function 8-5-3 "Installation Status", which reports the status of the network.…

View on the Global Fire Equipment OCTO+ page

Global Fire Equipment OCTO+

PANEL CONFIGURATION MISMATCH

Source-checked

The OCTO+ has detected that Chameleon network panels do not hold the same system configuration or operating mode.

View on the Global Fire Equipment OCTO+ page

Global Fire Equipment OCTO+

Primary Supply Fault

Source-checked

Displayed when the mains AC supply to the panel fails or is switched off. After a short delay the amber SUPPLY FAULT LED comes on and the fault buzzer sounds. Cleared when mains is restored and SYSTEM RESET is pressed.

View on the Global Fire Equipment OCTO+ page

Browse by manufacturer

49 panels

Got the panel in front of you? Look the fault up.

Search fault records by panel, each showing its review status and the source document where one is cited, and ask the assistant when a message is not listed. A free account needs no card and includes 5 assistant questions and 20 fault searches a day.