Haes Systems Esento Excel 2-12 Zone

Power supply fault on connecting mains before batteries

Source-checked

If the mains is connected before the batteries, the panel shows a Power Supply fault for up to 1 minute until the monitoring cycle has finished polling. The manual says this is normal, and to check connections if the…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Power supply fault: battery failure or high impedance

Source-checked

With the Power Supply Fault LED pulsing, press and hold ENTER (fault diagnosis mode): the LED steady after pressing ENTER means battery failure or high impedance. The specification table (printed page 9) gives the…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Power supply fault: mains failure

Source-checked

With the Power Supply Fault LED pulsing, press and hold ENTER (fault diagnosis mode): the LED pulsing after pressing ENTER means mains failure. The location given is the Main PCB.

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Power supply fault: voltage fault

Source-checked

With the Power Supply Fault LED pulsing, press and hold ENTER (fault diagnosis mode): the LED going off after pressing ENTER means a voltage fault. The location given is the Main PCB.

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Repeater fault: faulty repeater

Source-checked

When a repeater fault is displayed, press and hold ENTER: a slow flash of the Repeater Fault LED indicates a faulty repeater. Red fire LEDs 1 to 8 show which repeater was offline, and amber fault LEDs 1 to 8 show which…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Repeater fault: network cable error

Source-checked

When a repeater fault is displayed, press and hold ENTER: a fast flash of the Repeater Fault LED indicates a network cable error.

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Repeater fault: repeater off line

Source-checked

When a repeater fault is displayed, press and hold ENTER: a normal flash of the Repeater Fault LED indicates the repeater is off line. Red fire LEDs 1 to 8 show which repeater was off line.

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Sounder circuit open circuit

Source-checked

In fault diagnosis mode (press and hold ENTER), a Zone 1 to 6 Fire LED that is steady after pressing ENTER indicates an open circuit on the matching sounder circuit (Zone 1 and 2 = Main PCB SNDR 1 and 2; Zones 3 to 6 =…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Sounder circuit short circuit

Source-checked

When a fault is showing, press and hold ENTER (works only when the panel is not in a fire condition). The Zone 1 to 6 Fire LED that is off before you press ENTER pulses for a short circuit on that sounder circuit: Zone…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

System fault recovery

Source-checked

System Fault LED pulsing and General Fault LED pulsing along with a pulsed (fault tone) buzzer means a system fault has occurred and the affected board has recovered. The indication remains until the panel is reset.

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

System fault: display board

Source-checked

A system fault is indicated when a processor controlling a function in the panel has a watchdog time out or processor failure. With only the System Fault LED continuous and a continuous buzzer, display board TPCA03 is…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

System fault: main board or zone extender board

Source-checked

Per the manual, a continuous System Fault LED with the General Fault LED pulsing and a continuous buzzer means the main board, or the extender card if fitted, is halted. The fault relay is activated, and alarms may be…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

System fault: repeater comms board

Source-checked

A continuous System Fault LED with the General Fault LED pulsing and the Repeater Fault LED continuous means Comms Board TPCA05 is halted. The fault relay and output are active and repeater panels cease to function.…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Zone detector removed

Source-checked

For zones 1 to 4 on the Main PCB, in fault diagnosis mode (press and hold ENTER) the Zone Fault/Disabled/Test LED going off after pressing ENTER, with a slow pulse shown in the table, means a detector has been removed…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Zone disabled or in test mode

Source-checked

A steady Zone 1 to 4 Fault/Disabled/Test LED (not pulsing) means that zone is disabled or in test mode; pressing ENTER in fault diagnosis mode does not show a fault type for it (N/A for pulsing and steady). The LED…

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Zone open circuit

Source-checked

For zones 1 to 4 on the Main PCB, in fault diagnosis mode (press and hold ENTER) the Zone Fault/Disabled/Test LED steady after pressing ENTER means that zone has an open circuit.

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esento Excel 2-12 Zone

Zone short circuit

Source-checked

For zones 1 to 4 on the Main PCB, the Zone Fault/Disabled/Test LED pulses when there is a fault. In fault diagnosis mode (press and hold ENTER), the LED pulsing after pressing ENTER means that zone has a short circuit.

View on the Haes Systems Esento Excel 2-12 Zone page

Haes Systems Esprit Apollo Addressable

Battery high impedance fault (Batt Hi Z)

Source-checked

The power supply specification lists the battery high impedance fault (Batt Hi Z) as resistance above 1 ohm, with a 1-hour reporting time.

View on the Haes Systems Esprit Apollo Addressable page

Haes Systems Esprit Apollo Addressable

General Fault LED pulsing (fault condition)

Source-checked

When the panel detects a fault the display indicates the number and nature of the fault(s), the internal buzzer sounds an intermittent tone and the amber General Fault LED pulses, with any other specific Fault LEDs lit.…

View on the Haes Systems Esprit Apollo Addressable page

Haes Systems Esprit Apollo Addressable

Loop fault: short circuit or interruption

Source-checked

If a fault occurs on a transmission path (short circuit or interruption), the manual says the function of the remaining operational devices is re-established within 300 seconds of the fault, compliant with EN 54-2…

View on the Haes Systems Esprit Apollo Addressable page

Haes Systems Esprit Apollo Addressable

Power Supply Fault LED

Source-checked

The Power Supply Fault LED pulsing indicates a power supply fault on the mains power input or battery. Steady indicates the same fault with the buzzer muted.

View on the Haes Systems Esprit Apollo Addressable page

Haes Systems Esprit Apollo Addressable

Power Supply Fault on connecting mains before batteries

Source-checked

If the mains is connected before the batteries, the panel shows a Power Supply Fault for up to 1 minute until the monitoring cycle has finished polling. The manual says this is normal, and to check connections if the…

View on the Haes Systems Esprit Apollo Addressable page

Haes Systems Esprit Apollo Addressable

Sounder Status LED pulsing

Source-checked

The Sounder Status LED pulsing indicates a fault on one or more sounder circuits. The same LED steady indicates sounder circuits have been disabled or are in test mode.

View on the Haes Systems Esprit Apollo Addressable page

Haes Systems Esprit Apollo Addressable

System Fault LED

Source-checked

The System Fault LED steady indicates a system failure, that the panel is not functional, or that the internal PCB configuration has not been set up correctly. Pulsing indicates the panel has recovered from a system…

View on the Haes Systems Esprit Apollo Addressable page

Haes Systems Esprit Apollo Addressable

System fault recovery

Source-checked

System Fault LED pulsing, General Fault LED pulsing and a pulsed (fault tone) buzzer indicate a system fault has occurred and the affected board has recovered. The indication remains until the panel is reset.

View on the Haes Systems Esprit Apollo Addressable page

Haes Systems Esprit Apollo Addressable

System fault: display board (main control board)

Source-checked

A system fault is a processor watchdog time-out or processor failure. With only the System Fault LED lit and a continuous buzzer, the display board (main control board) is halted and no other indication or control is…

View on the Haes Systems Esprit Apollo Addressable page

Haes Systems Esprit Apollo Addressable

System fault: extension LED board

Source-checked

On the optional extension LED board, a continuous System Fault LED with the General Fault LED pulsing means the extension LED board is halted. The fault relay is active, and fire alarms can still be detected and…

View on the Haes Systems Esprit Apollo Addressable page

Haes Systems Esprit Apollo Addressable

System fault: power supply board

Source-checked

With the System Fault, General Fault and Power Supply Fault LEDs all pulsing, the fault relay is activated. Mains or battery power will still operate the panel, but batteries will not be charging. The indications remain…

View on the Haes Systems Esprit Apollo Addressable page

Haes Systems Esento Eclipse 2-4 Zone

Power supply fault: battery failure or high impedance

Source-checked

With the Power Supply Fault LED pulsing, press and hold ENTER (fault diagnosis mode): the LED steady after pressing ENTER means battery failure or high impedance. The location given is the Main PCB.

View on the Haes Systems Esento Eclipse 2-4 Zone page

Haes Systems Esento Eclipse 2-4 Zone

Power supply fault: mains failure

Source-checked

With the Power Supply Fault LED pulsing, press and hold ENTER (fault diagnosis mode): the LED pulsing after pressing ENTER means mains failure. The location given is the Main PCB.

View on the Haes Systems Esento Eclipse 2-4 Zone page