Fault records by panel
Search fault records across 49 panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from.
Searches 608 records across 49 panels — 573 of them source-verified. Signed in, your dashboard fault search covers only the fully source-verified records, on any plan.
Want to test yourself? Try the free daily fault challenge.
30+ partial matches for “Haes Systems manuals”
Nothing matched every word, so these match some of them. Check the record and panel before relying on it.
Haes Systems Esento Excel 2-12 Zone
Power supply fault on connecting mains before batteries
If the mains is connected before the batteries, the panel shows a Power Supply fault for up to 1 minute until the monitoring cycle has finished polling. The manual says this is normal, and to check connections if the…
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
Power supply fault: battery failure or high impedance
With the Power Supply Fault LED pulsing, press and hold ENTER (fault diagnosis mode): the LED steady after pressing ENTER means battery failure or high impedance. The specification table (printed page 9) gives the…
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
Power supply fault: mains failure
With the Power Supply Fault LED pulsing, press and hold ENTER (fault diagnosis mode): the LED pulsing after pressing ENTER means mains failure. The location given is the Main PCB.
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
Power supply fault: voltage fault
With the Power Supply Fault LED pulsing, press and hold ENTER (fault diagnosis mode): the LED going off after pressing ENTER means a voltage fault. The location given is the Main PCB.
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
Repeater fault: faulty repeater
When a repeater fault is displayed, press and hold ENTER: a slow flash of the Repeater Fault LED indicates a faulty repeater. Red fire LEDs 1 to 8 show which repeater was offline, and amber fault LEDs 1 to 8 show which…
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
Repeater fault: network cable error
When a repeater fault is displayed, press and hold ENTER: a fast flash of the Repeater Fault LED indicates a network cable error.
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
Repeater fault: repeater off line
When a repeater fault is displayed, press and hold ENTER: a normal flash of the Repeater Fault LED indicates the repeater is off line. Red fire LEDs 1 to 8 show which repeater was off line.
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
Sounder circuit open circuit
In fault diagnosis mode (press and hold ENTER), a Zone 1 to 6 Fire LED that is steady after pressing ENTER indicates an open circuit on the matching sounder circuit (Zone 1 and 2 = Main PCB SNDR 1 and 2; Zones 3 to 6 =…
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
Sounder circuit short circuit
When a fault is showing, press and hold ENTER (works only when the panel is not in a fire condition). The Zone 1 to 6 Fire LED that is off before you press ENTER pulses for a short circuit on that sounder circuit: Zone…
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
System fault recovery
System Fault LED pulsing and General Fault LED pulsing along with a pulsed (fault tone) buzzer means a system fault has occurred and the affected board has recovered. The indication remains until the panel is reset.
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
System fault: display board
A system fault is indicated when a processor controlling a function in the panel has a watchdog time out or processor failure. With only the System Fault LED continuous and a continuous buzzer, display board TPCA03 is…
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
System fault: main board or zone extender board
Per the manual, a continuous System Fault LED with the General Fault LED pulsing and a continuous buzzer means the main board, or the extender card if fitted, is halted. The fault relay is activated, and alarms may be…
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
System fault: repeater comms board
A continuous System Fault LED with the General Fault LED pulsing and the Repeater Fault LED continuous means Comms Board TPCA05 is halted. The fault relay and output are active and repeater panels cease to function.…
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
Zone detector removed
For zones 1 to 4 on the Main PCB, in fault diagnosis mode (press and hold ENTER) the Zone Fault/Disabled/Test LED going off after pressing ENTER, with a slow pulse shown in the table, means a detector has been removed…
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
Zone disabled or in test mode
A steady Zone 1 to 4 Fault/Disabled/Test LED (not pulsing) means that zone is disabled or in test mode; pressing ENTER in fault diagnosis mode does not show a fault type for it (N/A for pulsing and steady). The LED…
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
Zone open circuit
For zones 1 to 4 on the Main PCB, in fault diagnosis mode (press and hold ENTER) the Zone Fault/Disabled/Test LED steady after pressing ENTER means that zone has an open circuit.
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esento Excel 2-12 Zone
Zone short circuit
For zones 1 to 4 on the Main PCB, the Zone Fault/Disabled/Test LED pulses when there is a fault. In fault diagnosis mode (press and hold ENTER), the LED pulsing after pressing ENTER means that zone has a short circuit.
View on the Haes Systems Esento Excel 2-12 Zone pageHaes Systems Esprit Apollo Addressable
Battery high impedance fault (Batt Hi Z)
The power supply specification lists the battery high impedance fault (Batt Hi Z) as resistance above 1 ohm, with a 1-hour reporting time.
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
General Fault LED pulsing (fault condition)
When the panel detects a fault the display indicates the number and nature of the fault(s), the internal buzzer sounds an intermittent tone and the amber General Fault LED pulses, with any other specific Fault LEDs lit.…
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
Loop fault: short circuit or interruption
If a fault occurs on a transmission path (short circuit or interruption), the manual says the function of the remaining operational devices is re-established within 300 seconds of the fault, compliant with EN 54-2…
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
Power Supply Fault LED
The Power Supply Fault LED pulsing indicates a power supply fault on the mains power input or battery. Steady indicates the same fault with the buzzer muted.
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
Power Supply Fault on connecting mains before batteries
If the mains is connected before the batteries, the panel shows a Power Supply Fault for up to 1 minute until the monitoring cycle has finished polling. The manual says this is normal, and to check connections if the…
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
Sounder Status LED pulsing
The Sounder Status LED pulsing indicates a fault on one or more sounder circuits. The same LED steady indicates sounder circuits have been disabled or are in test mode.
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
System Fault LED
The System Fault LED steady indicates a system failure, that the panel is not functional, or that the internal PCB configuration has not been set up correctly. Pulsing indicates the panel has recovered from a system…
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
System fault recovery
System Fault LED pulsing, General Fault LED pulsing and a pulsed (fault tone) buzzer indicate a system fault has occurred and the affected board has recovered. The indication remains until the panel is reset.
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
System fault: display board (main control board)
A system fault is a processor watchdog time-out or processor failure. With only the System Fault LED lit and a continuous buzzer, the display board (main control board) is halted and no other indication or control is…
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
System fault: extension LED board
On the optional extension LED board, a continuous System Fault LED with the General Fault LED pulsing means the extension LED board is halted. The fault relay is active, and fire alarms can still be detected and…
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esprit Apollo Addressable
System fault: power supply board
With the System Fault, General Fault and Power Supply Fault LEDs all pulsing, the fault relay is activated. Mains or battery power will still operate the panel, but batteries will not be charging. The indications remain…
View on the Haes Systems Esprit Apollo Addressable pageHaes Systems Esento Eclipse 2-4 Zone
Power supply fault: battery failure or high impedance
With the Power Supply Fault LED pulsing, press and hold ENTER (fault diagnosis mode): the LED steady after pressing ENTER means battery failure or high impedance. The location given is the Main PCB.
View on the Haes Systems Esento Eclipse 2-4 Zone pageHaes Systems Esento Eclipse 2-4 Zone
Power supply fault: mains failure
With the Power Supply Fault LED pulsing, press and hold ENTER (fault diagnosis mode): the LED pulsing after pressing ENTER means mains failure. The location given is the Main PCB.
View on the Haes Systems Esento Eclipse 2-4 Zone page