Skip to main content
Panel fault records

Fault records by panel

Search fault records across 49 panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from.

Searches 608 records across 49 panels — 573 of them source-verified. Signed in, your dashboard fault search covers only the fully source-verified records, on any plan.

Want to test yourself? Try the free daily fault challenge.

30+ partial matches for “JUNO NET”

Nothing matched every word, so these match some of them. Check the record and panel before relying on it.

Notifier by Honeywell ID3000

ID2net: Channel 1 Link Fault

Source-checked

Most likely to occur in the event of a broken network connection, i.e. short or open circuit cable or broken optical fibre. May also indicate an NGM PCB hardware fault. There would normally be two fault messages, one at…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Channel 2 Link Fault

Source-checked

The source states this fault has the same cause and remedy as 'ID2net: Channel 1 Link Fault' — see that entry.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Network card missing

Source-checked

The ID2net Network Gateway Module (NGM) has not been detected, although it has been configured as present on the network. Action: Make sure the NGM PCB is fitted in every panel where the 'Mon' column is ticked.…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Network runtime fault

Source-checked

Displayed only if the NGM PCB stopped working after a period of working correctly. If this is not quickly followed by the Network startup fault message, the NGM PCB has successfully re-started. Action (shared with…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Network startup fault

Source-checked

Displayed if either: a. the NGM PCB fails to start initially, or b. the NGM PCB fails to start after the occurrence of a runtime fault, such as a panel/NGM PCB communication loss. Action (shared with Network runtime…

View on the Notifier by Honeywell ID3000 page

Ziton ZP2-FR

Firenet panel offline

Source-checked

If a control panel previously configured to be in the fire network is not detected, a fault message indicating the offline status (with the Firenet ID) is reported. From the ZP2 Series Installation Manual, "Firenet…

View on the Ziton ZP2-FR page

Kentec Syncro AS

unexpected network card

Source-checked

The panel has detected a newly installed network card not yet stored in its configuration.

View on the Kentec Syncro AS page

Protec 6500

Network - Break Panel X - Panel Y

Not yet verified

There is a break in the network between Panel X and Panel Y, where X and Y are the panel numbers.

View on the Protec 6500 page

Protec 6500

Network - CH1 Shutdown Fault

Not yet verified

A network fault has occurred causing the panel to ignore data from network CH1. Not available on some panel options.

View on the Protec 6500 page

Protec 6500

Network - CH2 PSU Fault

Not yet verified

There is a fault in the network card's isolated power supply; replace the card.

View on the Protec 6500 page

Protec 6500

Network - CH2 Shutdown Fault

Not yet verified

A network fault has occurred causing the panel to ignore data from network CH2. Not available on some panel options.

View on the Protec 6500 page

Protec 6500

Network - Configuration Fault

Not yet verified

The configuration data received by the network card is corrupt.

View on the Protec 6500 page

Protec 6500

Network - Duplicate Master

Not yet verified

Two master panels have been detected on the network — either two panels were assigned as master in their configuration data (correct via the PC commissioning software), or a double break in the network wiring left two…

View on the Protec 6500 page

Protec 6500

Network - Duplicate Panel(s)

Not yet verified

The network has initialised with two panels sharing the same number; correct this using the PC commissioning software. Neither panel is allowed to transmit an event, so each will eventually also display a Slave CTS…

View on the Protec 6500 page

Protec 6500

Network - Failed

Not yet verified

The network is not operational because there are too many faults.

View on the Protec 6500 page

Protec 6500

Network - I2C Link Fault

Not yet verified

The communications link between the local network card and the core network card is faulty. Not available on some panel options.

View on the Protec 6500 page

Protec 6500

Network - Missing Panel

Not yet verified

One or more panels in the master panel's network configuration data is missing.

View on the Protec 6500 page

Protec 6500

Network - Reverse Wiring Fault

Not yet verified

One or more panels has its network CH1 and CH2 wiring reversed.

View on the Protec 6500 page

Protec 6500

Network - Short A Leg To B Leg

Not yet verified

There is a short circuit fault in the network between CH1+ and CH1-. Not available on some panel options.

View on the Protec 6500 page

Protec 6500

Network - Short A Leg To Screen

Not yet verified

There is a short circuit fault in the network between CH1+ and the screen. Not available on some panel options.

View on the Protec 6500 page

Protec 6500

Network - Short B Leg To Screen

Not yet verified

There is a short circuit fault in the network between CH1- and the screen. Not available on some panel options.

View on the Protec 6500 page

Protec 6500

Network - Slave CTS Fault

Not yet verified

The panel has an event to transmit but the network master panel is not permitting it to transmit. This fault will be reported by duplicate panels.

View on the Protec 6500 page

Protec 6500

Network - Too Many Panels

Not yet verified

The network has initialised with too many panels. The network supports a maximum of 64 panels.

View on the Protec 6500 page

Protec 6500

Network - Unknown Panel(s)

Not yet verified

The network has initialised with a panel that is not in the master panel's network configuration data.

View on the Protec 6500 page

Protec 6500

Network Card Flash Checksum Fault

Not yet verified

There is a memory corruption in the network card; replace the card.

View on the Protec 6500 page

Protec 6500

Network Card Isolated

Not yet verified

The network card is not communicating with the network; check that switch 1 is off.

View on the Protec 6500 page

Protec 6500

Network Fault

Source-checked

The "Network Fault" LED on the 6500 panel's indicator strip, covering the panel-to-panel network connection used when multiple 6500 panels are networked together. This is one of the labelled LED indicators on the 6500…

View on the Protec 6500 page

Protec 6500

Network Fault - Network Master Elected

Not yet verified

The network has unexpectedly lost the master panel, so another panel has automatically been assigned as master until the problem is fixed.

View on the Protec 6500 page

C-TEC ZFP

Network Fault LED (steady yellow)

Source-checked

Per the manual, a steady yellow Network Fault indicator means a system network error has occurred. Action listed: call the service engineer.

View on the C-TEC ZFP page

Notifier by Honeywell ID3000

ID2net duplicate node n

Source-checked

Two nodes have the same node id. Action: Change the id number of one of the duplicate nodes (use the diagnostic tool).

View on the Notifier by Honeywell ID3000 page

Browse by manufacturer

49 panels

Got the panel in front of you? Look the fault up.

Search fault records by panel, each showing its review status and the source document where one is cited, and ask the assistant when a message is not listed. A free account needs no card and includes 5 assistant questions and 20 fault searches a day.