Search fault records across 49 panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from.

Searches 608 records across 49 panels — 573 of them source-verified. Signed in, your dashboard fault search covers only the fully source-verified records, on any plan.

Want to test yourself? Try the free daily fault challenge.

30+ partial matches for “JUNO NET fault finding”

Nothing matched every word, so these match some of them. Check the record and panel before relying on it.

Notifier by Honeywell ID3000

ID2net: Channel 1 Link Fault

Source-checked

Most likely to occur in the event of a broken network connection, i.e. short or open circuit cable or broken optical fibre. May also indicate an NGM PCB hardware fault. There would normally be two fault messages, one at…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Channel 2 Link Fault

Source-checked

The source states this fault has the same cause and remedy as 'ID2net: Channel 1 Link Fault' — see that entry.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Network runtime fault

Source-checked

Displayed only if the NGM PCB stopped working after a period of working correctly. If this is not quickly followed by the Network startup fault message, the NGM PCB has successfully re-started. Action (shared with…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Network startup fault

Source-checked

Displayed if either: a. the NGM PCB fails to start initially, or b. the NGM PCB fails to start after the occurrence of a runtime fault, such as a panel/NGM PCB communication loss. Action (shared with Network runtime…

View on the Notifier by Honeywell ID3000 page

Protec 6500

Network - CH1 Shutdown Fault

Not yet verified

A network fault has occurred causing the panel to ignore data from network CH1. Not available on some panel options.

View on the Protec 6500 page

Protec 6500

Network - CH2 PSU Fault

Not yet verified

There is a fault in the network card's isolated power supply; replace the card.

View on the Protec 6500 page

Protec 6500

Network - CH2 Shutdown Fault

Not yet verified

A network fault has occurred causing the panel to ignore data from network CH2. Not available on some panel options.

View on the Protec 6500 page

Protec 6500

Network - I2C Link Fault

Not yet verified

The communications link between the local network card and the core network card is faulty. Not available on some panel options.

View on the Protec 6500 page

Protec 6500

Network - Slave CTS Fault

Not yet verified

The panel has an event to transmit but the network master panel is not permitting it to transmit. This fault will be reported by duplicate panels.

View on the Protec 6500 page

Protec 6500

Network Fault

Source-checked

The "Network Fault" LED on the 6500 panel's indicator strip, covering the panel-to-panel network connection used when multiple 6500 panels are networked together. This is one of the labelled LED indicators on the 6500…

View on the Protec 6500 page

C-TEC ZFP

Network Fault LED (steady yellow)

Source-checked

Per the manual, a steady yellow Network Fault indicator means a system network error has occurred. Action listed: call the service engineer.

View on the C-TEC ZFP page

Notifier by Honeywell ID3000

Power Fault, ID2net Booster n

Source-checked

This message indicates an open circuit on the power fault input of the NGM. Action: Check for missing or broken wiring. Check that the PSU is not faulty.

View on the Notifier by Honeywell ID3000 page

Protec 6500

Network - Configuration Fault

Not yet verified

The configuration data received by the network card is corrupt.

View on the Protec 6500 page

Protec 6500

Network - Reverse Wiring Fault

Not yet verified

One or more panels has its network CH1 and CH2 wiring reversed.

View on the Protec 6500 page

Protec 6500

Network Card Flash Checksum Fault

Not yet verified

There is a memory corruption in the network card; replace the card.

View on the Protec 6500 page

Protec 6500

Network Fault - Network Master Elected

Not yet verified

The network has unexpectedly lost the master panel, so another panel has automatically been assigned as master until the problem is fixed.

View on the Protec 6500 page

Siemens Fire Safety Cerberus PRO FC726

Communication fault of a networked 'Station'

Source-checked

Action: Check the transmission line; check the faulty 'Station'.

View on the Siemens Fire Safety Cerberus PRO FC726 page

Protec 6500

Network - Map Fault

Not yet verified

The physical order of the panels does not match the order downloaded to the master panel.

View on the Protec 6500 page

Protec 6500

Network Comms Fault

Not yet verified

See loop-comms diagnostic section of the manual for details.

View on the Protec 6500 page

Ziton ZP2-FR

Firenet panel offline

Source-checked

If a control panel previously configured to be in the fire network is not detected, a fault message indicating the offline status (with the Firenet ID) is reported. From the ZP2 Series Installation Manual, "Firenet…

View on the Ziton ZP2-FR page

Zeta Simpo

Panel Fault

Source-checked

Fault in the connection with another panel, when two or more panels are connected in a network.

View on the Zeta Simpo page

Fike Safety Technology Quadnet

Earth Fault

Source-checked

Per the manual, if the panel detects a short circuit to earth/screen from one of its supply rails (0 V or +ve) an Earth Fault is displayed. Remove the circuit cables one at a time and reset the system: when the faulty…

View on the Fike Safety Technology Quadnet page

Fike Safety Technology Quadnet

EARTH FAULT LED

Source-checked

Yellow EARTH FAULT indicator, flashing: the manual says an earth fault has been detected where a path exists from the circuit wiring to earth; remove circuits one at a time to discover which one, and then rectify. An…

View on the Fike Safety Technology Quadnet page

Fike Safety Technology Quadnet

FIRE OUTPUT fault LED

Source-checked

Yellow FIRE OUTPUT indicator, flashing: the manual says a fault condition is present on a monitored relay circuit or on the addressable device loop outputs. Continuous means a device or action associated with the…

View on the Fike Safety Technology Quadnet page

Fike Safety Technology Quadnet

LOOP fault LED

Source-checked

Yellow LOOP indicator, flashing: the manual says a fault condition is present on one or more addressable device loops, or one or more addressable devices. Continuous means a device or an action associated with the…

View on the Fike Safety Technology Quadnet page

Fike Safety Technology Quadnet

POWER FAULT LED (continuous: battery or charger)

Source-checked

Yellow POWER FAULT indicator, continuous: the manual says a battery supply or charger fault has been detected, and to check the fuse and the battery voltages.

View on the Fike Safety Technology Quadnet page

Fike Safety Technology Quadnet

POWER FAULT LED (flashing: mains)

Source-checked

Yellow POWER FAULT indicator, flashing: the manual says the mains supply has failed, and to check the fuse and the 230 V AC supply on the PCB AC terminals.

View on the Fike Safety Technology Quadnet page

Fike Safety Technology Quadnet

SOUNDER fault LED

Source-checked

Yellow SOUNDER indicator, flashing: the manual says a fault condition is present on a monitored sounder circuit or on the addressable device loop sounders. Continuous means a device or action associated with the…

View on the Fike Safety Technology Quadnet page

Fike Safety Technology Quadnet

SYSTEM FAULT LED

Source-checked

Yellow SYSTEM FAULT indicator, flashing: the manual says it indicates the presence of a processor or a checksum error. Power the system down to clear, reprogram all settings and test the system.

View on the Fike Safety Technology Quadnet page

Haes Systems Esento Excel 2-12 Zone

Repeater fault: network cable error

Source-checked

When a repeater fault is displayed, press and hold ENTER: a fast flash of the Repeater Fault LED indicates a network cable error.

View on the Haes Systems Esento Excel 2-12 Zone page