9 matches for “Kentec Electronics”

Kentec Syncro AS

ZONE FAULT

Legacy record reviewed

A conventional zone circuit has reported an open or short circuit fault. Kentec Syncro AS monitors zone wiring with end-of-line resistors (EOLR).

View on the Kentec Syncro AS page

Kentec Syncro AS

Aux. 24V fuse failed

verified

The panel has detected operation of the monitored self-resetting 500 mA auxiliary 24 V output protection.

View on the Kentec Syncro AS page

Kentec Syncro AS

BAD DATA

verified

The panel has received invalid loop data from one device on four consecutive polls.

View on the Kentec Syncro AS page

Kentec Syncro AS

BATTERY DISCONNECTED

verified

The panel power-supply monitoring cannot detect the connected standby battery set.

View on the Kentec Syncro AS page

Kentec Syncro AS

BATTERY LOW VOLTAGE

verified

The monitored standby battery voltage has fallen to the panel low-voltage threshold.

View on the Kentec Syncro AS page

Kentec Syncro AS

Earth fault

verified

The panel has detected leakage to earth; the manual specifies indication below 30 kOhm from +28 V or 0 V to earth.

View on the Kentec Syncro AS page

Kentec Syncro AS

MAINS FAILED

verified

The panel power-supply monitoring has detected loss of the mains supply.

View on the Kentec Syncro AS page

Kentec Syncro AS

SOUNDER FAULT

Legacy record reviewed

A monitored sounder or bell circuit has reported an open or short circuit. The circuit is monitored at rest to ensure sounders will function when called on.

View on the Kentec Syncro AS page

Kentec Syncro AS

unexpected network card

verified

The panel has detected a newly installed network card not yet stored in its configuration.

View on the Kentec Syncro AS page