Kentec Syncro AS
Aux. 24V fuse failed
The panel has detected operation of the monitored self-resetting 500 mA auxiliary 24 V output protection.
View on the Kentec Syncro AS pageKentec Syncro AS
BAD DATA
The panel has received invalid loop data from one device on four consecutive polls.
View on the Kentec Syncro AS pageKentec Syncro AS
BATTERY DISCONNECTED
The panel power-supply monitoring cannot detect the connected standby battery set.
View on the Kentec Syncro AS pageKentec Syncro AS
BATTERY LOW VOLTAGE
The monitored standby battery voltage has fallen to the panel low-voltage threshold.
View on the Kentec Syncro AS pageKentec Syncro AS
Double address (fault announced at loop initialisation)
Per the manual, the control panel can detect devices that have been set to the same address and will announce a “Double address” fault if it finds any. It cannot tell which devices are double addressed. To help find…
View on the Kentec Syncro AS pageKentec Syncro AS
Earth fault
The panel has detected leakage to earth; the manual specifies indication below 30 kOhm from +28 V or 0 V to earth.
View on the Kentec Syncro AS pageKentec Syncro AS
MAINS FAILED
The panel power-supply monitoring has detected loss of the mains supply.
View on the Kentec Syncro AS pageKentec Syncro AS
SOUNDER FAULT
The sounder fault/disabled indicator lights when any output treated as a sounder is faulty or disabled. Syncro AS treats an output as a sounder when its Silenceable and Evacuate Output attributes are selected. The same…
View on the Kentec Syncro AS pageKentec Syncro AS
unexpected network card
The panel has detected a newly installed network card not yet stored in its configuration.
View on the Kentec Syncro AS page