Fault records by panel
Search fault records across 49 panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from.
Searches 608 records across 49 panels — 573 of them source-verified. Signed in, your dashboard fault search covers only the fully source-verified records, on any plan.
Want to test yourself? Try the free daily fault challenge.
26 partial matches for “Nittan Europe”
Nothing matched every word, so these match some of them. Check the record and panel before relying on it.
Nittan Evolution
Break in -ve wire (ISOLATOR FAULT)
Reported as an ISOLATOR FAULT with a description. The manual says to use the same method to locate the break (re-run the loop search and check the detailed loop report). In its example, the break is between address 150,…
View on the Nittan Evolution pageNittan Evolution
Break in +ve wire (ISOLATOR FAULT)
The manual says the panel's loop isolator monitors the addressable loop for open and short circuit faults, reported as ISOLATOR FAULTS with a description. For a break in the positive wire, it says to locate the cable…
View on the Nittan Evolution pageNittan Evolution
Cable break (loop contents different from expected)
If the loop contents differ from what was expected, the manual lists a cable break as a probable cause. If a system is only wired as a loop, any breaks will be reported and can be located as in section 12.1. If a system…
View on the Nittan Evolution pageNittan Evolution
Reverse polarity devices (missing from the loop)
The manual says some devices are polarity sensitive and will not be seen if the + and - connections are reversed. Look for missing devices in the loop report and check their connections.
View on the Nittan Evolution pageNittan Evolution
Short circuit in the middle of the loop
The manual says a short circuit in the middle of the loop will usually cause two loop short circuit isolators to activate, and the devices between the isolators go missing because they are no longer powered. The short…
View on the Nittan Evolution pageNittan Evolution
Short circuit on side A of the loop (ISOLATOR FAULT)
If the panel reports a loop short on side A, the manual says there is a short circuit fault on the loop somewhere between the panel (side A) and the first device with a short circuit isolator on the loop.
View on the Nittan Evolution pageNittan Evolution
Short circuit on side B of the loop (ISOLATOR FAULT)
If the panel reports a loop short on side B, the manual says there is a short circuit fault on the loop somewhere between the panel (side B) and the last device with a short circuit isolator on the loop.
View on the Nittan Evolution pageNittan Evolution
Zone fault LED
The manual lists several reasons for the zone fault LED to light: a device has been removed from that zone; a device has been changed for one of a different type; there is a double address in the zone; or a device in…
View on the Nittan Evolution pageHochiki HFP AP-1AS/2AS
General Fault
The yellow General Fault LED flashes when there is a fault on the system. Other fault LED indications may also be present to identify the nature of the fault. The Fault Contact energises and the panel buzzer sounds…
View on the Hochiki HFP AP-1AS/2AS pageHochiki HFP AP-1AS/2AS
Sounder Fault / Disabled
Combined fault/disablement LED for sounder outputs. Illuminates if a sounder output fault is present, and also illuminates (with the General Disablement indicator) when sounder outputs are deliberately disabled via the…
View on the Hochiki HFP AP-1AS/2AS pageNittan Evolution
Battery high impedance fault
The panel has measured the battery internal resistance and determined it is too high. The batteries will need to be replaced.
View on the Nittan Evolution pageNittan Evolution
Battery Removed
Check the battery fuse, check that battery connections are secure, check battery voltage (should be around 26-27V for well-charged batteries), check that the two batteries are connected in series, and check the charger…
View on the Nittan Evolution pageNittan Evolution
Charger Fault
The panel has determined that the power supply is not charging the batteries. This is likely to be a problem with the Charger PCB — contact the supplier to arrange a replacement.
View on the Nittan Evolution pageNittan Evolution
DOUBLE ADDRESS FAULT
Two or more devices may have the same address setting. All devices with the same address will answer at the same time and the panel will not be able to understand the reply it receives. Search the detailed loop report…
View on the Nittan Evolution pageNittan Evolution
Earth Negative Fault
Something is shorting to earth on the negative side. Located using the same method as an Earth Positive Fault, but looking for shorts to loop negative rather than positive.
View on the Nittan Evolution pageNittan Evolution
Earth Positive Fault
Something is shorting to earth on the positive side (usually through a cable screen). Most earth faults occur on the addressable loop — disconnect all loop connections and reset the panel; if no earth fault is reported…
View on the Nittan Evolution pageNittan Evolution
LOCAL INPUT OPEN
Check the local input has an end-of-line resistor fitted, check it is the correct value (4.7 kΩ), and check for cable breaks or loose connections.
View on the Nittan Evolution pageNittan Evolution
LOCAL INPUT SHORTED
Check for cable short circuits on the circuit, check the end-of-line resistor is the correct value (4.7 kΩ), and check there are no normally-closed switches connected to the circuit.
View on the Nittan Evolution pageNittan Evolution
LOCAL OUTPUT OPEN
Check the local output (sounder circuit) has an end-of-line resistor fitted, check it is the correct value (4.7 kΩ), and check for cable breaks or loose connections.
View on the Nittan Evolution pageNittan Evolution
LOCAL OUTPUT SHORTED
Check that there are no cable short circuits on the circuit, and check that there are no non-polarised devices connected to the circuit. (The manual lists these two checks for this message.)
View on the Nittan Evolution pageNittan Evolution
Mains Supply Fault
Check if mains power is present, and check for 29.5V DC at the PSU cage output.
View on the Nittan Evolution pageNittan Evolution
System Fault
A system fault is an abnormal microprocessor running condition caused by various unexpected phenomena. The panel attempts to correct itself; while the fault is present the System Fault LED, General Fault LED, General…
View on the Nittan Evolution pageHochiki HFP AP-1AS/2AS
Double address (fault announced at loop initialisation)
Per the manual, the control panel can detect devices set to the same address and will announce a “Double address” fault if it finds any. It cannot tell which devices are double addressed. To help find them, go to access…
View on the Hochiki HFP AP-1AS/2AS pageHochiki HFP AP-1AS/2AS
Fault events are non-latching (Reset does not clear them)
Per the user manual, the Reset button is used to reset any activation defined as a latching input type, which includes fire and pre-alarm events. In general, fault events are non-latching and cannot be cleared by…
View on the Hochiki HFP AP-1AS/2AS pageHochiki HFP AP-1AS/2AS
Loop open circuit or short circuit (how the panel responds)
Per the manual, power is driven from the LOOP OUT terminals and returned to the LOOP IN terminals, where it is monitored for loop continuity. If the loop is open circuit (a cable fault, or a short circuit isolator…
View on the Hochiki HFP AP-1AS/2AS pageHochiki HFP AP-1AS/2AS
System fault message after a PC configuration download
Per the manual, after a configuration is sent back to the panel from the PC (write enable on, then synchronise), the panel shows RECEIVING NEW CONFIGURATION, PLEASE WAIT during the transfer and then the start-up…
View on the Hochiki HFP AP-1AS/2AS page