Panel fault records

Fault records by panel

Fault records for a small, deliberately staged set of panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from. More panels are added as more records go through source review.

Searches 148 records across 6 panels.

30+ partial matches for “Notifier by Honeywell manuals”

Nothing matched every word, so these match some of them. Check the record and panel before relying on it.

Notifier by Honeywell ID3000

Battery Failure

Not yet verified

These faults indicate the occurrence of one or more of: a. Faulty or disconnected batteries (if discharged batteries are connected, they may remain in Battery Low Voltage for a period until the voltage is raised by the…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Battery Low Voltage

Not yet verified

These faults indicate the occurrence of one or more of: a. Faulty or disconnected batteries (if discharged batteries are connected, they may remain in Battery Low Voltage for a period until the voltage is raised by the…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Network runtime fault

Not yet verified

Displayed only if the NGM PCB stopped working after a period of working correctly. If this is not quickly followed by the Network startup fault message, the NGM PCB has successfully re-started. Action (shared with…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

PSU/Charger Fault

Not yet verified

These faults indicate the occurrence of one or more of: a. Faulty or disconnected batteries (if discharged batteries are connected, they may remain in Battery Low Voltage for a period until the voltage is raised by the…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Aux. Output X Fault

Not yet verified

Parameterised message covering auxiliary outputs 1 and 2 (X = 1 or 2), as printed in the source ('Aux. Output 1 Fault'; 'Aux. Output 2 Fault'). Indicates a failure of the auxiliary drive circuits, not the attached…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Dev#0 Present

Not yet verified

This indicates that a device has been installed without setting a valid address, i.e. left at factory default of '00'. No separate remedial action is stated beyond this cause in the source.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Driver Fault

Not yet verified

These four fault messages are grouped in the source as all indicating a loop PCB failure. Action: Replace the loop PCB (PN: 020-588).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Earth Fault

Not yet verified

The earth fault monitor detects the presence of an earth on the positive or negative sides of the system. Should this condition occur, disconnect the field circuit wiring one cable at a time and view the LED at the top…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 47 - CPU/Display hardware fault

Not yet verified

Communications fault between the CPU and the display. Action: Change the CPU PCB assembly (PN: 020-569) and/or the Display PCB/Membrane Keypad (PN: 020-571-XXX).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 48 - Base PCB/Expansion h/w fault

Not yet verified

No separate cause description is given for this message beyond its name. Action: Change the Base PCB (PN: 020-568) or Extension Chassis with Display Module Kit (PN: 020-559-XXX).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 71 - Config. needs Expansion Card

Not yet verified

This fault message can only appear when ID3000 panels are networked with earlier compatible panels; it is not applicable to the 'local' ID3000 Series panel. Where it is applicable, an Extension Chassis with Display…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 72 - Config. needs RS485 Card

Not yet verified

Missing PCB — the panel is configured for network but no RS485 PCB is present. Fit Isolated RS485 Module Kit (PN: 020-479) or change configuration.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 73 - Config. needs RS232 Card

Not yet verified

Missing PCB — the panel is configured for 3rd-party protocol but no RS232 PCB is present (does not apply to other modes of the port). Fit Isolated RS232 Module Kit (PN: 020-478) or change configuration.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Fault 74 - RS232\RS485\PRINTER Card displaced

Not yet verified

An attempt has been made to remove one of these items while the panel is powered up. Remove power before proceeding.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net duplicate node n

Not yet verified

Two nodes have the same node id. Action: Change the id number of one of the duplicate nodes (use the diagnostic tool).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Channel 1 Link Fault

Not yet verified

Most likely to occur in the event of a broken network connection, i.e. short or open circuit cable or broken optical fibre. May also indicate an NGM PCB hardware fault. There would normally be two fault messages, one at…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Channel 2 Link Fault

Not yet verified

The source states this fault has the same cause and remedy as 'ID2net: Channel 1 Link Fault' — see that entry.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Flash Checksum Error

Not yet verified

This message indicates an NGM PCB failure. Action: Replace the NGM PCB. Note: the source states other fault conditions may occur in exceptional circumstances, in which case contact your supplier for guidance.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Network card missing

Not yet verified

The ID2net Network Gateway Module (NGM) has not been detected, although it has been configured as present on the network. Action: Make sure the NGM PCB is fitted in every panel where the 'Mon' column is ticked.…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

ID2net: Network startup fault

Not yet verified

Displayed if either: a. the NGM PCB fails to start initially, or b. the NGM PCB fails to start after the occurrence of a runtime fault, such as a panel/NGM PCB communication loss. Action (shared with Network runtime…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Incompatible or faulty sensor installed

Not yet verified

No separate cause description is given beyond the message name. Action: For IPX sensors, replace with SDX751TEM or equivalent. For other MULTI and SMART sensors, replace (sensor is faulty).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Mains/PSU Failure

Not yet verified

This indicates that the incoming supply has failed. Check for the following: a. Faulty PSU; b. Failed 230VAC mains supply.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

OPTIPLEX incompatible with LIB software

Not yet verified

An Optiplex sensor has been found on the loop but the LIB software does not support it. Action: Replace the Base PCB and LIB PCBs with revisions that have LIB software version 8.0 or above (as shown in lamp test).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Panel Fault 17 - Card Missing

Not yet verified

Loop PCB missing or failed to respond. Possible causes are: a. Wrong ribbon cable connected; b. Ribbon cable disconnected; c. Loop PCB failure. Action: For the last case, change the loop PCB (PN: 020-588).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Panel Fault 49 - CPU Watchdog timer fault

Not yet verified

This message is one of ten Processor Fault messages the source groups together under a single shared action: if any of these faults occur repeatedly and randomly, replace the CPU PCB assembly (PN: 020-569). No separate…

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Panel Fault 5 - Power Restart

Not yet verified

These four fault messages are grouped in the source as all indicating a loop PCB failure. Action: Replace the loop PCB (PN: 020-588).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Panel Fault 65 - Clock set to after AD2099

Not yet verified

No separate cause description is given beyond the message name. Action: Set the clock to the correct date and time.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Panel Key Stuck

Not yet verified

No separate cause description is given for this message beyond its name. Action: Change the Display PCB/Membrane Keypad (PN: 020-571-XXX).

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Power Fault, ID2net Booster n

Not yet verified

This message indicates an open circuit on the power fault input of the NGM. Action: Check for missing or broken wiring. Check that the PSU is not faulty.

View on the Notifier by Honeywell ID3000 page

Notifier by Honeywell ID3000

Printer Fault

Not yet verified

Internal printer only. This fault may be an indication of a paper jam or malfunction, no paper, or the printer may be disconnected. Note: the printer operation is only monitored if the printer was functional at the last…

View on the Notifier by Honeywell ID3000 page