5 matches for “OCTO+”
Global Fire Equipment OCTO+
PANEL CONFIGURATION MISMATCH
The OCTO+ has detected that Chameleon network panels do not hold the same system configuration or operating mode.
View on the Global Fire Equipment OCTO+ pageGlobal Fire Equipment OCTO+
Battery Fault
Displayed when the battery connection is broken (the manual's own test procedure is to temporarily remove the wire linking the batteries). After a short delay the SUPPLY FAULT LED comes on, the panel buzzer sounds, and…
View on the Global Fire Equipment OCTO+ pageGlobal Fire Equipment OCTO+
NO COMMS TO PANEL
Shown on a remote Chameleon Display (not the main panel itself) when, after initialization, serial communication between the panel and the display has not been established. The FAULT LED on the display is also lit.…
View on the Global Fire Equipment OCTO+ pageGlobal Fire Equipment OCTO+
No nodes detected
Given in the source only as an illustrative example ("Example: 'No nodes detected'") of the network status/error text shown by programming function 8-5-3 "Installation Status", which reports the status of the network.…
View on the Global Fire Equipment OCTO+ pageGlobal Fire Equipment OCTO+
Primary Supply Fault
Displayed when the mains AC supply to the panel fails or is switched off. After a short delay the amber SUPPLY FAULT LED comes on and the fault buzzer sounds. Cleared when mains is restored and SYSTEM RESET is pressed.
View on the Global Fire Equipment OCTO+ page