Skip to main content
Panel fault records

Fault records by panel

Search fault records across 49 panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from.

Searches 608 records across 49 panels — 573 of them source-verified. Signed in, your dashboard fault search covers only the fully source-verified records, on any plan.

Want to test yourself? Try the free daily fault challenge.

8 partial matches for “Premier Elite 168 fault finding”

Nothing matched every word, so these match some of them. Check the record and panel before relying on it.

Zeta Premier Elite (4 to 8 zone)

Faults are non-latching (system fault excepted)

Source-checked

The manual says most faults need checking by an engineer, but the system can be checked for a removed detector by the responsible person. All faults in the Premier Elite are non-latching: they cannot be reset with the…

View on the Zeta Premier Elite (4 to 8 zone) page

Zeta Premier Elite (4 to 8 zone)

Earth fault

Source-checked

Per the manual, an earth fault indicates that something is shorting to earth, usually through the cable screen. Disconnect the earth screens one at a time to determine the problem line. Connecting other equipment, for…

View on the Zeta Premier Elite (4 to 8 zone) page

Zeta Premier Elite (4 to 8 zone)

Sounder circuit fault: open circuit

Source-checked

Per the manual, for a sounder open circuit fault: check that the correct end-of-line resistor (10K) has been fitted to both circuits; check sounder fuses FS4 and FS5 are intact; check there are no breaks in the cable…

View on the Zeta Premier Elite (4 to 8 zone) page

Zeta Premier Elite (4 to 8 zone)

Sounder circuit fault: short circuit (Gen S/C LED lit)

Source-checked

Per the manual, a sounder short circuit fault lights the Gen S/C LED. Check the correct end of line (10K resistor) has been fitted to both circuits; check that all sounders and bells are polarised and fitted the correct…

View on the Zeta Premier Elite (4 to 8 zone) page

Zeta Premier Elite (4 to 8 zone)

Supply fault

Source-checked

Per the manual, a power supply fault indicates loss of mains power or loss of battery power. For loss of mains: check that 230 V AC is present at the mains terminal block, check the mains fuse, check that there is 30 to…

View on the Zeta Premier Elite (4 to 8 zone) page

Zeta Premier Elite (4 to 8 zone)

System fault

Source-checked

Per the manual, a system fault is an abnormal microprocessor running condition due to various unexpected phenomena, and the panel attempts to correct itself. The System Fault LED, General Fault LED, General Fault relay…

View on the Zeta Premier Elite (4 to 8 zone) page

Zeta Premier Elite (4 to 8 zone)

Zone fault: open circuit

Source-checked

Per the manual, an open circuit zone fault: check that the correct end-of-line diode (1N4002) has been fitted; check there are no breaks in the cable and all screw connections are secure; check no detectors have been…

View on the Zeta Premier Elite (4 to 8 zone) page

Zeta Premier Elite (4 to 8 zone)

Zone fault: short circuit (Gen S/C LED lit)

Source-checked

Per the manual, a short circuit zone fault lights the Gen S/C LED. Check that the correct end of line (1N4002 diode) has been fitted and not backwards (stripe to +ve); check that no equipment other than detectors or…

View on the Zeta Premier Elite (4 to 8 zone) page

Browse by manufacturer

49 panels

Got the panel in front of you? Look the fault up.

Search fault records by panel, each showing its review status and the source document where one is cited, and ask the assistant when a message is not listed. A free account needs no card and includes 5 assistant questions and 20 fault searches a day.