Zeta Premier Elite (4 to 8 zone)
Faults are non-latching (system fault excepted)
The manual says most faults need checking by an engineer, but the system can be checked for a removed detector by the responsible person. All faults in the Premier Elite are non-latching: they cannot be reset with the…
View on the Zeta Premier Elite (4 to 8 zone) pageZeta Premier Elite (4 to 8 zone)
Supply fault
Per the manual, a power supply fault indicates loss of mains power or loss of battery power. For loss of mains: check that 230 V AC is present at the mains terminal block, check the mains fuse, check that there is 30 to…
View on the Zeta Premier Elite (4 to 8 zone) pageZeta Premier Elite (4 to 8 zone)
Earth fault
Per the manual, an earth fault indicates that something is shorting to earth, usually through the cable screen. Disconnect the earth screens one at a time to determine the problem line. Connecting other equipment, for…
View on the Zeta Premier Elite (4 to 8 zone) pageZeta Premier Elite (4 to 8 zone)
Sounder circuit fault: open circuit
Per the manual, for a sounder open circuit fault: check that the correct end-of-line resistor (10K) has been fitted to both circuits; check sounder fuses FS4 and FS5 are intact; check there are no breaks in the cable…
View on the Zeta Premier Elite (4 to 8 zone) pageZeta Premier Elite (4 to 8 zone)
Sounder circuit fault: short circuit (Gen S/C LED lit)
Per the manual, a sounder short circuit fault lights the Gen S/C LED. Check the correct end of line (10K resistor) has been fitted to both circuits; check that all sounders and bells are polarised and fitted the correct…
View on the Zeta Premier Elite (4 to 8 zone) pageZeta Premier Elite (4 to 8 zone)
System fault
Per the manual, a system fault is an abnormal microprocessor running condition due to various unexpected phenomena, and the panel attempts to correct itself. The System Fault LED, General Fault LED, General Fault relay…
View on the Zeta Premier Elite (4 to 8 zone) pageZeta Premier Elite (4 to 8 zone)
Zone fault: open circuit
Per the manual, an open circuit zone fault: check that the correct end-of-line diode (1N4002) has been fitted; check there are no breaks in the cable and all screw connections are secure; check no detectors have been…
View on the Zeta Premier Elite (4 to 8 zone) pageZeta Premier Elite (4 to 8 zone)
Zone fault: short circuit (Gen S/C LED lit)
Per the manual, a short circuit zone fault lights the Gen S/C LED. Check that the correct end of line (1N4002 diode) has been fitted and not backwards (stripe to +ve); check that no equipment other than detectors or…
View on the Zeta Premier Elite (4 to 8 zone) page