Protec 6500
Loop Drive Series Fault
There is a high resistance in the loop wiring. The fault threshold is 80Ω (Issue E) or 50Ω (Issue F), though the manual adds that "any value greater than 32 is considered high" (no unit given). The loop current…
View on the Protec 6500 pageProtec 6500
Network - Duplicate Master
Two master panels have been detected on the network — either two panels were assigned as master in their configuration data (correct via the PC commissioning software), or a double break in the network wiring left two…
View on the Protec 6500 pageProtec 6500
Network - Duplicate Panel(s)
The network has initialised with two panels sharing the same number; correct this using the PC commissioning software. Neither panel is allowed to transmit an event, so each will eventually also display a Slave CTS…
View on the Protec 6500 pageProtec 6100
System Faults
The manual says the 6100 performs regular self tests to ensure the software is working correctly. If a fault is detected in software operation a System Fault is declared. It is a latching fault and can only be cleared…
View on the Protec 6100 page