Fault codes by panel
Search fault records across 49 panels. Each record is labelled with its review status and, where one is cited, the source document and page it comes from.
Searches 608 records across 49 panels — 573 of them source-verified. Signed in, your dashboard fault search covers only the fully source-verified records, on any plan.
Want to test yourself? Try the free daily fault challenge.
13 matches for “Siemens”
Siemens Fire Safety Cerberus PRO FC726
'Zone', 'Serial no. ("ID-Nr.")', 'Dev.location fault'
Displayed for each swapped C-NET device if the C-NET detector line was restarted after devices of the same type were swapped over in their bases. To clear, at least the device types in the corresponding bases must be…
View on the Siemens Fire Safety Cerberus PRO FC726 pageSiemens Fire Safety Cerberus PRO FC726
'Zone', 'Serial no. ("ID-Nr.")', 'Device missing'
Shown on the Person Machine Interface display for each C-NET device that has been swapped over with another non-stationary device of the same type in its base (e.g. during work on the line), leaving the 'Line' not…
View on the Siemens Fire Safety Cerberus PRO FC726 pageSiemens Fire Safety Cerberus PRO FC726
Alarm device Fault / Off (LED 10)
'Acoustic control line' fault. Action: Check the line for open line/short-circuit, or a missing/defective end-of-line element (EOL).
View on the Siemens Fire Safety Cerberus PRO FC726 pageSiemens Fire Safety Cerberus PRO FC726
Communication fault of a networked 'Station'
Action: Check the transmission line; check the faulty 'Station'.
View on the Siemens Fire Safety Cerberus PRO FC726 pageSiemens Fire Safety Cerberus PRO FC726
Control function Fault / Off (LED 12)
'Fire control line' fault. Action: Check the line for open line/short-circuit; check the function of the external control devices; check the function of any existing feedback switch.
View on the Siemens Fire Safety Cerberus PRO FC726 pageSiemens Fire Safety Cerberus PRO FC726
Control panel communication fault
An FC726S or FC726S-10 cannot communicate correctly with other control panels on the documented FC-NET/SASF-NET system.
View on the Siemens Fire Safety Cerberus PRO FC726 pageSiemens Fire Safety Cerberus PRO FC726
FAULT (LED 1)
The 'Site' has a fault. Action: Check whether another fault LED is flashing; if not, check the display, and check whether the 'Fault' control input is activated.
View on the Siemens Fire Safety Cerberus PRO FC726 pageSiemens Fire Safety Cerberus PRO FC726
Fault of a component
Listed in the fault-message table on the row after System Fault (LED 5), with no LED number of its own. Action: Restart the 'Station'; when the fault is still indicated, exchange the module.
View on the Siemens Fire Safety Cerberus PRO FC726 pageSiemens Fire Safety Cerberus PRO FC726
Line (card) fault
The FC726S or FC726S-10 has detected a line-card, address, C-NET communications/power-line or field-device condition.
View on the Siemens Fire Safety Cerberus PRO FC726 pageSiemens Fire Safety Cerberus PRO FC726
Power supply fault
The FC726S or FC726S-10 has detected a power-supply condition covered by the commissioning guide.
View on the Siemens Fire Safety Cerberus PRO FC726 pageSiemens Fire Safety Cerberus PRO FC726
Remote alarm Fault / Off (LED 8)
Transmission equipment has a 'Fault'. Action: Check remote transmission.
View on the Siemens Fire Safety Cerberus PRO FC726 pageSiemens Fire Safety Cerberus PRO FC726
System Fault (LED 5)
Failure of the main CPU. Action: Visual check of the cable connections; check whether the red LED H37 on the operating unit FCM72xx is on — if so, exchange the PMI & mainboard.
View on the Siemens Fire Safety Cerberus PRO FC726 pageSiemens Fire Safety Cerberus PRO FC726
Topology is invalid
Displayed after a C-NET detector line has been read in, if the topology of that line is invalid (source gives four invalid-topology diagrams: stub on stub or loop interrupted; stub on stub on loop; several stubs…
View on the Siemens Fire Safety Cerberus PRO FC726 page